NA / NB series

Circular VAV and CAV air volume control terminals


Circular VAV and CAV Table of contents
air volume control terminals

Description Page

Type designation 1

Technical data

- General 2

- Specification 3

- Installation instruction 3

Model overview / dimensios 4-5

Sound data NBOA... / NBOB... 6-7

Sound data NAOC... / NBOC... 8-9

Sound data NAOG... / NBOG... / NAON... / NBON... 10 - 11

Sound data NAOJ... / NBOJ... / NAOQ... / NBOQ... 12 -13

Changes w/o notice or obligation


Rev 100422
Circular VAV and CAV Type designation
air volume control terminals NA / NB.....

Composition type designation:

N - B - O - N - E - O - B
N Position 1 : Product group
N = air volume control terminals Ordering example

B Position 2 : Function NBONEOB 1 6 0R 1 0 0 0


A = single wall , circular volume control terminal
See above Model Handing Electric heater
B = double wall , circular volume control terminal 100-400 controls capacity (Watt)
& Heater
1 = non standard , specify separately

O Position 3 : Controls ( manufacturer )


O = without controls
For controls , contact our sales staff

N Position 4 : Outlet
A= rectangular outlet
B= circular outlet
C= 4 circular outlets (' Octopus ')
G= rectangular outlet and provision for
integral hot water reheat coil Ordering codes " Specials "
J = 4 circular outlets and provision for
integral hot water reheat coil N..1... - 3010 = 4 balancing dampers in
N= rectangular outlet and provision for ‘Octopus’ outlet
integral electric reheat coil N..1... - 3006 = ‘Octopus’ with 6 outlets
Q= 4 circular outlets and provision for instead of 4
integral electric reheat coil N..1... - 3016 = ‘Octopus’ with 6 outlets
1 = non standard , specify separately incl. balancing dampers
N..1... - FL = Flange connection 30mm
E Position 5 : Reheat coil
for rectangular outlet
O = without reheat coil
A = 1-row hot water reheat
B = 2-row hot water reheat
4-row hot water reheat Ordering information :
D =
E = 1-stage 230VAC/1-phase electric reheat coil
F = 2-stage 230VAC/1-phase electric reheat coil Standard terminals:
= 3-stage 230VAC/1-phase electric reheat coil - quantity of terminals
G
= 1-stage 400VAC/3-phase electric reheat coil - complete 7 digit code
H
= 2-stage 400VAC/3-phase electric reheat coil - terminal size or model
J
= non standard , specify separately - air volume setting (V m ax , V m in etc)
1
- control handing (standard right side)
O Position 6: Controls ( type & function ) - if applicable, electric reheat coil capacity
O = without controls - supply or return air
For controls, contact our sales staff
Non standard terminals:
B Positon 7: Sensor
O = not applicable - for non standard terminals a full
B = Flo-cross, 2 x 12 point averaging and signal description and / or drawing are
amplifying air flow sensor (standard)
requested .
1 = non standard, specify separately

1
Changes w/o notice or obligation
Rev 100422
Circular VAV and CAV Technical data
air volume control terminals Single wall (NA.....)
Double wall (NB.....)

