Air System Sizing Summary for At-L1-2

Project Name: ME2058 zoneload 20171129 12/13/2017


Prepared by: Meinhardt M&E Limited 05:48PM

Air System Information


Air System Name At-L1-2 Number of zones 1
Equipment Class CW AHU Floor Area 677.0 m2
Air System Type SZCAV Location Xiamen, China

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 202.8 kW Load occurs at Jul 1400
Sensible coil load 119.8 kW OA DB / WB 31.8 / 26.3 °C
Coil L/s at Jul 1400 7216 L/s Entering DB / WB 27.1 / 20.8 °C
Max block L/s 7216 L/s Leaving DB / WB 13.2 / 12.8 °C
Sum of peak zone L/s 7216 L/s Coil ADP 11.7 °C
Sensible heat ratio 0.591 Bypass Factor 0.100
m2/kW 3.3 Resulting RH 54 %
W/m2 299.5 Design supply temp. 13.0 °C
Water flow @ 5.0 °K rise 9.71 L/s Zone T-stat Check 1 of 1 OK
Max zone temperature deviation 0.0 °K

Supply Fan Sizing Data


Actual max L/s 7216 L/s Fan motor BHP 10.11 BHP
Standard L/s 7162 L/s Fan motor kW 8.02 kW
Actual max L/(s-m2) 10.66 L/(s-m2) Fan static 600 Pa

Outdoor Ventilation Air Data


Design airflow L/s 1489 L/s L/s/person 4.40 L/s/person
L/(s-m2) 2.20 L/(s-m2)

Hourly Analysis Program v4.80 Page 1 of 6


Air System Design Load Summary for At-L1-2
Project Name: ME2058 zoneload 20171129 12/13/2017
Prepared by: Meinhardt M&E Limited 05:48PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1400 HEATING DATA AT DES HTG
COOLING OA DB / WB 31.8 °C / 26.3 °C HEATING OA DB / WB 6.0 °C / 4.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 300 m2 40326 - 300 m2 - -
Wall Transmission 0 m2 0 - 0 m2 0 -
Roof Transmission 0 m2 0 - 0 m2 0 -
Window Transmission 0 m2 0 - 0 m2 0 -
Skylight Transmission 300 m2 4968 - 300 m2 13590 -
Door Loads 0 m2 0 - 0 m2 0 -
Floor Transmission 677 m2 2803 - 677 m2 2234 -
Partitions 0 m2 0 - 0 m2 0 -
Ceiling 0 m2 0 - 0 m2 0 -
Overhead Lighting 23695 W 23694 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 339 21664 39605 0 0 0
Infiltration - 872 2632 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 9433 4224 0% 0 0
>> Total Zone Loads - 103758 46460 - 15824 0
Zone Conditioning - 101172 46460 - -2995 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 7216 L/s 0 - 7216 L/s 0 -
Ventilation Load 1489 L/s 10576 36564 1489 L/s 11131 0
Supply Fan Load 7216 L/s 8018 - 7216 L/s -8018 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 119766 83023 - 117 0
Central Cooling Coil - 119766 83025 - 0 0
>> Total Conditioning - 119766 83025 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program v4.80 Page 2 of 6


Air System Sizing Summary for At-L1-3
Project Name: ME2058 zoneload 20171129 12/13/2017
Prepared by: Meinhardt M&E Limited 05:48PM

Air System Information


Air System Name At-L1-3 Number of zones 1
Equipment Class CW AHU Floor Area 559.0 m2
Air System Type SZCAV Location Xiamen, China

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 194.1 kW Load occurs at Jul 1400
Sensible coil load 123.4 kW OA DB / WB 31.8 / 26.3 °C
Coil L/s at Jul 1400 7567 L/s Entering DB / WB 26.8 / 20.2 °C
Max block L/s 7567 L/s Leaving DB / WB 13.2 / 12.7 °C
Sum of peak zone L/s 7567 L/s Coil ADP 11.7 °C
Sensible heat ratio 0.636 Bypass Factor 0.100
m2/kW 2.9 Resulting RH 51 %
W/m2 347.2 Design supply temp. 13.0 °C
Water flow @ 5.0 °K rise 9.29 L/s Zone T-stat Check 1 of 1 OK
Max zone temperature deviation 0.0 °K

Supply Fan Sizing Data


Actual max L/s 7567 L/s Fan motor BHP 10.60 BHP
Standard L/s 7511 L/s Fan motor kW 8.41 kW
Actual max L/(s-m2) 13.54 L/(s-m2) Fan static 600 Pa

Outdoor Ventilation Air Data


Design airflow L/s 1230 L/s L/s/person 4.40 L/s/person
L/(s-m2) 2.20 L/(s-m2)

