You are on page 1of 13

Dorman Smith PowerForm

Low Voltage Factory Built Assemblies


Contents

Introduction to the PowerForm Switchboard System 1 Dorman Smith Switchgear Introduction

PowerForm Specification 2
1
3
Continuous product development Dorman Smith's world class circuit protection, has firmly
2500A Switchboard Specification 4 including new uprated manufacturing facilities are established a Worldwide
specifications have provided the dedicated to answering the reputation for high quality and
opportunity for Dorman Smith to individual needs of customers expertise.
6300A Switchboard Specification 6 update their low voltage factory using the company's own unique Located in Preston, Lancashire,
built assembly range. refinement of ‘Just In Time’ Dorman Smith occupies a
Cast Resin Transformers 9 This publication gives detailed techniques to achieve total purpose built site totalling
information on Dorman Smith’s manufacturing flexibility. 19,000m2 and is one of Britain’s
Packaged Substations 9 extensive range of low voltage Such is the efficiency of the largest and most well respected
factory built assemblies and is Dorman Smith UK plant, it won a manufacturers of low voltage
Loadline ACBs 10 intended to assist the design Britain’s Best factory award, and switchgear, systems and
engineer and installer in the has been chosen by the DTI as a associated distribution
Microprocessor Based Overcurrent Releases 10 selection of equipment to meet manufacturing reference plant for equipment.
today's stringent specifications. the UK and was also the subject In addition, there are also
of an Open University video on manufacturing plants in Dubai
Loadline HP Circuit Breakers 11
manufacturing. Dorman Smith's and Riyadh, which service the
ability to design and manufacture Middle East markets.
Loadswitch Fused Devices 11 reliable, durable products and to
give advice on complex electrical
Switchboard Standards 12
EN60439-1:1999 (IEC 60439-1:1999) Switchboard Standard 12

Internal Separation of Assemblies 14

UK National Annex Table NA1 16


Forms of Separation 17
Form 1 – 4 17
Degrees of Protection 19
EN60529:1991 (IEC 60529-1:1989) Degrees of Protection 19
Energy Management 20
Power Factor Correction 20
PowerForm Specification PowerForm Specification

Certification 2500A Busbar System


4
2 • Rated voltage 415V a.c. 5
3
The PowerForm Switchboard System has been fully tested and ASTA certified. • Rated insulation voltage 690V a.c.
• Dielectric test voltage 2.5kV
• Nominal frequency 50 Hz
• Fully ASTA certified Busbar System
Standards
• Busbar Ratings
- 1000A
PowerForm is a fully type tested switchboard fully complying with
- 1250A
• IEC 60439-1:1999 - 1600A
• EN 60439-1:1999 - 2000A
• BSEN60439-1:1999 - 2500A
• Busbar supports are flame
retardant and high temperature
glass reinforced.
Mechanical Characteristics
Max Horizontal Phase Busbar 2500A
• Degree of protection to EN 60529 • Steel pre-treatment involves iron Max Horizontal Neutral Busbar 2500A
(IEC 60529) is minimum IP3X with phosphate process for degreasing Max Vertical Phase and Neutral Busbar 1600A
higher protection available. • Paint finish in (Light Grey) Powder Max Short Time Current Busbars 50kA - 3 secs
• Internal degree of protection Coated polyester, colour RAL 7035 Max Peak Current 105kA
exceeds IP2X • Standard frames available are
• Functional unit interconnections as shown below
PVC insulated 6300A Busbar System
• All doors manufactured from
1.6mm steel and hinged • Rated voltage 415V a.c.
• All rigid busbar partitions made • Rated insulation voltage 690V a.c.
from perforated 1.5mm steel • Dielectric test voltage 2.5kV
• Nominal frequency 50 Hz
Frame Frame Widths (mm)
• Fully ASTA certified Busbar System
Range Cable Access Steel (mm) Height (mm) 500 550 600 650 800 850 1000 1300
PowerForm 25 Front 2 2356 • • •
• Busbar Ratings
Rear 2 2356 • • •
- 3200A
PowerForm 63 Rear 3 2356 • • • • • • •
- 4000A
- 5000A
- 6300A
• Busbar supports are flame
retardant and high temperature
glass reinforced.

