You are on page 1of 14

Instruction Sheet

C503a 12-2003

Installation Instructions for


Bus PT Module Kit 300-4767
GENERAL INFORMATION make sure that proper phasing of the sensing leads
is maintained.
WARNING Incorrect installation or parts re-
placement can result in severe personal injury, PowerCommand paralleling generator sets may in-
death, and/or equipment damage. Service per- corporate a 300−4309 Bus PT Module or the
sonnel must be trained and experienced to per- 300−4985 Bus PT Module with First Start Sensor in-
form electrical and mechanical service. cluded in this kit. The 300−4985 module may be
used in systems with 300−4309 modules, simply by
This kit can be used in the following situations:
connecting the 300−4985 in the same way as the
• Upgrade the PowerCommand Control existing 300−4309 modules.
(PCC) with the PowerCommand Digital Par-
alleling control. Review the installation in- The First Start Sensor system prevents simulta-
structions for each kit to become familiar with neous closing of generator set breakers on to a
the safety precautions and installation proce- dead bus during black start conditions.
dures before starting. Begin the modification
with Digital Board EPROM kit 300−4721 (In- Note that there are four distinct versions of Bus PT
struction Sheet C499), followed by Paralleling Modules. The proper module for each application is
Control kit 300−4883 (Instruction Sheet determined by the primary side line-to-neutral volt-
C514), and then this Bus PT Module kit and age that the module is designed to support. Select a
Rail Mount kit 300−4765 (Instruction Sheet module suitable for the operating voltage range
C501) or 300−4766 (Instruction Sheet C502). where it will be used. The table below lists the oper-
ating voltage range for the four kits covered by this
• Upgrade a current paralleling generator set instruction sheet.
to include an integrated first start sensor
function.
Kit Volts Line-to-Line
• Replace a failed Bus PT Module.
300−4767−01 0 − 300V
The primary function of the Bus PT Module is to pro- 300−4767−02 301 − 480V
vide a synchronizing reference voltage to the PCC
so that a generator set can be safely paralleled to an 300−4767−03 600V
energized system bus. The Bus PT transforms the 300−4767−04 Special
primary voltage sensed (up to 600 VAC) to a nomi-
nal 18 VAC level required by the control. Higher volt- The modules normally sense line-to-line voltages
age systems are managed by using a PT to drop the and are applied in 3-phase/4-wire systems. Howev-
sensing voltage to a level less than 600V, so that the er, if a 3-phase/3-wire system is required, the
Bus PT Module can safely sense it. In these situa- neutral wire to the control from the Bus PT Mod-
tions, it is especially important that care be taken to ule must be disconnected.

PowerCommand is a registered trademark of Cummins Inc.

Page 1 of 14
FUNCTION AND INTERCONNECTION OF source for the first start logic of the Bus PT Module
THE BUS PT WITH A FIRST START comes from the genset battery.
SENSOR
Black Start Sequence (summary):
The Bus PT Module receives the ready to load sig- 1. Gensets start – Bus PT Modules receive ready
nal from the PCC. The PCC receives the first start to load signals.
signal from the Bus PT Module if the PCC is to be
the first genset to connect to the dead bus. The Bus 2. Bus PT Modules arbitrate to select which unit to
PT Module has inhibit lines which are daisy chained go on-line first.
between the modules. When the modules receive 3. One genset wins arbitration and provides a first
the “ready to load” signals from their PCC controls, start signal to its PCC; other modules are inhib-
the modules arbitrate, using the inhibit line to deter- ited.
mine which unit is allowed to close its breaker. The 4. The PCC that receives the first start signal
Bus PT Module that wins the arbitration activates its closes the breaker; bus is live.
first start output and inhibits all other first start Bus
PT Modules from performing first start commands. Figure 2 shows the physical layout locations for the
One phase of the bus voltage is used by the first I/O on the first start Bus PT Module. The bus voltage
start logic to inhibit operation of the first start func- inputs and outputs are located in the same spot and
tion when bus voltage is present. use the same terminal block connectors in both Bus
PT Module designs. On the 300−4985 module,
Figure 1 is a block diagram showing the inter-mod- there are 2 new terminal blocks that have four posi-
ule connections for paralleling PCC gensets with tions each to provide connections for the first start
the new first start Bus PT Module. The power sensor inputs and outputs.

START

PCC #1 PCC #2 PCC #N


...