Hourly Analysis Program v4.80 Page 3 of 6


Air System Design Load Summary for At-L1-3
Project Name: ME2058 zoneload 20171129 12/13/2017
Prepared by: Meinhardt M&E Limited 05:48PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1400 HEATING DATA AT DES HTG
COOLING OA DB / WB 31.8 °C / 26.3 °C HEATING OA DB / WB 6.0 °C / 4.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 387 m2 52021 - 387 m2 - -
Wall Transmission 0 m2 0 - 0 m2 0 -
Roof Transmission 0 m2 0 - 0 m2 0 -
Window Transmission 0 m2 0 - 0 m2 0 -
Skylight Transmission 387 m2 6408 - 387 m2 17531 -
Door Loads 0 m2 0 - 0 m2 0 -
Floor Transmission 559 m2 2314 - 559 m2 1845 -
Partitions 0 m2 0 - 0 m2 0 -
Ceiling 0 m2 0 - 0 m2 0 -
Overhead Lighting 19565 W 19564 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 280 17888 32702 0 0 0
Infiltration - 720 2312 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 9891 3501 0% 0 0
>> Total Zone Loads - 108806 38515 - 19376 0
Zone Conditioning - 106305 38515 - -276 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 7567 L/s 0 - 7567 L/s 0 -
Ventilation Load 1230 L/s 8726 32128 1230 L/s 8840 0
Supply Fan Load 7567 L/s 8409 - 7567 L/s -8409 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 123440 70643 - 156 0
Central Cooling Coil - 123440 70660 - 0 0
>> Total Conditioning - 123440 70660 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program v4.80 Page 4 of 6


Air System Sizing Summary for At-L1-4
Project Name: ME2058 zoneload 20171129 12/13/2017
Prepared by: Meinhardt M&E Limited 05:48PM

Air System Information


Air System Name At-L1-4 Number of zones 1
Equipment Class CW AHU Floor Area 766.0 m2
Air System Type SZCAV Location Xiamen, China

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 231.2 kW Load occurs at Jul 1400
Sensible coil load 137.9 kW OA DB / WB 31.8 / 26.3 °C
Coil L/s at Jul 1400 8418 L/s Entering DB / WB 27.2 / 20.9 °C
Max block L/s 8418 L/s Leaving DB / WB 13.6 / 13.1 °C
Sum of peak zone L/s 8418 L/s Coil ADP 12.0 °C
Sensible heat ratio 0.596 Bypass Factor 0.100
m2/kW 3.3 Resulting RH 53 %
W/m2 301.9 Design supply temp. 13.0 °C
Water flow @ 5.0 °K rise 11.07 L/s Zone T-stat Check 0 of 1 OK
Max zone temperature deviation 0.1 °K

Supply Fan Sizing Data


Actual max L/s 8418 L/s Fan motor BHP 11.79 BHP
Standard L/s 8355 L/s Fan motor kW 9.35 kW
Actual max L/(s-m2) 10.99 L/(s-m2) Fan static 600 Pa

Outdoor Ventilation Air Data


Design airflow L/s 1685 L/s L/s/person 4.40 L/s/person
L/(s-m2) 2.20 L/(s-m2)

Hourly Analysis Program v4.80 Page 5 of 6


Air System Design Load Summary for At-L1-4
Project Name: ME2058 zoneload 20171129 12/13/2017
Prepared by: Meinhardt M&E Limited 05:48PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1400 HEATING DATA AT DES HTG
COOLING OA DB / WB 31.8 °C / 26.3 °C HEATING OA DB / WB 6.0 °C / 4.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 367 m2 49332 - 367 m2 - -
Wall Transmission 0 m2 0 - 0 m2 0 -
Roof Transmission 0 m2 0 - 0 m2 0 -
Window Transmission 0 m2 0 - 0 m2 0 -
Skylight Transmission 367 m2 6077 - 367 m2 16625 -
Door Loads 0 m2 0 - 0 m2 0 -
Floor Transmission 559 m2 2314 - 559 m2 1845 -
Partitions 0 m2 0 - 0 m2 0 -
Ceiling 0 m2 0 - 0 m2 0 -
Overhead Lighting 26810 W 26808 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 383 24512 44811 0 0 0
Infiltration - 987 2937 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 11003 4775 0% 0 0
>> Total Zone Loads - 121033 52523 - 18470 0
Zone Conditioning - 116987 52523 - -1963 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 8418 L/s 0 - 8418 L/s 0 -
Ventilation Load 1685 L/s 11533 40810 1685 L/s 11555 0
Supply Fan Load 8418 L/s 9353 - 8418 L/s -9353 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 137873 93334 - 239 0
Central Cooling Coil - 137873 93355 - 0 0
>> Total Conditioning - 137873 93355 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program v4.80 Page 6 of 6