Max Horizontal Phase Busbar 6300A


Max Horizontal Neutral Busbar 10,000A
Max Vertical Phase and Neutral Busbar 1600A
Max Short Time Current Busbars 100kA - 1 sec
Max Peak Current 220kA
25 25
2500A Switchboard 2500A Switchboard
Specification Specification

PowerForm 25 Constructional Details Typical Arrangements


4 1. Typical arrangement 2500A
5
busbar system
• 2500A, 50kA/3sec Busbars
• Loadline HP changeover MCCBs
• Front access cabling
• High performance Loadline HP
outgoing MCCBs

2. Typical Controlgear Compartment

Horizontal Busbar Positions

2
63 63
6300A Switchboard 6300A Switchboard
Specification Specification

25 Constructional Details
PowerForm 63 Typical Arrangements
6 3. Typical arrangement 6300A 7
busbar system
• 6300A 100kA/1sec Busbars.
• Selective forced air cooling to:
- Busbars.
- ACB Enclosure.
• 4 Pole withdrawable ACBs.
• Rear access cabling.
• High performance Loadline HP
outgoing MCCBs.

4. Internal view showing 6300A


Busbar
• Outgoing Connections.
• 800mm Main Cubicle.
• 500mm or 800mm
Cable Access Way.

5. View showing special


Busbar arrangements

Horizontal Busbar Positions

4 5
63
6300A Switchboard Packaged Substations
Specification

Special Arrangements Cast-Resin Transformers IEC 726


8 6. Insulated busbar components Advantages and characteristics of Maintenance-free Maximum reliability 9
Certain essential installations may cast-resin transformers. The high stability of the physical The product offers the maximum
require insulated Busbars within Excellent antipollution features and characteristics of the materials and reliability thanks to the computerised
the Busbar enclosure to ensure maximum safety the state-of-the-art technology control of thermal processes, to the
resilience of supply. To comply with All constructive materials and reduce maintenance to the check of the chemical and the
this Dorman Smith can offer a totally especially the insulating resin are minimum. physical characteristics and to the
insulated system. self-extinguishing: they do not Where can cast-resin transformers measuring of the TG (Glass-
To comply with EN 60439-1 develop, in case of fire, toxic gases be used? transition) temperature of resin.
(IEC 60439-1) Form 4, UK Annex and they are moisture tolerant. The electrical and physical Economy of installation
Types 1 and 4, the Busbar Performances properties of cast-resin transformers Elimination of sumps for oil
separation is achieved using Cast-resin transformers are the best fit them for both civil and industrial collection, reduced overall
insulated coverings. solution for all technical installation use: hospitals, theatres, airports, dimensions and an excellent
problems, thanks to their capability subway, mines, off-shores platforms, distribution of weights allow cost
to withstand network impulsive nuclear power plants, vessels, reduction of the plant.
• 6300A Busbar fully insulated.
voltage peaks,dynamic short-circuit, industrial plants, etc. That is to say
• Joints also insulated using wherever there are fire or
and overloads, with the optional
shrouds. environmental pollution risks and
addition of cooling fans for
• Insulation by means of a durable increasing rated capacity. where safety is a must.
polymeric coating.

7. Fan assisted cooling system


To assist with cooling, high current Packaged Substations
switchboards, an option is to force
air cool the internal components.

• Fan will cool ACBs.


• Also can cool Busbars.
• Air flow adjusted to suit final
temperature requirements.
• Thermostatically controlled.
• Main and standby options.

