You are on page 1of 1

Project: ETAP Page: 1

16.1.1C
Location: Date: 02-22-2018

Contract: SN: TATASTEEL6

Engineer: Revision: Base


Study Case: MS
Filename: TCC SLD 120118 Config.: Normal

% Alert Settings

Critical Marginal
Starting Motors/MOV

MOV Terminal Voltage 80.00 90.00 (Vmtr, rate)

Motor Terminal Voltage 80.00 90.00 (Vmtr, rate)

Failed to Start, Slip Kept 5.00

Generator/Engine/Exciter Rating Min. Span (Sec.)


Generator Rating 100.00 95.00 0.00

Engine Continuous Rating 100.00 95.00 0.00

Engine Peak Rating 100.00 95.00 0.00

Exciter Peak Rating 100.00 95.00 0.00

Bus Voltage Group Min. Dip Width (Sec.)


Starting Motor Bus VBus 80.00 90.00 0.00

Grid/Generator Bus VBus 92.00 95.00 0.00

HV Bus, kV 10.00 VBus 90.00 95.00 0.00


MV Bus, 10.00 kV 1.00 VBus 90.00 95.00 0.00

LV Bus, kV 1.00 VBus 90.00 95.00 0.00

Marginal Alert Report


DeviceID Type Alert Condition Rating/Limit Unit Operating % Operating T Begin Duration

Bus3 MV Bus Bus Voltage Under Voltage 6.900 kV 6.517 94.5 15.000 0.000

Bus4 MV Bus Bus Voltage Under Voltage 6.900 kV 6.506 94.3 15.000 0.000

Bus5 MV Bus Bus Voltage Under Voltage 6.900 kV 6.519 94.5 15.000 0.000

Bus10 MV Bus Bus Voltage Under Voltage 6.900 kV 6.468 93.7 15.000 0.000

Bus11 MV Bus Bus Voltage Under Voltage 6.900 kV 6.511 94.4 15.000 0.000

Bus12 MV Bus Bus Voltage Under Voltage 6.900 kV 6.504 94.3 15.000 0.000

Bus13 MV Bus Bus Voltage Under Voltage 6.900 kV 6.510 94.3 15.000 0.000

Bus21 LV Bus Bus Voltage Under Voltage 0.433 kV 0.411 94.8 15.000 0.000

Bus27 MV Bus Bus Voltage Under Voltage 6.900 kV 6.510 94.3 15.000 0.000