®
Application ● Flo-Cross , 2 x 12 points Controls:
averaging and signal amplifying Suitable for use with pneumatic,
Types NA and NB are circular airflow sensor, better than 2.5% analogue electronic or DDC
pressure independent VAV and accuracy even with irregular duct controllers. Controls can be
CAV air volume control terminals . approach . factory fitted, wired and calibrated .
The terminals are designed for the ● Maintenance free . Controls enclosure ( galvanised
accurate measurement and sheet steel ) can be provided
control of air volumes coutresy of Technical information optionally .
the patented airflow sensor type
Flo-Cross ®. Casing : Delivery format:
In CAV application, the terminals Single or double wall, air-tight
maintain the required constant construction made of galvanized Delivery format:
airflow independent to the inlet sheet steel with low casing ● The VAV or CAV terminal will be
static pressure. leakage rate. supplied as a single mounting
In VAV application, the terminals assembly.
control the air volume to the room, Insulation : Optional ordered distribution
depending on the cooling load The rectangular discharge section plenum, reheat coil and/or
required thus saving energy is internally insulated . controls are factory fitted, wired
consumption in both cooling and and calibrated. The terminal can
heating applications. Damper : be directly installed and
The VAV or CAV terminals can be Damper blade : made of steel , commissioned when delivered to
used either for supply or return air sandwich construction with twin site.
applications in new or blades and a neoprene gasket with
refurbishment projects. The low leakage . ● Controls location and hot water
terminals have single wall (NA) or Damper shaft : aluminium,Φ or electric connections are as
double wall (NB) construction and 12mm with self lubricating nylon standard fitted on the right hand
can be delivered with a distribution bearings. side of the terminal when looking
plenum and a built-in hot water or in the direction of the airflow .
Flo-Cross : On request, the terminal can be
electric reheat coil.
Extruded aluminium construction delivered with connections on
Features: with nylon core and feet . the left hand side.
● Pressure independent control
Distribution plenum :
functions . ● When terminals are ordered
Made of galvanised sheet steel
● Volume control range 100% to with controls, these will be
with 13 mm internal isolation.
10% . factory fitted, wired and
Plenum with standard rectangular
● Low pressure loss over the calibrated upon request .
or multiple (4 x circular) outlet
terminal .
construction. Optional 1,2,3 or 6
● Single or double wall
circular outlets are possible .
construction.
Outlet spigots are made of
● Factory fitted distribution
galvanised steel and optionally
plenum with built - in hot water
can be provided with volume
or electric reheat coil .
control dampers .
● Oval shaped damper blade for
linear control characteristics . Reheat coil :
● Low leakage damper, less than
Choice of 1, 2 or 4-row hot water
1% of Vnom at 750 Pa . reheat coil or electric reheat coil
● Low noise level .
(230VAC/1-phase or 400VAC/3-
● Suitable for all control functions
phase).
(VAV, CAV, shut-off, etc.) To
maximise system energy savings

2
Changes w/o notice or obligation
Rev 100422
Circular VAV and CAV Technical data
air volume control terminals Single wall (NA.....)
Double wall (NB.....)

Specify as:
Example: Installation Instructions : 5 . Additional manual volume
Supply and install, variable air control
volume terminals with distribution The HC Barcol-Air VAV terminals dampers ( VCD ' s ) before the
plenum and 4 circular outlets, shall be installed using at least unit inlet should not be used.
constructed from galvanized sheet two support channels, with anti- 6 . All connections shall be
steel. The casing leakage rate vibration rubber under the thermally isolated .
shall be classified according to terminal ( as shown in the drawing 7 . Pressure sensing tubes of
class II, VDI3803/DIN24194. The below). Each of these channels FloCross airflow sensor shall
VAV terminals shall have oval shall be fixed with two threaded not be " kinked " or otherwise
shaped damper blade with rods to the ceiling slab obstructed by the external
neoprene gasket and an above . Alternatively 4 duct fixing duct insulation .
aluminium damper shaft with self hooks can be privided for
lubricating nylon bearings. suspending the units . See drawing below.

A centre averaging airflow sensor The installation method :


with at least 2 x 12 test points and 1 . Shall prevent the body of the
amplified signal, type Flo-Cross VAV terminal from high
shall control the airflow with an mechanical tension, which
accuracy better than 2.5%. The could damage the construction
terminals shall be supplied with 1- and performance of the
row hot water reheat coil. terminal .
2 . Shall prevent torsion on the VAV
The controller shall be I / A Series, terminals, which could cause
DDC controller : LonMark malfunction of the damper
compatible, type MNL-V2RVx or blades .
BACnet, type MNB-V2. 3 . Provides some flexibility to the
final location of the VAV
Controls must be factory fitted, terminals .
wired and calibrated according to 4 . Use at least one diameter
the following requirements: straight duct length before the
VAV inlet . suspension bracket for duct (with anti-vibrotion rubber
against vibration and to avoid thermal bridge)
Miximum air volume 250 l/s
Minimum air volume 60 l/s “slip & Drive connections”

Minimum air volume 120 l/s (in


case of reheat)
Terminal size 200 mm
Max. pressure loss 38 Pa
Max. discharge sound index <
NC30 (@250Pa Δp)
Max. radiated sound index < NC30
(@250Pa Δp)

Ordering example : type - model -


handing= NCOJAOB - 200R STANDARD MOUNTING
OPTIONAL MOUNTING

Manufacturer: HC Barcol-Air
anti-vibration rubber inlay
mounting rail M8
ring M8
hexagonal nut M8
theroded end M8 optional: 4 x duct fixing hook contact
HC Barcol-Air for futther details

3
Changes w/o notice or obligation
Rev 100422
Circular VAV and CAV Technical data
air volume control terminals Single wall (NA.....)