4 3 2 1 4 3 2 1 4 3 2 1 4 3 2 1 4 3 2 1 4 3 2 1
INHB INHB INHB INHB RDY 1ST B+ GND INHB INHB INHB INHB RDY 1ST B+ GND INHB INHB INHB INHB RDY 1ST B+ GND
GND GND TO ST GND GND TO ST GND GND TO ST
TB13 LD TB14 TB13 LD TB14 TB13 LD TB14
C− 1 C− 1 C− 1
A39 A39 A39
C+ 2 C+ 2 C+ 2
BUS PT/ BUS PT/ BUS PT/
B− 3 1st START B− 3 1st START B−
1st START 3
MODULE PCC B+ MODULE MODULE
PCC PCC
300−4985 4 300− 4985 B+ 4 300− 4985 B+ 4
A− 5 MODULE #2 A− A−
MODULE #1 5 MODULE #N 5
A+ 6 A+ 6 A+
BUS BUS 6
BUS
A B C N A B C N A B C N
TB2 TB2 TB2
1 2 3 4 1 2 3 4 1 2 3 4
TB1 TB1 TB1

LOAD

FIGURE 1. BLOCK DIAGRAM FOR PARALLELING PCC GENSETS USING BUS PT MODULES WITH FIRST
START SENSOR
C503a
Page 2 of 14
4 3 2 1 4 3 2 1
If a single module is used and a First Start pulse is
required (i.e. one unit in utility single mode), the
INHB INHB INHB INHB RDY 1ST B+ GND
GND GND TO ST module can be made to generate a First Start pulse
TB13 LD TB14 by connecting a 10k 1/2 watt resistor from TB 14-2
RUNNING
C− 1 to TB13-2 (see Figure ).
CONNECTOR C+ 2
J1 When the genset is in utility single mode, the first
1ST START
B− 3
start input is used for sync enable. In this case,
PCC since the Bus PT Module is not connected to any
B+ 4 other modules, it will never provide a first start sig-
A− 5
nal and shouldn’t interfere with an external sync en-
able signal.
BUS A+ 6
A B C N TB2
TB1 1 2 3 4 10k
RESISTOR
BUS PT/FIRST START MODULE 300−4985
TB13 TB14

FIGURE 2. FIRST START BUS PT MODULE PCB


LAYOUT B+ B+

The Bus PT Module with First Start Sensor also has 4 3 2 1 4 3 2 1


a J1 connector located in the center of the board.
This connector duplicates the connections going to
TB2 and TB14. These are the connections that go
to the control. If the proper connector is in the en-
gine harness, no connections need to be made to
these terminal blocks. Although current production
does not include a harness that can connect to the FIRST START
J1 connector, this connector can be used to simplify MODULE 300−4985
installation with future gensets.

The maximum number of gensets that can be paral-


leled is limited by the Bus PT Module to 24. This limit
is due to the LED current ratings of the opto couplers. TB2
Note that there may be a lower maximum number of
paralleled units allowed if components, other than
the Bus PT Module, are the limiting factor.

There must be at least two powered Bus PT Mod- TB1


ules wired together at the inhibit connections before
one of the Bus PT Modules will produce a first start
signal. If only one Bus PT Module is operational, the FIGURE 3. CONNECTION FOR FIRST START
first start signal will never occur. PULSE USING A SINGLE MODULE

C503a
Page 3 of 14
INSTALLATION DANGER Hazardous voltage will cause se-
vere personal injury or death. Disconnect all
CAUTION Always disconnect a battery char- electrical supply sources before opening the
ger from its AC source before disconnecting the generator output box, control panels, or per-
battery cables. Otherwise, disconnecting the forming any service work.
cables can result in voltage spikes high enough 1. Place the genset Start/Stop/Remote switch to
to damage the DC control circuits of the set. the Stop position.
2. Disconnect the power supply to the battery
WARNING Accidental starting of the generator
charger (if applicable). Remove all electrical
set while working on it can cause severe per- supply sources.
sonal injury or death. Prevent accidental start-
ing by disconnecting the starting battery cables 3. Disconnect the generator set starting battery
(negative [−] first). cable(s). disconnect the negative (−) cable(s)
first to reduce the risk of arcing.
Make certain the battery area has been well-ven- 4. Verify that the paralleling breaker is open, and
tilated before servicing a battery. Arcing can ig- prevented from closing.
nite explosive hydrogen gas given off by batter- 5. Verify that the parallel bus that is the source of
ies, causing severe personal injury. Arcing can voltage to the Bus PT Module is de-energized,
occur when a cable is removed or re-attached, or the Bus PT Module is effectively isolated.
or when the negative (−) battery cable is con- 6. Secure the Bus PT Module to the back of the
nected and a tool used to connect or disconnect accessory box with the four screws provided,
the positive (+) battery cable touches the frame as shown in Figures 4, 5, or 6.
or other grounded metal part of the set. Always
remove the negative (−) cable first, and recon- 7. Complete the Rail Mount kit (C501 [HC4/5] or
nect it last. Make certain hydrogen from the bat- C502 [HC6/7]).
tery, engine fuel, and other explosive fumes are 8. Refer to the wiring instructions in C501 or C502
fully dissipated. This is especially important if a and the customer connection wiring diagrams
battery has been connected to a battery char- at the end of this instruction sheet to complete
ger. the installation.

