Professional Documents
Culture Documents
2009. 7, 2: 95-114
Keywords: Tall building; passive damper; semi-active control; double friction; wind load
1. Introduction
Various structural control methods like pas- wind excitations [1]. The wind excited bench-
sive control, active control, semi-active con- mark building is a 76-storey, 306 m concrete
trol and hybrid control have been studied on office tower proposed for the city of Mel-
different buildings for different dynamic loads. bourne, Australia. The building is tall and
Significant progress has also been made in the slender with a height to width ratio of 7.3;
area of structural control. Some of the control hence it is wind sensitive. Wind tunnel tests [2]
methods have been implemented for real for the 76-storey building model have been
structures. However, to streamline and focus conducted at the University of Sydney and the
the study of structural control on the same results of across-wind data are provided for
building with the same load, the concept of the analysis of the benchmark problem.
benchmark problems has come into picture. Performance of various dampers like tuned
Therefore, based on realistic full scale build- liquid column dampers [3], liquid column vi-
ings, two structural control benchmark prob- bration absorbers [4], hybrid viscous-tuned
lems have been proposed for earthquake and liquid column damper [5], variable stiffness
*
Corresponding author; e-mail: rsjangid@civil.iitb.ac.in Accepted for Publication: January 8, 2010,
© 2010 Chaoyang University of Technology, ISSN 1727-2394
tuned mass damper [6] on the benchmark structural responses, of connected adjacent
building have been studied. Patil and Jangid structures is investigated. They also con-
(2009) [7] studied the response of the bench- ducted a parametric study to investigate the
mark building with the various arrangements optimum slip force of the damper. In addition,
of linear viscous dampers and SAVFDs by the authors studied the optimal placement of
connecting them to alternative floors of the dampers. So far the conventional dampers
building. have been used to control the vibration of the
A typical friction damper usually consists of structures. Bhaskararao and Jangid (2006b)
a frictional sliding interface and a clamping studied the dynamic response of two adjacent
mechanism that produces normal contact single story building structures connected
force on the interface. Bhaskararao and Jangid with a friction damper under harmonic ground
(2006a) proposed two numerical models to excitation [9]. Here, an attempt is made to
evaluate the frictional force in the connected enhance the performance of friction dampers
dampers for multi-degree of freedom (MDOF) by providing an additional plate (Figure 1)
structures and validated with the results ob- between the two existing plates and make an
tained from the analytical model considering additional interface available to resist the ex-
an example of single degree of freedom ternal loads.
(SDOF) structures [8]. Further, the effective-
ness of dampers in terms of the reduction of
Figure 1. Schematic and mathematical models of conventional and double friction dampers
Further, to improve the performance of pas- The control by semi-active friction dampers
sive dampers semi-active dampers are pro- requires a feedback control algorithm and
posed in the literature. A semi-active friction on-line measurement of structural response in
damper is able to adjust its slip force by con- order to determine the appropriate level of
trolling its clamping force in real-time, de- adjustable clamping forces of the dampers.
pending on the structure’s motion during an Akbay and Aktan (1995) [10] proposed the
earthquake. This adaptive nature makes a control algorithm that determines the clamp-
semi-active friction damper more efficient. ing force at the next time step. Other proposed
control laws include the bang-bang control Thus, the need of the present study is to
[11], modulated homogenous control (Inaudi, evaluate the enhancement in the performance
1997) [12], linear quadratic regulator [13], of double friction dampers and SAVDFDs as
friction-force incremental control [14], modal compared to their conventional counterparts
control (Lu and Chung, 2001; Lu, 2004a) on the wind excited benchmark building sub-
[15,16], predictive control [17], modal and jected to across wind loads. The specific ob-
optimal control [18]. jectives of the present study may be summa-
Kori and Jangid (2008) [19] studied the per- rized as:(i) to study the improvement in the
formance of SAVFDs by placing them at performance of wind excited benchmark
various floors of multi-storey buildings using building with the proposed double friction
predictive control law. Predictive control al- dampers and SAVDFDs, as compared to their
gorithm is able to keep the friction force of a conventional counterparts installed in all the
semi-active friction damper slightly lower floors, (ii) to study the reduction in the num-
than the critical friction force, so that the ber of double friction dampers compared to
damper is kept continuously slipping to avoid conventional friction dampers both at their
the unwanted high frequency structural re- optimized locations, to achieve the perform-
sponse which would have been produced in ance criteria comparable to those obtained
passive friction dampers. This results in better with the conventional friction dampers in-
energy dissipation. The method is formulated stalled in all the floors, (iii) to study the re-
in a discrete-time domain and cast in the form duction in the number of SAVDFDs as com-
of direct output feedback for easy control im- pared to SAVFDs both at their optimized lo-
plementation. Thus investigation on predic- cations, to achieve the performance criteria
tive control algorithm method was focused on comparable to those obtained with the
predicting the critical friction force, but with a SAVFDs installed in all the floors and (iv) to
single sliding surface for each damper. optimize the slip force of conventional fric-
By providing an additional friction pad (Fig- tion dampers and double friction dampers at
ure 2) on the inner side of the clamping their optimized location and numbers.