Type NAOG.OB Type NAON.OB


Type NAOAOOB

Type NAOH.OB Type NAOP.OB

Type NAOCOOB

Type NAOJ.OB Type NAOQ.OB


Dimensions NA terminals

Other dimensions are avaliable upon request .


Kv values

4
Changes w/o notice or obligation
Rev 100422
Circular VAV and CAV Model overview:
air volume control terminals Double wall type (NB.....)

Type NBOG.OB Type NBON.OB


Type NBOBOOB

Type NBOH.OB Type NBOP.OB


Type NBOCOOB

Type NBOJ.OB Type NBOQ.OB


Dimensions NA terminals

Other dimensions are avaliable upon request .


Kv values

5
Changes w/o notice or obligation
Rev 100422
Circular VAV and CAV Type NAOBOOB
NBOBOOB
air volume control terminals
Sound data Δp = 125 Pa
Δp = 125 Pa
data refering to
discharge sound radiated sound single wall radiated sound double wall
inlet spigot
L w in dB / Oct .( re 1pWLp
) values L w in dB / Oct .( re 1pWLp
) values L w in dB / Oct .( re 1pWLp
) values
min .
Δ Ps
air volume

1. Sound data is determined in a reverberation with the assumptions as mentioned in table 1 for Table 1 : Assumptions for additional attenuation
room at an independent sound laboratory, ceiling plenum and suspended ceiling absorption.
Hz 4K
according to ISO3741 and ISO 5135 standards. 5. Lp values are including a room absorption of 10 125 250 500 1K 2K
Discharge ( dB )
2. Lw in dB/Oct.(re 1pW) are sound power levels for dB/Oct. 5 10 20 30 30 25
Radiated ( dB )
discharge sound and case radiated sound. 6. DB(A), NC and NR index figures are sound 2 5 10 15 15 20
Figures less than 17 dB are indicated by “-”. pressure levels. Figures less than 20 are indicated
3. The discharge sound pressure levels are by “- -”.
determined with the assumptions as mentioned in 7. Δps is static pressure drop across VAV air
table 1 for downstream ductwork including a volume control terminal with damper fully open.
diffuser with insulated plenum box. 8. For non standard applications and/or selections,
4. The radiated sound pressure levels are determined please contatct our technical staff.

6
Changes w/o notice or obligation
Rev 100422
Circular VAV and CAV Type NAOBOOB
NBOBOOB
air volume control terminals
Sound data Δp = 250 Pa
Δp = 250 Pa
data refering to
discharge sound radiated sound single wall radiated sound double wall
inlet spigot
L w in dB / Oct .( re 1pWLp
) values L w in dB / Oct .( re 1pWLp
) values L w in dB / Oct .( re 1pWLp
) values
min .
Δ Ps
air volume

1. Sound data is determined in a reverberation with the assumptions as mentioned in table 1 for Table 1 : Assumptions for additional attenuation
room at an independent sound laboratory, ceiling plenum and suspended ceiling absorption.
Hz 125 250 500 1K 2K 4K
according to ISO3741 and ISO 5135 standards. 5. Lp values are including a room absorption of 10
2. Lw in dB/Oct.(re 1pW) are sound power levels for dB/Oct. Discharge ( dB ) 5 10 20 30 30 25
discharge sound and case radiated sound. 6. DB(A), NC and NR index figures are sound Radiated ( dB ) 2 5 10 15 15 20
Figures less than 17 dB are indicated by “-”. pressure levels. Figures less than 20 are indicated
3. The discharge sound pressure levels are by “- -”.
determined with the assumptions as mentioned in 7. Δps is static pressure drop across VAV air
table 1 for downstream ductwork including a volume control terminal with damper fully open.
diffuser with insulated plenum box. 8. For non standard applications and/or selections,
4. The radiated sound pressure levels are determined please contatct our technical staff.