7
LV Protective Devices LV Protective Devices

Loadline ACBs Loadline High Performance MCCBs


10 The apparatus complies with the mechanical, electrical and thermal Loadline HP circuit breakers and ensure high reliability, precise 11
specifications of the regulations for stresses. their accessories conform to the tripping and immunity to the
on-board installations and is Loadline Air Circuit Breakers International Standards IEC 947-2, influence of ambient conditions. The
approved by the following Naval represent the logical functional EN 60947 (harmonised in the 17 power supply required for correct
Registers: complement to the Loadline HP CENELEC countries), CEI EN 60947 operation is supplied directly by the
• RINA (Italian Naval Register) moulded case circuit breakers and and IEC 1000, while also conforming releases’s current transformers with
have, like them, been designed for to the following EC directives: one phase current ≥ 15% of their
• Det Norske Veritas
integration and perfect co-ordination • Low Voltage Directives (LVD) rated curents, even with only one
• Bureau Veritas phase powered. Just one adjustment
with the different lines of low voltage No. 73/23 EEC
• Germanischer Lloyd products. is required for all the phases and
• Electromagnetic Compatibility
• Lloyd’s Register of Shipping neutral, and tripping of the release is
Loadline Air Circuit Breakers are Directive (EMC) No. 89/336 EEC
simultaneous for all the poles of the
• Polskj Reiestr Statkow available in five different models: Loadline HP S4, S5, S6 and SX7 circuit breaker with operating
The constant increase in the E1, E2, E3, E4 and E6, each of circuit breakers for alternating characteristics that are unaffected by
technological and functional which benefits from the current protection can be fitted with ambients conditions. Operation of
complexity of electrical installations interchangeability of the various overcurrent releases PR211/P and the release can be checked using a
Loadline Air Circuit Breakers and makes it essential for every different versions of moving parts PR212/P featuring mircoprocessor- TT1 portable test device powered
their accessories conform to the component - particularly those such (with different breaking and rated based electronic technology. This using normal batteries.
International Standards IEC 947, as protection circuit breakers which current capacities) for the same makes it possible to obtain
EN 60947 (harmonised in the 17 are crucial to safety - to offer the fixed part. The rated uninterrupted protection functions which
CENELEC countries), CEI EN 60947 highest levels of continuity of service currents range from 800 to 6300 A.
and IEC 1000, and conform to the and reliability combined with The breaking capacities range from
relevant CE directives: minimal maintenance requirements. 40kA to 150kA (380/415 V a.c.).
• Low Voltage Directives Loadline Air Circuit Breakers were
(LVD) No. 73/23EEC designed in line with the advanced
• Electromagnetic compatibility plant engineering requirements, and
Directive” (EMC) No. 89/336EEC features high resistance to

Microprocessor Based Overcurrent Releases Loadswitch Fuse Combination Units


The circuit breakers fitted with All this is thanks to the fact that the Loadswitch fuse Combination Units category of AC23A and short-circuit
Protection PR111 PR112 microprocessor-based releases offer selection criteria are common to both conform to EN 60947-3 (IEC 60947- capacity of 80KA enables Loadswitch
Functions load control, self-test and information families of circuit breakers and use 3). 80kA RMS Fused Short Circuit to be installed with confidence on
transmission capabilities in addition intuitive and easy-to-read codes and Current any inductive or resistive load.
Overload protection symbols.
L to the traditional protection functions, • 415V ac Rated Voltage The door handle can be padlocked
with inverse long
time-delay trip
enabling them to be interfaced with The new circuit breakers continue a • Current ratings 32A to 800A off as standard. Up to three padlocks
centralised control and supervision tradition of switchear designed and can be attached with ease.
• 80kA RMS Fused Short-Circuit
Selective short-circuit systems. Loadline offers all the manufactured paying particular
S Current
protection with inverse components needed to build systems attention to use and user interface-
or definite short time that are tailored to each installation, related aspects, with obvious • AC23A Utilisation Category
delay from field units to front ends (with Loadswitch has been designed to
advantages in terms of ergonomics,
Instantanious short
standard communication protocols), clarity and speed of identification. exceed the requirements of
I circuit protection with from actuators to control systems. EN 60947-3 (IEC 60947-3) and to
adjustable trip current As a result, the work of specifiers and offer solutions demanded by our
setting designers is considerably simplified customers where ease of installations
when it comes to choosing the and ever increasing cable sizes are
Earth Fault Protection required.
G technical characteristics and
RESIDUAL performance required. A full uninterrupted duty ensures
that the unit can maintain full rated
SOURCE GROUND load indefinitely. A utilisation
RETURN