mechanism of a SAVFD an additional resist-
ing interface is brought into use with the same 2. Benchmark Building
clamping mechanism, thus enhancing the re-
sisting frictional force. This is how a SAVFD The wind excited benchmark building is a
is converted into a semi-active double friction 76-storey 306 m office tower proposed for the
damper (SAVDFD). This SAVDFD is used to city of Melbourne, Australia. The plan and
study the performance of wind excited elevation are shown in Figure 3. The building
benchmark building. is a reinforced cement concrete building con-
Optimization of location and number of sisting of a concrete core and concrete frame.
dampers is also carried out by adopting a se- The mass density of the building is 300 kg per
quential search procedure [20] with the help cubic meter. The building is slender with a
of a controllability index which is obtained height-to-width ratio of 306.1/42=7.288; there
with the help of RMS value of inter-storey fore, it is wind sensitive.
drift.
Figure 2. Schematic and mathematical models of SAVFD and SAVDFD (Modified after Kori and Jan-
gid,2008)
The outer dimension for the central rein- element model (FEM) is constructed. The 76
forced concrete core is 21m×21m. The 24 rotational degrees of freedom have been re-
columns on the periphery of the building are moved by the static condensation. This results
distributed equally on each of the four sides in 76 degrees of freedom, representing the
of the building. These columns are connected displacement of each floor in the lateral direc-
to a 900 mm deep and 400 mm wide beam on tion. The mass matrix M and stiffness matrix
each floor. The lightweight floor construction K each of order (76×76) are constructed for
is made up of steel beams with a metal deck the FEM model of the building and provided
and a 120 mm slab. The compressive strength for the analysis. The first five natural fre-
of concrete is 60 MPa and the modulus of quencies of the model are 0.16, 0.765, 1.992,
elasticity is 40 GPa. Column sizes, core wall 3.790, and 6.395 Hz. ζ = 1% is assumed for
thickness, and floor mass are varying along the first five modes to construct the
the height. The building has six plant rooms. damping matrix C of order (76×76) using
The building is modeled as a vertical cantile- Rayleigh’s approach [1].
ver beam (Bernoulli–Euler beam). The por- The performance criteria (J1-J12) defined
tion of the building between adjacent floors is for the building is given in Table 1.