7
Changes w/o notice or obligation
Rev 100422
Circular VAV and CAV Type NAOCOOB
air volume control terminals NBOCOOB

Sound data Δp = 125 Pa


Δp = 125 Pa
data refering to
discharge sound radiated sound single wall radiated sound double wall
inlet spigot
L w in dB / Oct .( re 1pWLp
) values L w in dB / Oct .( re 1pWLp
) values L w in dB / Oct .( re 1pWLp
) values
min .
Δ Ps
air volume

1. Sound data is determined in a reverberation 5. Lp values are including a room absorption of 10 Table 2 : Insertion Loss
room at an independent sound laboratory, dB/Oct. Model 125 250 500 1K 2K 4K Hz
according to ISO3741 and ISO 5135 standards. 6. DB(A), NC and NR index figures are sound
2. Lw in dB/Oct.(re 1pW) are sound power levels for pressure levels. Figures less than 20 are indicated 100 9 10 11 13 15 15 dB
discharge sound and case radiated sound. by “- -”. 125 8 9 10 12 14 14 dB
Figures less than 17 dB are indicated by “-”. 7. Δps is static pressure drop across VAV air
160 8 9 10 12 14 14 dB
3. The discharge sound pressure levels are volume control terminal with damper fully open.
determined with the assumptions as mentioned in 8. For non standard applications and/or selections, 200 8 8 9 11 13 13 dB
table 1 for downstream ductwork including a please contatct our technical staff. 250 7 8 9 11 13 13 dB
diffuser with insulated plenum box. Table 1 : Assumptions for additional attenuation
4. The radiated sound pressure levels are determined 315 7 8 9 11 13 13 dB
Hz 125 250 500 1K 2K 4K
with the assumptions as mentioned in table 1 for 355 7 8 9 11 13 13 dB
Discharge ( dB ) 5 10 20 30 30 25
ceiling plenum and suspended ceiling absorption.
Radiated ( dB ) 2 5 10 15 15 20 400 7 8 9 11 13 13 dB

8
Changes w/o notice or obligation
Rev 100422
Circular VAV and CAV Type NAOCOOB
air volume control terminals NBOCOOB

Sound data Δp = 250 Pa


Δp = 250 Pa
data refering to
discharge sound radiated sound single wall radiated sound double wall
inlet spigot
L w in dB / Oct .( re 1pWLp
) values L w in dB / Oct .( re 1pWLp
) values L w in dB / Oct .( re 1pWLp
) values
min .
Δ Ps
air volume

1. Sound data is determined in a reverberation 5. Lp values are including a room absorption of 10 Table 2 : Insertion Loss
room at an independent sound laboratory, dB/Oct. Model 125 250 500 1K 2K 4K Hz
according to ISO3741 and ISO 5135 standards. 6. DB(A), NC and NR index figures are sound
2. Lw in dB/Oct.(re 1pW) are sound power levels for pressure levels. Figures less than 20 are indicated 100 9 10 11 13 15 15 dB
discharge sound and case radiated sound. by “- -”. 125 8 9 10 12 14 14 dB
Figures less than 17 dB are indicated by “-”. 7. Δps is static pressure drop across VAV air
160 8 9 10 12 14 14 dB
3. The discharge sound pressure levels are volume control terminal with damper fully open.
determined with the assumptions as mentioned in 8. For non standard applications and/or selections, 200 8 8 9 11 13 13 dB
table 1 for downstream ductwork including a please contatct our technical staff. 250 7 8 9 11 13 13 dB
diffuser with insulated plenum box. Table 1 : Assumptions for additional attenuation
4. The radiated sound pressure levels are determined 315 7 8 9 11 13 13 dB
Hz 125 250 500 1K 2K 4K
with the assumptions as mentioned in table 1 for 355 7 8 9 11 13 13 dB
Discharge ( dB ) 5 10 20 30 30 25
ceiling plenum and suspended ceiling absorption.
Radiated ( dB ) 2 5 10 15 15 20 400 7 8 9 11 13 13 dB