Thermal memory
for functions L and S
Switchboard Standards Switchboard Standards

Introduction EN60439-1:1999 Fundamentals of Separation


12 This International Standard applies This standard applies to assemblies The object of this standard is to lay In accordance with the Standard, separation of the 2. Protection against the passage of solid foreign 13
to low voltage switchgear and intended for use in connection with down the definitions and to state the various elements of an Assembly: busbars, functional bodies from one unit of an Assembly to an adjacent
controlgear assemblies (type-tested the generation transmission, service conditions, construction units, terminals, can be claimed providing one or more unit. The degree of protection shall be at least IP2X.
assemblies (TTA) and partially type- distribution and conversion of requirements, technical of the following criteria are met: The minimum requirement is proven by the standard
tested assemblies (PTTA)), the rated electric energy, and for the control of characteristics and tests for low- 1. Protection against contact with live parts belonging test finger not being able to touch live parts in adjacent
voltage of which does not exceed electric energy consuming voltage switchgear and controlgear to adjacent functional units. The degree of protection units and a 12mm ball not being able to pass between
1000 V a.c. at frequencies not equipment. assemblies. shall be at least IP2X or IPXXB. units.
exceeding 1000Hz, or 1500V d.c. As a minimum, finger contact with live parts in adjacent In practice a higher degree of protection may be
functional units is prevented. With Assemblies supplied required for horizontal partitions to prevent small objects
by Dorman Smith Switchgear this is extended to include form falling between compartments and should be
protection against finger contact between: functional identified in the contract specification.
units, adjacent busbars and busbar connections, and These two fundamental criteria are interrelated. Dorman
Type Tested Assemblies (TTA) Section 2.1.1.1 terminals as required for the particular form of Smith Switchgear will therefore ensure all these are fully
separation being considered. met in respect of the particular form of separation
Section 2.1.1.1
A low voltage switchgear and The requirement is proven with the standard test finger. offered.
controlgear assembly conforming to
an established type or system
without deviations likely to Typical Applications
significantly influence the
performance, from the typical
assembly verified to be in Form 1 - No separation Form 3 - Separation of busbars from functional units
accordance with this standard. Typical applications are places where the switchboard is and the functional units from one another but not
in a secure location and where failure of the switchboard their terminations.
will cause little or no additional disruption to other areas Should be applied where it is important to provide
being fed by the switchboard. protection from internal live parts and where failure of
Partially Type Tested Assemblies (PTTA) Section 2.1.1.2 functional units being fed from the same busbar would
cause unacceptable disruption.
Section 2.1.1.2 Form 2 - Separation of busbars from functional units.
Applications may well be the same as Form 1 but where Form 4 - Separation of busbars from functional units
A low voltage switchgear and and the functional units from one another including
controlgear assembly, containing it is important that a fault in the switchboard need not
affect all functional units being fed from the same their terminations.
both type-tested and non-type-tested Should be applied where it is important to provide
arrangements, provided that the busbar system.
protection from internal live parts and where failure of
latter are derived (e.g. by functional units being fed from the same busbar would
calculation) from type-tested cause unacceptable disruption. Because all the
arrangements which have complied terminations are separated it is possible to isolate and
with the relevant test. work on a single functional unit.

Methods of Construction
Type Tests Section 8.2 Section 8 Dorman Smith have considerable experience in has been employed which enables the maximum
designing and constructing low voltage switchboard number of permutations to be achieved within a highly
Type tests include the following: e) verification of clearances and
assemblies from the simplest panelboard to the cost effective frame work.
a) verification of temperature-rise creepage distances (8.2.5);
most complex multi-cubicle control and distribution If you would like more information on Dorman Smith Low
limits (8.2.1): f) verification of mechanical switchboard including HV/LV transformer to provide Voltage Switchgear Systems our technical Sales Team
b) verification of the dielectric operation (8.2.6); a packaged substation. will be pleased to assist and can upon request organise
properties (8.2.2); g) verification of the degree of The various methods of separation and construction educational seminars and training for your staff on
c) verification of the short-circuit protection (8.2.7). offered by Dorman Smith from Form I through to EN 60439-I and the UK National Annex.
withstand strength (8.2.3); Form 4 are illustrated in detail on pages 14-15 can
d) verification of the effectiveness of be seen from these diagrams a modular approach
the protective circuit (8.2.4);
Switchboard Specification Switchboard Specification