considered as a classical beam and the finite
Performance
Expression
Criteria
J1 max(σ &&x1 , σ &&x 30 , σ &&x 50 , σ &&x 55 , σ &&x 60 , σ &&x 65 , σ &&x 70 , σ &&x 75 ) / σ &&x 75 o
1
J2 ∑ (σ &&xi / σ &&xio ) ; for i =50, 55, 60, 65, 70, and 75
6 i
J3 σ x 76 / σ x 76o
1
J4
7 ∑σi
xi / σ xio ; for i=50,55,60,65,70,75 and 76
J5 σ xm / σ x 76o
⎧⎪ 1 T ⎫
∫ [ x&m (t ) u (t )] dt ⎪⎬
2
J6 σp = ⎨
⎪⎩ T 0 ⎪⎭
J7 max ( &&
x p1 , &&
x p 30 , &&
x p 50 , &&
x p 55 , &&
x p 60 , &&
x p 65 , &&
x p 70 , &&
x p 75 ) / &&
x p 75o
1
J8
6 i
∑ &&x pi / &&x pio ; for i = 50, 55, 60, 65, 70, and 75
J9 x p 76 / x p 76 o
1
J10
7 i
∑ x pi / x pio ; for i = 50, 55, 60, 65, 70, 75, and 76
J11 x pm / x p 76 o
J12 Pmax = max x&m (t )u (t )
dZi n-1 n
q = A( x&i 2 − x&i1 ) − β ( x&i 2 − x&i1 ) Zi Zi −τ ( x&i 2 − x&i1 ) Zi
dt (1.a)
where, q is the yield displacement; its slip force by controlling its clamping force
β ,τ , n and A are non-dimensional parame- in real-time in response to a structure’s mo-
ters of the hysteretic loop. The parameters tion during a wind. Because of this adaptive
β ,τ , n and A control the shape of the loop nature, a semi-active friction damper is ex-
and are selected such as to provide a pected to be more effective than a passive
rigid-plastic behavior (typical Cou- damper. On the other hand, just like in active
lomb-friction behavior). The recommended structural control, the control of semi-active
values for the above parameters are: q = 0.1 friction dampers requires a feedback control
mm, A = 1, β = 0.5, τ = 0.5 and n = 2. The algorithm and online measurement of struc-
hysteretic displacement component, Zi is tural response in order to determine the ap-
bounded by its peak values of ±1 to account propriate level of adjustable clamping forces
of the dampers. Nevertheless, a semi-active
for the conditions of sliding and non-sliding
control device generally has the following
phases.
advantages over an active control one (i) be-
And for a SAVDFD, as the number of inter-
cause the control action is carried out by ad-
faces is 2, the frictional forces developed in
justing the internal mechanism (i.e., the
the dampers are modified as
clamping force for a semi-active friction
damper), the required control stroke and en-
f di = 2 f si Z i for ( i =1 − r ) ergy can be very small; and (ii) because it
(1.b)
does not pump energy into the controlled
2.2 Semi-Active Variable Double Friction structures, control instability can be prevented.
Damper As already mentioned, the control of
semi-active dampers requires a control algo-
In order to improve the performance of fric- rithm. Needless to say, the control perform-
tion dampers, the concept of semi-active con- ance of the semi-active dampers significantly
trol is introduced to the dampers. A relies on the control algorithm applied. One of
semi-active friction damper is able to adjust the recent control laws “predictive control
%u[k ] = G z z[k − 1] + G u u[ k − 1] + G w F[ k − 1] ⎡ 0 ⎤ ⎡ 0 ⎤
(2) B= ⎢ -1 ⎥ ; E= ⎢ -1 ⎥ (2.h)
⎣M Λ ⎦ ⎣M ⎦
The physical meaning of the ith element
Let y be a vector listing all damper elonga-
u%i [k] in the vector %u[k] is the minimum
tions (deformations) that are equal to the
friction force required by the ith damper at kth drifts of the stories on which the dampers are
time step, in order to keep the damper in its installed. At any given instant in time, the re-
stick state (or prevent the damper from enter- lation between y and the state of the structure
ing the slip state). By applying a normal force z may be written as
N i [k ] for ith damper such that the resulting
slip force is slightly less than the value u%i [k ] y[k ] = Dz[k ] (2.i)
predicted by equation (2) the damper can be
brought into slip state. For a SAVDFD, the number of interface
available is 2; the control force offered by ith
u%i [ k ] device is given by,
N i [ k ]= R f 0 ≤ R f < 1 (for i =1- r ) (2.a)
μ u i [k ] = 2R f u% i [k ]
(2.j)
Thus, the control force vector when all the
dampers are brought into slip state is given 2.3 Governing Equations of Motion
by,
u[k ]= R f u% [k ] The governing equation of motion for the
(2.b) controlled building structure model sub-
jected to wind excitations can be written as
where, Rf is a gain multiplier defined as
the ratio of damper force to critical damper Mx
&& + Cx& + Kx + Λu = F (3)
control force and plays an important role in
the present control law. where x is displacement vector, x& and && x
where,
the first and second time derivatives, M, C
and K are mass, damping and stiffness matri-
G z = K b D( A d − I) (2.c) ces respectively; u=[fd1, fd2, ….fdr]T and F
are control force vector and wind load vec-
G u = K b DB d + I (2.d) tor respectively; Λ is a matrix of zeros and
ones, where 1 will indicate where the damper
force is being applied.