9
Changes w/o notice or obligation
Rev 100422
Circular VAV and CAV Type NAOG.OB NAON.OB
air volume control terminals NBOG.OB NBON.OB

Sound data Δp = 125 Pa


Δp = 125 Pa
data refering to
discharge sound radiated sound single wall radiated sound double wall
inlet spigot
L w in dB / Oct .( re 1pWLp
) values L w in dB / Oct .( re 1pWLp
) values L w in dB / Oct .( re 1pWLp
) values
min .
Δ Ps
air volume

1. Sound data is determined in a reverberation 5. Lp values are including a room absorption of 10 Table 2 : Insertion Loss
room at an independent sound laboratory, dB/Oct. Model 125 250 500 1K 2K 4K Hz
according to ISO3741 and ISO 5135 standards. 6. DB(A), NC and NR index figures are sound
2. Lw in dB/Oct.(re 1pW) are sound power levels for pressure levels. Figures less than 20 are indicated 100 3 4 6 11 10 12 dB
discharge sound and case radiated sound. by “- -”. 125 3 4 6 11 10 12 dB
Figures less than 17 dB are indicated by “-”. 7. Δps is static pressure drop across VAV air
160 2 6 10 10 10 11 dB
3. The discharge sound pressure levels are volume control terminal with damper fully open.
determined with the assumptions as mentioned in 8. For non standard applications and/or selections, 200 2 5 10 10 10 11 dB
table 1 for downstream ductwork including a please contatct our technical staff. 250 2 5 10 11 10 10 dB
diffuser with insulated plenum box. Table 1 : Assumptions for additional attenuation
4. The radiated sound pressure levels are determined 315 1 4 9 10 10 10 dB
Hz 125 250 500 1K 2K 4K
with the assumptions as mentioned in table 1 for 355 1 4 9 10 10 10 dB
Discharge ( dB ) 5 10 20 30 30 25
ceiling plenum and suspended ceiling absorption.
Radiated ( dB ) 2 5 10 15 15 20 400 1 3 9 10 10 10 dB

10
Changes w/o notice or obligation
Rev 100422
Circular VAV and CAV Type NAOG.OB NAON.OB
air volume control terminals NBOG.OB NBON.OB

Sound data Δp = 250 Pa


Δp = 250 Pa
data refering to
discharge sound radiated sound single wall radiated sound double wall
inlet spigot
L w in dB / Oct .( re 1pWLp
) values L w in dB / Oct .( re 1pWLp
) values L w in dB / Oct .( re 1pWLp
) values
min .
Δ Ps
air volume

1. Sound data is determined in a reverberation 5. Lp values are including a room absorption of 10 Table 2 : Insertion Loss
room at an independent sound laboratory, dB/Oct. Model 125 250 500 1K 2K 4K Hz
according to ISO3741 and ISO 5135 standards. 6. DB(A), NC and NR index figures are sound
2. Lw in dB/Oct.(re 1pW) are sound power levels for pressure levels. Figures less than 20 are indicated 100 3 4 6 11 10 12 dB
discharge sound and case radiated sound. by “- -”. 125 3 4 6 11 10 12 dB
Figures less than 17 dB are indicated by “-”. 7. Δps is static pressure drop across VAV air
160 2 6 10 10 10 11 dB
3. The discharge sound pressure levels are volume control terminal with damper fully open.
determined with the assumptions as mentioned in 8. For non standard applications and/or selections, 200 2 5 10 10 10 11 dB
table 1 for downstream ductwork including a please contatct our technical staff. 250 2 5 10 11 10 10 dB
diffuser with insulated plenum box. Table 1 : Assumptions for additional attenuation
4. The radiated sound pressure levels are determined 315 1 4 9 10 10 10 dB
Hz 125 250 500 1K 2K 4K
with the assumptions as mentioned in table 1 for 355 1 4 9 10 10 10 dB
Discharge ( dB ) 5 10 20 30 30 25
ceiling plenum and suspended ceiling absorption.
Radiated ( dB ) 2 5 10 15 15 20 400 1 3 9 10 10 10 dB

