1. Portable Fire extinguishers shall be provided for the protection of both the Yes N/A No
building structure and the occupancy hazards contained therein regardless of
the presence of any fixed fire suppression systems.
2. Are the installed portable fire extinguishers listed? The extinguishers shall Yes N/A No
bear UL or FM or LPCB labels.
3. Offices: Yes N/A No
Are multipurpose (ABC) dry type extinguishers (4.5 kg) and CO2 extinguisher
(2 kg) provided and the maximum travel distance from a remote area to the
nearest extinguisher is less than 15 m.
4. Common Circulation Areas Corridors, Lobby’s, Passage ways: Yes N/A No
Are multipurpose (ABC) dry type extinguishers (4.5 kg) and CO2 extinguisher
(5 kg) provided and the maximum travel distance from a remote area to the
nearest extinguisher is less than 22.5 m.
5. Electrical Rooms, Telephone Rooms Mechanical Plant Room, Lift Machine Yes N/A No
Room, Other service rooms:
Are multipurpose (ABC) dry type extinguishers (4.5 kg) and CO2 extinguisher
(5 kg) provided and the maximum travel distance from a remote area to the
nearest extinguisher is less than 9 m.
6. Parking areas: Yes N/A No
a) Are multipurpose (ABC) dry type extinguishers (4.5 kg) and CO2
extinguisher (5 kg) provided and the maximum travel distance from a
remote area to the nearest extinguisher is less than 15 m?
b) Are FFP foam trolley type (20 Gal) extinguisher is provided with a 30
m spacing along the drive way within the carpark?
7. Transformer Room: Yes N/A No
a) Are multipurpose (ABC) dry type extinguishers (4.5 kg) and CO2
extinguisher (5 kg) provided and the maximum travel distance from a
remote area to the nearest extinguisher is less than 9 m?
b) Are Dry Powder trolley type (25 kg) extinguisher is provided per
transformer?
8. HV / LV Room: Yes N/A No
a) Are multipurpose (ABC) dry type extinguishers (4.5 kg) and CO2
extinguisher (5 kg) provided and the maximum travel distance from a
remote area to the nearest extinguisher is less than 9 m?
b) Are CO2 trolley type (12 kg) extinguisher is provided near exit?
9. Diesel Generator Room: Yes N/A No
a) Are multipurpose (ABC) dry type extinguishers (4.5 kg) and CO2
extinguisher (5 kg) provided and the maximum travel distance from a
remote area to the nearest extinguisher is less than 9 m?
b) Are FFP foam trolley type (20 Gal) extinguisher is provided per
generator set?
10. Garbage Collection Room: Yes N/A No
Are multipurpose (ABC) dry type extinguishers (6 kg) provided and the
maximum travel distance from a remote area to the nearest extinguisher is
less than 9 m.