G w = K b DEd (2.e)
z& = Az + Bu + EF (4)
After being multiplied by the factor Rf, these
matrices may also be treated as the control where z is the state vector of structure, and
gains. where, contains displacement and velocity of each
floor; A denotes the system matrix composed
B d = A −1 ( A d − I )B (2.f) of structural mass, damping and stiffness ma-
trices; B represents the distributing matrices 150 kN. The performance of SAVDFDs using
of the control forces; and E represents the predictive control law installed in all the
distributing matrices for excitation. floors with complete state feedback is also
The Equationn (3) is discretized in the time investigated. In case of SAVFDs and
domain and excitation force is assumed to be SAVDFDs stiffness of bracing in each floor is
constant within any time interval and can be maintained as 8.94e6 kN/m. Each semiactive
written into a discrete-time form [17]. friction damper is a bundle of 4 dampers.
Wind tunnel tests [2] for the benchmark build-
z[k +1]=A d z[k] + B d u[k] + Ed F[k] ing model have been conducted at the Uni-
(5)
versity of Sydney and the results of
across-wind data for a duration of 3600 s is
where Ad = eAΔt represents the discrete time
provided for the analysis of the benchmark
system matrix with Δt as the time interval.
problem. However, in the present study the
performance of dampers is studied for dura-
3. Numerical Study
tion of 900 s. The time history and frequency
content of across wind load at top floor of the
The efficiency of double friction dampers
building is shown in Figure 5. The response
installed in all the floors (Figure 4) of the
quantities and performance criteria of the
benchmark building is investigated. The slip
benchmark building are studied.
force of each friction damper is maintained as
The comparison of peak response quantities Table 2. Peak displacement quantities have
with the conventional friction dampers and reduced with the double friction dampers as
double friction dampers installed at all the compared to those with the conventional fric-
floors and at optimized locations is given in tion dampers. Peak acceleration quantities
have significantly reduced. The reductions in conventional friction dampers. However, with
peak quantities are further improved at opti- the proposed double friction dampers, the im-
mized locations. Thus, with the double fric- provement against acceleration is better than
tion dampers, the performance of the building that against displacement.
has improved as compared to that with the
Figure 5. Comparison of frequency response and time variation of wind load at top floor of the benchmark
building
Table 2. Peak response quantities of the benchmark building installed with friction dampers
† Conventional friction dampers in all the floors †† Double friction dampers in all the floors
‡ Conventional friction dampers, optimized ‡‡ Double friction dampers, optimized
Table 3. RMS response quantities of the benchmark building installed with friction dampers
† Conventional friction dampers in all the floors †† Double friction dampers in all the floors
‡ Conventional friction dampers, optimized ‡‡ Double friction dampers, optimized
Table 4. Performance criteria of the benchmark building installed with friction dampers
Number of Dampers
Criteria 76† 76†† 47 ‡ 24 ‡‡
J1 0.437 0.312 0.463 0.458
J2 0.431 0.304 0.452 0.447
J3 0.561 0.473 0.571 0.567
J4 0.564 0.477 0.575 0.571
J7 0.483 0.377 0.544 0.540
J8 0.484 0.400 0.530 0.525
J9 0.678 0.653 0.689 0.685
J10 0.682 0.663 0.694 0.690
† Conventional friction dampers in all the floors †† Double friction dampers in all the floors
‡ Conventional friction dampers, optimized ‡‡ Double friction dampers, optimized
The peak quantities obtained with SAVFDs reductions in RMS quantities are seen with
and SAVDFDs installed in all the floors and at the proposed SAVDFDs. With dampers at op-
their optimized locations are presented in Ta- timized locations, the reductions are signifi-
ble 5. Similar to the trend shown by passive cantly high. Again with the proposed
friction dampers peak quantities have consid- SAVD-FDs improvement in the performance
erably reduced with SAVDFDs as compared against acceleration is better than that against
to those with SAVFDs. With dampers at opti- displacement. And, from Table 7, perform-
mized locations the enhancement in the per- ance criteria which depend on acceleration
formance is significantly high. The reductions quantities (J1, J2, J7 & J8) have reduced more
in peak acceleration quantities are more than than those (J3,J4,J9 & J10) which depend
those in peak displacement quantities. on displacement quantities.