Internal Separation of Assemblies Section 7.7 Form 3a Criteria


14 15
Symbols used in Diagrams
Separation of busbars from the functional units
and separation of all functional units from one
Barrier another. Separations of the terminals for external
conductors from the functional units, but not
from each other.
Terminal Device Busbar
Terminals for external conductors not separated
from busbars.
Form 1 Criteria

No Separation. Form 3b Criteria

Separation of busbars from the functional units


and separation of all functional units from one
another. Separations of the terminals for external
conductors from the functional units, but not
from each other.

Terminals for external conductors separated from


busbars.

Form 2a Criteria
Form 4a Criteria
Separation of busbars from the functional Units.
Separation of busbars from the functional units
Terminals for external conductors not separated and separation of all functional units from one
from busbars. another, including the terminals for external
conductors which are an integral part of the
functional unit.

Terminals for external conductors in the same


compartment as the associated functional unit

Form 2b Criteria
Form 4b Criteria

Separation of busbars from the functional Units. Separation of busbars from the functional units
and separation of all functional units from one
another, including the terminals for external
Terminals for external conductors separated from
conductors which are an integral part of the
busbars.
functional unit
Terminals for external conductors not in the
same compartment as the associated functional
unit, but in individual, separate, enclosed
protected spaces or compartments.
Switchboard Standards Switchboard Standards

UK National Annex Table NA.1 Form 2b Type 2 Internal Separation of Assemblies Section 7.7
16 The internal separation of of construction, based on typical However, in order to achieve 17
Assemblies by barriers or partitions practice in the United Kingdom. agreement between manufacturers
is specified in 7.7 and is subject to Other types of construction are not and users, it is recommended to
agreement between the precluded, and it is not essential to adopt one of the listed types of Incoming
Unit
Outgoing
Units
Outgoing
Units
Outgoing
Units
manufacturer and the user. adopt any of the listed types in order construction.
Table NA.1 gives additional to comply with the requirements of
information regarding different types the Standard.

Forms of Separation Table NA.1


Main criteria Sub criteria Form Type of Construction
No separation Form 1
Terminals for external
conductors not separated Form 3b Type 2 Internal Separation of Assemblies Section 7.7
Separation of busbars from the from busbars.
functional units. Form 2 Type 1 Busbar separation is achieved by insulated covering,
Terminals for external e.g. sleeving, wrapping or coatings
conductors separated from
busbars. Type 2 Busbar separation is by metallic or non-metallic rigid
barriers or partition. Incoming Outgoing Outgoing Outgoing
Unit Units Units Units
Separation of busbars from the Terminals for external
functional units and separation conductors not separated Form 3a
of all functional units from one from busbars.
another. Separation of the
terminals for external Type 1 Busbar separation is achieved by insulated coverings,
Terminals for external e.g. sleeving, wrapping or coatings
conductors from the functional
conductors separated from Form 3b
units, but not from each other. Type 2 Busbar separation is by metallic or non-metallic rigid
busbars.
barriers or partitions.
Type 1 Busbar separation is achieved by insulated coverings,
e.g. sleeving, wrapping or coatings. Cables may be glanded elsewhere.
Terminals for external
conductors in the same Type 2 Busbar separation is by metallic or non-metallic rigid barriers or
compartment as the partitions. Cables may be glanded elsewhere. Incoming Outgoing
Cables
Cable
associated functional unit. Outgoing
Type 3 Bushbar separation is by metallic or non-metallic rigid barriers or partitions. Cables
Separation of busbars from the The termination for each functional unit has its own integral glanding facility.
functional units and separation
of all functional units from one Type 4 Busbar separation is achieved by insulated coverings,
another, including the terminals Form 4a e.g. sleeving, wrapping or coatings. Cables may be glanded elsewhere. Form 4a Type 2 Internal Separation of Assemblies Section 7.7
Terminals for external
for external conductors which Type 5 Busbar separation is by metallic or non-metallic rigid barriers or partitions.
conductors not in the same Terminals may be separated by insulated coverings and glanded in common
are an integral part of the
compartment as associated cabling chamber(s).
functional unit.
functional unit, but in
individual, separate, Type 6 All separation requirements are by metallic or non-metallic rigid barriers or
enclosed protected spaces partitions. Cables are glanded in common cabling chamber(s). Incoming Outgoing Outgoing Outgoing
Unit Units Units Units
or compartments. Type 7 All separation requirements are by metallic or non-metallic rigid barriers or
partitions. The termination for each functional unit has its own integral
glanding facility.