C503a
Page 4 of 14
BUS PT
MODULE
(A39)

ALTERNATOR
FRAME SIZE
HC4/HC5
ACCESSORY BOX
WRAPPER
(COVER NOT SHOWN)

BUS PT
MODULE

ALTERNATOR
FRAME SIZE
HC6/HC7

FIGURE 4. TYPICAL PCC 3100 ACCESSORY BOX ASSEMBLY


C503a
Page 5 of 14
BUS PT
MODULE

FIGURE 5. TYPICAL PCC 3200 ACCESSORY BOX ASSEMBLY (8 SLOT CARD CAGE)

C503a
Page 6 of 14
BUS PT
MODULE

FIGURE 6. TYPICAL PCC 3200 ACCESSORY BOX ASSEMBLY (4 SLOT CARD CAGE)

C503a
Page 7 of 14
THIS PAGE LEFT INTENTIONALLY BLANK

C503a
Page 8 of 14
THIS IS A TYPICAL SCHEMATIC/WIRING DIA-
GRAM. FOR WIRING, REFER TO THE SCHE-
MATIC AND WIRING DIAGRAM PACKAGE THAT
WAS SHIPPED WITH YOUR GENERATOR SET.

No. 612-6675 Sh 3 of 3
Rev. D Sys: HP
Modified 8/1997

FIGURE 7. PCC 3100 CUSTOMER WIRING CONNECTIONS

C503a
Page 9 of 14
THIS IS A TYPICAL SCHEMATIC/WIRING DIA-
GRAM. FOR WIRING, REFER TO THE SCHE-
MATIC AND WIRING DIAGRAM PACKAGE THAT
WAS SHIPPED WITH YOUR GENERATOR SET.

No. 612-6751 Sh 6 of 7
Rev. B Sys: Pro-E
Modified 7/2002

FIGURE 8. PCC 3200 CUSTOMER WIRING CONNECTIONS − 8 SLOT CARD CAGE (SHEET 1 OF 2)
C503a
Page 10 of 14
THIS IS A TYPICAL SCHEMATIC/WIRING DIA-
GRAM. FOR WIRING, REFER TO THE SCHE-
MATIC AND WIRING DIAGRAM PACKAGE THAT
WAS SHIPPED WITH YOUR GENERATOR SET.

No. 612-6751 Sh 7 of 7
Rev. B Sys: Pro-E
Modified 7/2002

FIGURE 9. PCC 3200 CUSTOMER WIRING CONNECTIONS − 8 SLOT CARD CAGE (SHEET 2 OF 2)

C503a
Page 11 of 14
THIS IS A TYPICAL SCHEMATIC/WIRING DIA-
GRAM. FOR WIRING, REFER TO THE SCHE-
MATIC AND WIRING DIAGRAM PACKAGE THAT
WAS SHIPPED WITH YOUR GENERATOR SET.

No. 630-2592 Sh 5 of 10
Rev. C Sys: Pro-E
Modified 9/2003

FIGURE 10. PCC 3200 CUSTOMER WIRING CONNECTIONS − 4 SLOT CARD CAGE (SHEET 1 OF 3)
C503a
Page 12 of 14
THIS IS A TYPICAL SCHEMATIC/WIRING DIA-
GRAM. FOR WIRING, REFER TO THE SCHE-
MATIC AND WIRING DIAGRAM PACKAGE THAT
WAS SHIPPED WITH YOUR GENERATOR SET.

No. 630-2592 Sh 6 of 10
Rev. C Sys: Pro-E
Modified 9/2003

FIGURE 11. PCC 3200 CUSTOMER WIRING CONNECTIONS − 4 SLOT CARD CAGE (SHEET 2 OF 3)

C503a
Page 13 of 14
THIS IS A TYPICAL SCHEMATIC/WIRING DIA-
GRAM. FOR WIRING, REFER TO THE SCHE-
MATIC AND WIRING DIAGRAM PACKAGE THAT
WAS SHIPPED WITH YOUR GENERATOR SET.

No. 630-2592 Sh 7 of 10
Rev. C Sys: Pro-E
Modified 9/2003

FIGURE 12. PCC 3200 CUSTOMER WIRING CONNECTIONS − 4 SLOT CARD CAGE (SHEET 3 OF 3)
C503a
Page 14 of 14

You might also like