From Table 6, it can be seen that similar to
the trend shown by passive friction dampers
Comparisons of time histories as well as fre- SAVFDs and SAVDFDs installed in all the
quency responses of displacement and accel- floors are made in Figures 8 and 9 respec-
eration quantities of the 76th floor with the tively. Displacement and acceleration quanti-
proposed double friction dampers and the ties of the 76th floor have considerably re-
conventional passive friction dampers in- duced with SAVDFDs as compared to those
stalled in all the floors are shown in Figures 6 with SAVFDs. The amplitude of both dis-
and 7 respectively. The displacement and ac- placement and acceleration frequency re-
celeration quantities have considerably re- sponses with both double friction dampers
duced with double friction dampers than those and SAVDFDs are reduced as compared to
with conventional friction dampers. The their conventional counter parts, correspond-
comparisons of time histories as well as fre- ing to the frequency of 0.16 which is the fun-
quency responses of displacement and accel- damental frequency of the benchmark builing.
eration quantities of the 76th floor with
Table 6. RMS response quantities of the benchmark building installed with variable friction dampers
Table 7. Performance criteria of the benchmark friction damper at the 76th floor for different
building with variable friction dampers arrangements of dampers. For both the ar-
rangements i.e. when dampers in all floors
Number of Dampers
Criteria †
and at optimized locations the energy dissi-
76 76†† 28‡ 14‡‡ pated by the double friction damper is sig-
J1 0.491 0.364 0.518 0.485 nificantly higher than the conventional fric-
tion damper. Same observations can be made
J2 0.491 0.364 0.519 0.485
with the hysteresis loops of SAVFD and
J3 0.614 0.535 0.632 0.610 SAVDFD at 76th floor shown in Figure 11.
J4 0.616 0.537 0.634 0.612 Thus, it is evident from the above observa-
tions that both the proposed dampers (double
J7 0.499 0.359 0.519 0.484 friction damper and SAVDFD) give better
J8 0.504 0.366 0.527 0.492 performance against displacement as well as
acceleration as compared to their conven-
J9 0.731 0.669 0.743 0.726
tional counterparts. In both the proposed
J10 0.740 0.678 0.751 0.734 dampers, the improvement in the performance
against acceleration is better than that against
†
SAVFDs in all the floors displacement.
††
SAVDFDs in all the floors
‡
SAVFDs, optimized 3.1 Optimization of Location of Dampers
‡‡
SAVDFDs, optimized
After studying the performance of the pro-
With both the modified dampers reductions posed dampers in all the floors, optimization
in accelerations is better than the displace- of location and number of dampers is carried.
ments. Figure 10 shows the hysteresis loops Shukla and Datta (1999) [20] studied the op-
of conventional friction damper and double timal use of visco-elastic dampers (VEDs) in
Figure 6. Comparison of frequency response and Figure 8. Comparison of frequency response and
time variation of displacement of top time variation of displacement of top
floor with friction dampers installed in all floor with semi ative friction dampers in-
the floors stalled in all the floors
Figure 7. Comparison of frequency response and Figure 9. Comparison of frequency response and
time variation of acceleration of top floor time variation of acceleration of top floor
with friction dampers installed in all the with semi active friction dampers in-
floors stalled in all the floors
Figure 10. Hysteretic loops for friction damper at the top floor
Figure 11. Hysteretic loops for semi-active friction damper at the top floor
Each damper is successively installed in the building is significantly enhanced with both
storey where the inter-storey drift is maxi- the proposed dampers at their optimized loca-
mum. This is done with a view that a damper tions.