Incoming Outgoing
Cable Cables
Outgoing
Cables
Switchboard Standards Degrees of Protection

Form 4b Type 5 Internal Separation of Assemblies Section 7.7 EN 60529 : 1991


18 EN 60529 : 1991 describes a system for The first characteristic numeral designates enclosures and protection of the 19
classifying degrees of protection provided the degree of protection with regards to equipment inside the enclosure
by enclosures of electrical equipment with a solid objects. against the ingress of solid foreign
Incoming Outgoing Outgoing Outgoing rated voltage not exceeding 1000V ac and The second numeral designates the degree objects.
Unit Units Units Units
1500V dc. of protection against the ingress of liquid. b) Protection of the equipment
The markings used to indicate the degree of It is intended to provide indication of: inside the enclosure against
protection consist of the letter IP (Ingress harmful ingress of water.
Protection) followed by two characteristic a) Protection of persons against
numerals. access to hazardous parts inside

First Number - Protection Against Solids Second Number - Protection Against Liquids
Protection of persons Protection against
Protection against solid against access to IP Example Liquids - Tests Protection from water
Outgoing
IP Example foreign objects - Tests hazardous parts with:
Incoming
Cable Cables
Outgoing 0 No protection. non-protected 0 No protection No protection
Cables

Full penetration of 50mm diameter Protection against


sphere allowed. Protection against
Form 4b Type 6 Internal Separation of Assemblies Section 7.7
II IIIII
III

1 vertically falling drops

II
1 50

IIIIIIIIIIIIIIIIIIIII
back of hand

IIIIIIIIIIIIIIIIIIIIIII
Contact with hazardous parts not vertically falling drops of water.
of water.

III
III

permitted.
III
III III

Protection against vertically falling dripping up to 15° from


Full penetration of 12.5mm 2 drops of water with enclosure
III
II IIIIIIIIIIIIIIIIIII
II
diameter sphere not allowed. The tilted 15° from the vertical. the vertical

I
IIIIIIIIIIIIIIIIIIIII

II
III
IIII
2 12.5

II IIIIIII
jointed test finger shall have finger
Protection against sprays to 60° from

III
III
I
adequate clearance from

II
III
IIIIIIIIIIIIIIIIIIIII
Incoming Outgoing Outgoing Outgoing II

Unit Units Units Units 3 the vertical - limited ingress limited spraying
hazardous parts.
permitted.
The access probe of 2.5mm Protection against water splashed
3 tool splashing from all
diameter shall not penetrate. 4 from all directions - limited ingress
permitted. directions
Compartment The access probe of 1.0mm
for future use 4 wire Protected against low pressure jets of hosing jets from all
diameter shall not penetrate. 5 water from all directions - limited
ingress permitted. directions
Limited ingress of dust permitted
5 wire Protected against strong jets of strong hosing jets from
(no harmful deposit). 6 water, eg. for use on shipdecks
limited ingress permitted. all directions
Totally protected against ingress of
6 wire 15cm min.
Protected against the effects of
dust. 7 temporary immersion
Incoming Outgoing immersion between 15cm and 1m.
Cable Cables
Outgoing
Cables
Protected against long periods of
8 continuous immersion
immersion under pressure.