11
Changes w/o notice or obligation
Rev 100422
Circular VAV and CAV Type NAOJ.OB NAOQ.OB
air volume control terminals NBOJ.OB NBOQ.OB

Sound data Δp = 125 Pa


Δp = 125 Pa
data refering to
discharge sound radiated sound single wall radiated sound double wall
inlet spigot
L w in dB / Oct .( re 1pWLp
) values L w in dB / Oct .( re 1pWLp
) values L w in dB / Oct .( re 1pWLp
) values
min .
Δ Ps
air volume

1. Sound data is determined in a reverberation 5. Lp values are including a room absorption of 10 Table 2 : Insertion Loss
room at an independent sound laboratory, dB/Oct. Model 125 250 500 1K 2K 4K Hz
according to ISO3741 and ISO 5135 standards. 6. DB(A), NC and NR index figures are sound
2. Lw in dB/Oct.(re 1pW) are sound power levels for pressure levels. Figures less than 20 are indicated 100 13 17 23 26 28 30 dB
discharge sound and case radiated sound. by “- -”. 125 12 15 22 25 27 29 dB
Figures less than 17 dB are indicated by “-”. 7. Δps is static pressure drop across VAV air
160 12 15 22 25 27 29 dB
3. The discharge sound pressure levels are volume control terminal with damper fully open.
determined with the assumptions as mentioned in 8. For non standard applications and/or selections, 200 11 15 21 24 26 28 dB
table 1 for downstream ductwork including a please contatct our technical staff. 250 11 15 21 24 26 28 dB
diffuser with insulated plenum box. Table 1 : Assumptions for additional attenuation
4. The radiated sound pressure levels are determined 315 8 11 21 24 26 26 dB
Hz 125 250 500 1K 2K 4K
with the assumptions as mentioned in table 1 for 355 8 11 21 24 26 26 dB
Discharge ( dB ) 5 10 20 30 30 25
ceiling plenum and suspended ceiling absorption.
Radiated ( dB ) 2 5 10 15 15 20 400 8 11 21 24 26 26 dB

12
Changes w/o notice or obligation
Rev 100422
Circular VAV and CAV Type NAOJ.OB NAOQ.OB
air volume control terminals NBOJ.OB NBOQ.OB

Sound data Δp = 250 Pa


Δp = 250 Pa
data refering to
discharge sound radiated sound single wall radiated sound double wall
inlet spigot
L w in dB / Oct .( re 1pWLp
) values L w in dB / Oct .( re 1pWLp
) values L w in dB / Oct .( re 1pWLp
) values
min .
Δ Ps
air volume

1. Sound data is determined in a reverberation 5. Lp values are including a room absorption of 10 Table 2 : Insertion Loss
room at an independent sound laboratory, dB/Oct. Model 125 250 500 1K 2K 4K Hz
according to ISO3741 and ISO 5135 standards. 6. DB(A), NC and NR index figures are sound
2. Lw in dB/Oct.(re 1pW) are sound power levels for pressure levels. Figures less than 20 are indicated 100 13 17 23 26 28 30 dB
discharge sound and case radiated sound. by “- -”. 125 12 15 22 25 27 29 dB
Figures less than 17 dB are indicated by “-”. 7. Δps is static pressure drop across VAV air
160 12 15 22 25 27 29 dB
3. The discharge sound pressure levels are volume control terminal with damper fully open.
determined with the assumptions as mentioned in 8. For non standard applications and/or selections, 200 11 15 21 24 26 28 dB
table 1 for downstream ductwork including a please contatct our technical staff. 250 11 15 21 24 26 28 dB
diffuser with insulated plenum box. Table 1 : Assumptions for additional attenuation
4. The radiated sound pressure levels are determined 315 8 11 21 24 26 26 dB
Hz 125 250 500 1K 2K 4K
with the assumptions as mentioned in table 1 for 355 8 11 21 24 26 26 dB
Discharge ( dB ) 5 10 20 30 30 25
ceiling plenum and suspended ceiling absorption.
Radiated ( dB ) 2 5 10 15 15 20 400 8 11 21 24 26 26 dB

13
Changes w/o notice or obligation
Rev 100422