You are on page 1of 5

1) OVERALL GST-GND MODE:-

HV TERMINAL
OVERALL GST-GND

G
R B

HF N

FIG-1

1. Connect Tan Delta Kit HV terminal to CVT main HV Point as shown in FIG-1.
2. Connect CVT’s HF (High Frequency) and N point to Earth.
3. Secondary of CVT’s must be shorted or connected to secondary instruments.
4. Take reading on 2 KV, 5 KV and 10 KV on GST-GND mode through Delta 4000 kit.

1|Page
Prepared By: Electrical Lab Team Approved By: Mr. Bhupendra Vala
Rev: 00
Doc No :02
2) OVERALL UST-R MODE:-

HV TERMINAL
OVERALL UST-R

G
R B

HF N

FIG-2

1. Connect Tan Delta Kit HV terminal to CVT main HV Point as shown in FIG-2.
2. Connect Tan Delta kit Red Measuring point to CVT’s HF (High Frequency) point and
open the earth link between HF and N point as shown in Fig-2.
3. Secondary of CVT’s must be shorted or connected to secondary instruments.
4. Take reading on 2 KV, 5 KV and 10 KV on UST-R mode through Delta 4000 kit.
2|Page
Prepared By: Electrical Lab Team Approved By: Mr. Bhupendra Vala
Rev: 00
Doc No :02
3) STACK-1 UST-R MODE:-
4)
STACK-1 UST-R

HV TERMINAL

G
R B

HF N

G
FIG-3

1. Connect Tan Delta Kit HV terminal to CVT main HV Point as shown in FIG-3.
2. Connect Tan Delta kit Red Measuring point to Bottom of Stack-1 of CVT as shown on
Fig-3.
3. Secondary of CVT’s must be shorted or connected to secondary instruments and
connect HF and N point to ground.
4. Take reading on 2 KV, 5 KV and 10 KV on UST-R mode through Delta 4000 kit.
3|Page
Prepared By: Electrical Lab Team Approved By: Mr. Bhupendra Vala
Rev: 00
Doc No :02
4) STACK-2 UST-R MODE:-

HV TERMINAL
STACK-2 UST-R

G
R B

HF N

G
FIG-4

1. Connect Tan Delta Kit HV terminal to TOP of STACK-2 of CVT as shown in FIG-4.
2. Connect Tan Delta kit Red Measuring point to Bottom of Stack-2 of CVT as shown on
Fig-4.
3. Secondary of CVT’s must be shorted or connected to secondary instruments and
connect HF and N point to ground.
4. Take reading on 2 KV, 5 KV and 10 KV on UST-R mode through Delta 4000 kit.
4|Page
Prepared By: Electrical Lab Team Approved By: Mr. Bhupendra Vala
Rev: 00
Doc No :02
5) STACK-3 UST-R MODE:-

HV TERMINAL

G
STACK-3 UST-R

R B

HF N

G
FIG-5

1. Connect Tan Delta Kit HV terminal to TOP of STACK-3 of CVT as shown in FIG-5.
2. Connect Tan Delta kit Red Measuring point to CVT’s HF (High Frequency) point and
open the earth link between HF and N point as shown in Fig-5.
3. Secondary of CVT’s must be shorted or connected to secondary instruments.
4. Take reading on 2 KV, 5 KV and 10 KV on UST-R mode through Delta 4000 kit.

5|Page
Prepared By: Electrical Lab Team Approved By: Mr. Bhupendra Vala
Rev: 00
Doc No :02