Form 4b Type 7 Internal Separation of Assemblies Section 7.7


EN 60529 : 1991
For switchboard assemblies intended for indoor use IP00 IP2X IP3X IP4X IP5X
Incoming Outgoing Outgoing Outgoing EN60439-1 : 1999 states that there is no requirement for protection
Unit Units Units Units
against ingress of water (clause 7.2.1.1) and that the IP references Where some degree of protection against ingress of water is required the
preferred for assemblies designated for indoor use are: following table gives the preferred IP combination numbers:-

List of Preferred IP References


Compartment
for future use

First Characteristic Numeral Second Characteristic Numeral


Protection against contact and protection Protection against harmful ingress of water
against ingress of solid foreign 1 2 3 4 5
2 IP21
3 IP31 IP32
Incoming Outgoing
Cables
4 IP42 IP43
Cable
Outgoing 5 IP53 IP54 IP55
Cables
6 IP64 IP65
Energy Management Energy Management

Power Factor Correction Harmonics


20 21
Introduction Introduction
Electrical installation sizing must be The ratio between the active power user with a higher power factor. Manufacturers are increasingly being rectifiers, microwave ovens, personal BSRIA (Building Services Research
carried out according to the apparent and the apparent power expresses Therefore the voltage drops and asked to provide for oversized neutral computers, etc. This can result in Association) has been working with
power S which, defined as the the power factor (cosφ) or the energy losses are higher, the lower capabilities in their products. This is severe overheating e.g. in cabIes, the industry to find the extent and
product of the voltage and the dephasing between voltage and the power factor. to cater for all anticipated increased busbar, enclosures, transformer coils, severity of power quality problems
current (V x I) is expressed in [VA]. current when the user absorbs To keep down voltage drops and current in the neutral system. etc. related to harmonic currents. It has
When there are ohmic loads, the reactive power. power losses it is therefore necessary The increased current is a result of Therefore, Industry, commercial found widespread problems and
apparent absorbed power is utilised The power factor is equal to 1 when to size the installations considering harmonics being introduced onto the premises, offices and homes, may all believes that unless designers and
completely as active power and is all the apparent absorbed power is the higher current due to the low system, by modern day equipment be affected, and with the growth of operators are more aware of the
dissipated in heat, whereas when active, whereas it is less than 1 when power factor, and this is to the such as, variable speed drives, static use of such equipment, the problem problems, and take action to avoid
there are other loads, such as the apparent absorbed power detriment of the installation’s cost- will escalate. them, they will become critical.
motors. welders, fluorescent lamps. consists of partly active power and effectiveness.
transformers. etc., a part of the partly reactive power. For these reasons, companies
apparent absorbed power, called Recommendations
This means that user equipment with supplying electrical energy increase
reactive power Q, is utilised only to a low power factor requires more the price of electricity for users with
energise the magnetic circuits. It • Obtain information about the • Calculate the harmonic voltage and • Specify transformers and filters to
apparent power from the network a low power factor. harmonic current for all equipment current at critical parts of the remove harmonics;
cannot therefore be used as active (and therefore more current) than a
power to carry out work. to be installed; system, phase and neutral • Follow guidelines for identification
• Consider the effect of source conductors; of harmonic problems including
impedance of ups and standby • Design the installation, including surveys, measurement methods
Types of Power Factor Correction generator systems - they can be proper sizing of neutral and diagnosis;
much higher than the impedance conductors, to accommodate • Safety considerations are
Distributed power factor correction corrected loads overall power which would be required of the main transformer and cause harmonic currents where they paramount and the correct choice
Distributed power factor correction Another advantage with regard to for distributed power factor correction, more severe voltage distortion; occur; of instruments is also emphasised
is, in fact, the best technical solution distributed power factor correction, is taking into account, too, that the kVAR • Eliminate the source of harmonics • Separate circuits supplying so that they will measure harmonic
since capacitor and user equipment its simple and cost-effective installation cost of a high-powered capacitor is less by specifying low harmonic harmonic generating loads from frequencies.
follow exactly the same path during since the capacitor and load are than that of small capacitors. versions of switch mode power those supplying loads which are
daily service of loads, so the cosφ connected and disconnected The bank can be connected supplies, variable speed drives and sensitive to harmonics;
setting becomes automatic and simultaneously and can use the same permanently only if the reactive high frequency ballasts;
systematic. protections against overloads arid energy absorption is fairly regular
Apart from this, with local power short-circuits. during the day, otherwise it must be
factor correction it is not only the switched to prevent having cosφ in
The Effects of Harmonics
Centralised power factor correction
supply authority which benefits from Centralised power factor correction is advance.
The effects of harmonic voltages are multiples (triplen harmonics) add Fortunately, diversity of the harmonic
reactive energy saving, but also the cost-effective in the case of installations When the reactive power absorption malfunctions in sensitive equipment together in the neutral. In severe loads leads to a certain amount of
whole internal distribution system of with several heterogenous loads is highly variable during operation of such as the sensing circuits of circuit cases the neutral current can exceed cancellation since the harmonic
the user. ln industrial installations, operating on an occasional basis, so the installation, automatic regulation breakers and ups switches. The twice the phase currents. In such currents of different loads are rarely
for example, the saving which can be there is high installed power and fairly is required with the bank split up effects of harmonic current are cases a double size neutral busbar is in perfect phase. The solution may
made with distributed power factor Iow average energy absorption by loads into several steps. overheating in conductors, often specified. require modelling software to predict
correction, is not just a question of in simultaneous service. With transformers, motor coils and However, it may be necessary to the neutral current. A range of
tariffs, but is also noted in sizing all centralised power factor correction, the capacitors. double rate busbar and circuit solutions is available, from U.P.S. to
the MV/LV substations with the bank power is notably less than the
When harmonic loaded single phase breakers in the main distribution avoid interruptions, through isoIating
circuits on different phases are board as well. In a large installation and phase shift transformers to
brought together in a distribution the main circuit breaker could be passive and active filters.
board, the third harmonic rated at 4000 A. Finding an acb to
components and all the odd take an 8000A neutral conductor
can be difficult.
All of the above information, including drawings, illustrations and graphic designs, reflects our present understanding and is to the best of our knowledge and belief correct and reliable. Users, however, should
independently evaluate the suitability of each product for the desired application. Under no circumstances does this constitute an assurance of any particular quality or performance. Such an assurance is only
provided in the context of our product specifications or explicit contractual arrangements. Our liability for these products is set forth in our standard terms and conditions of sale.
© Tyco Electronics EPP-0891-3/01