is optimally located if it is placed in the storey
in which the displacement (or relative dis- 3.2 Parametric Study
placement) of the uncontrolled (or modified)
structure is largest. This procedure is repeated A parametric study is carried out with both
until the required level of performance is conventional friction dampers (47 number)
achieved. and double friction dampers (24 number)
Optimization of location of double friction installed at their optimized locations (as ex-
dampers and conventional friction dampers is plained in section 3.1), by varying slip force
carried out till the performance criteria are in the range of 150 to 2000 kN. Then plots of
comparable to those obtained with the con- various performance criteria against slip force
ventional friction dampers installed in all the are shown in Figures 16 and 17. It is observed
floors. From Table 4, it is seen that at opti- at optimized locations the number of double
mized locations, only 24 double friction friction dampers is half of the conventional
dampers are sufficient to achieve the per- friction dampers to achieve the same values of
formance criteria comparable to those ob- criteria at every slip force. The values of J1
tained with the conventional friction dampers and J2 initially decrease attain a least value
installed in all the floors, whereas, 47 con- and then increase with the increase in slip
ventional friction dampers are required to force. Thus, there is an optimum value of slip
achieve the same performance criteria. force for the performance criteria J1 and J2.
From Figures 12 and 13, it is seen that at the The optimum value of slip force for J1 is 825
optimized locations, 24 double friction damp- kN and that for J2 is 725 kN. Similar behav-
ers give displacement and acceleration values iour is observed for the performance criteria
comparable to those obtained with 47 conven- J7 and J8. The optimum slip force for J7 and J8
tional friction dampers. Similar results are is 1150 kN. For J3, J4, J9 and J10 there is no
obtained with the SAVDFDs also (Figures 14 optimum value of slip force as such. However,
and 15). This achievement of similar per- it is seen that the larger the value of slip
formance with only half the number of both forces the smaller the values of J3, J4, J9 and
the proposed dampers is confirmed in the re- J10.
spective frequency responses. Thus, at the op-
timized locations, both the proposed dampers 4. Conclusions
give 50% improved performance as compared
to their conventional counterparts. The opti- Numerical study of wind excited benchmark
mized location and number of friction damp- building with modified friction dampers
ers is shown in Figure 4. The optimized loca- (double friction damper and SAVDFDs) is
tions of friction dampers (both conventional carried out under the deterministic wind load.
and double friction dampers) are between 71 The comparison of the response quantities/
to 76th floors. And, the optimized location of performance criteria is made with those ob-
all the semi-active variable friction dampers tained with their conventional counterparts to
(both SAVFDs and SAVDFDs) is at 76th floor. verify the effect of the modified dampers.
Thus, the performance of the benchmark
Figure 13. Comparison of frequency response and Figure 15. Comparison of frequency response and
time variation of acceleration of top time variation of acceleration of top
floor with friction dampers installed at floor with semi active friction dampers
optimized locations installed at optimized locations
Figure 16. Variation of performance criteria (J1-J4) with slip force for the optimized location of friction da-
mpers
Figure 17. Variation of performance criteria (J7-J10) with slip force for the optimized location of friction
dampers
Optimization of location of both conven- installed with passive friction dampers (both
tional and modified dampers is also carried conventional and double friction damper) at
out and the results are compared. Addition- their optimized locations. From the trends of
ally a parametric study is carried out to criti- the numerical results of the present study, the
cally examine the performance of the building following conclusions may be drawn:
Coefficient matrices
time step
C matrix
y[k ] Vector of drifts between the stories
D System matrix
E Distributing matrices for excitation to which the dampers are connected
z State space vector
Ed Coefficient matrices χ ( L) Controllability index
f di th
Damper force of i damper σp
f si th RMS control power
Slip force of i friction damper σ x ( L) RMS value of inter-storey drift of