ALR, AMP, Dorman Smith, Dulmison, Hellstern, Raychem, and SIMEL are trademarks of Tyco International Ltd.

Argentina Canada Thailand


Phone: ++54-11-4733 2277 Phone: ++1-905-475 6222 Phone: ++66-2-7394026 - 32
Fax: ++54-11-4733 2267 Fax: ++1-905-470-4453 Fax: ++66-2-3260563 - 64
Australia France United States of America
Phone: ++61-2-4390 1111 Phone: ++33-3-80583200 Phone: ++1-800-327-6996
Fax: ++61-2-4353 2497 Fax: ++33-3-80341015 Fax: ++1-800-527-8350
Brazil Mexico
Phone: ++55-11-861 1311 Phone: ++52-5-729 0405
Fax: ++55-11-861 1862 Fax: ++52-5-361-8545

E-mail: info.dss@tycoelectronics.com www.tycoelectronics.com

Dorman Smith Switchgear Ltd Tyco Electronics Raychem GmbH


Energy Division Energy Division
Blackpool Road, Preston, PR2 2DQ, UK Haidgraben 6, 85521 Ottobrunn/Munich, Germany
Phone: 01772 325400 Fax: 01772 726276 Phone: ++49-89-6089-0, Fax: ++49-89-6096345

You might also like