Project Name

Revision

Approved by

LEASE 1ERO

CHAP REF

ESTIMATE FOR HORA

HOUR OF OPERATION
CONDITIONS DB
OUTDOOR (OA) [ºF] 95.36
2

ROOM (RM) [ºF] 75


DIFFERENCE [ºF] 20.36
O
25
VENTILATION
906.09
CFM VENTILA

SWINGING REVOLVING DOORS


6

OPENS DOORS
INFILTRATION E
CRACK
CFM INFILTR
CFM OUTDOOR AIR TH
APPA
ESHF
ESHF =

ADP INDICATED ADP

1-
TEMP. RISE 22.95
EFFECTIVE ROOM SENSIBLE HE
DESHUM CFM =
8

1,08 x TEMP RISE


ROOM SENSIBLE HEAT(Btu
OUTLET TEMP. DIFF =
1,08 x DESHUM CFM
SUPPLY AIR QUANT
ROOM SENSIBLE HEAT(Btu
SUPPLY CFM =
SUPPLY CFM =
1,08 x OUTLET TEMP. DIF

BYPASS CFM = SUPPLY CFM - DESHUM C

RE

Troom 75 ºF + CFMoa/CFMsupply

TEDB 93.55 ºF

TADP 48 ºF + B.f

TLDB 54.83 ºF

FROM PSYCH. CHART : TEWD

NOTES

1. USE DRY-BULB (DB) TEMPERATURE DIFFERENCE FROM TOP OF


2. USE MOISTURE CONTENT (GR/LB) DIFFERENCE FROM TOP OF
3. NORMALLY. USE "CFM VENTILATION" FOR "CFM OUTDOOR A
WHEN INFILTRATION IS TO BE OFFSET, REFER TO PAGE 92 TO
"CFM OUTDOOR AIR."
4. WHEN INFILTRATION IS NOT TO BE OFFSET, AND "CFM VENTILAT
"CFM INFILTRATION," THEN THE EXCESS INFILTRAITON IS ACCOU
* IF THIS DIFF TEMP IS TOO HIGH, DETERMINE SUPPLY CFM FOR DESIRED
AIR QUANTITY FORMLA.
#
WHEN BYPASSING MIXTURE OF OUTDOOR AND RETURN AIR, USE SUPPL
RETURN AIR ONLY, USE DEHUMIFIED CFM.
COOLIN

GYM

TABLE REFERENCE
LOCAL TIME
SUN TIME PEAK LOAD

8
WB % RH DP GR/LB
0 80 0 206
0 50 0 65.6
XXX XXX XXX 140.4
OUTDOOR AIR
PEOPLE X 30 CFM/PERSON 750
SQ FT X 0.1 CFM/SQ FT = 90.609
CFM VENTILATION 750

0 PEOPLE 0 CFM/PEOPLE
0 DOOR 0 CFM/DOOR
EXHAUST FAN
0 FEET 0 CFM/FEET
CFM INFILTRATION 0
CFM OUTDOOR AIR THRU APPARATUS 750
APPARATUS DEWPOINT
EFFECTIVE ROOM SENSIBLE HEAT(Btu/hr)
0.170
EFFECTIVE ROOM TOTAL HEAT(Btu/hr)
48 ºF 48 ºF
DEHUMIDFIED AIR QUANTITY
0.15 X (Troom 75 ºF
ºF
TIVE ROOM SENSIBLE HEAT(Btu/hr)
823 CFMDA
1,08 x TEMP RISE
OOM SENSIBLE HEAT(Btu/hr)
20 ºF
1,08 x DESHUM CFM
SUPPLY AIR QUANTITY
OOM SENSIBLE HEAT(Btu/hr)
823 CFMSUPPLY
823 CFMSUPPLY
1,08 x OUTLET TEMP. DIFF

UPPLY CFM - DESHUM CFM - CFMBYPASS

RESULTING ENT & LVG CONDITIONS AT APPARATUS


EDB
0.91 X (TOUTDOOR 95.36 ºF -

LDB
0.15 X (TEDB 93.55 ºF -

0 ºF TLWD 0

TES PROCEDIMIENTO

FFERENCE FROM TOP OF ESTIMATE FORM. 1. RELLENAR LAS CELDAS UNICAMENTE Q


FERENCE FROM TOP OF ESTIMATE FORM.
N" FOR "CFM OUTDOOR AIR" HOWEVER 2. LA CELDA DEL DATO ES EN LA QUE SE
ET, REFER TO PAGE 92 TO DETERMINE QUE TIENE
DOOR AIR." 3. LLENE LOS ESPACIO CONFORME VA
SET, AND "CFM VENTILATION IS LESS THAN QUE TIENE EL COLOR ROJO
S INFILTRAITON IS ACCOUNTED FORHERE.
UPPLY CFM FOR DESIRED DIFFERENCE BY SUPPLY
TITY FORMLA.
RETURN AIR, USE SUPPLY CFM WHEN BYPASSING
USE DEHUMIFIED CFM.
COOLING LOAD CALCULATION SHEET

Prepared by

Lacation

Sheet Nº:

CHAP REF
LOCAL TIME
HORA SUN TIME

TADP [ºF] B.f

3&4
48 0.15

0
0
0
0

CFM OA
5

adimensional

ANTITY
- TADP 48 ºF)
6
3&7
3&7
Troom 75 ºF)

2&3
TADP 48 ºF)

ºF

7
PROCEDIMIENTO DEL USO DE LA HOJA

8
LENAR LAS CELDAS UNICAMENTE QUE TIENEN LA SIGUIENTE FORMA: DATO

CELDA DEL DATO ES EN LA QUE SE TIENE QUE INTRODUCIR EL VALOR NUMERICO

6
QUE TIENE EL COLOR AZUL
LENE LOS ESPACIO CONFORME VAYA AVANZANDO Y LEA EL RESULTADO FINAL
QUE TIENE EL COLOR ROJO PARA SABER LA CARGA DEL LOCAL

3&7
5
7
8
7
7
Prepared by JOSE ALBERTO BAL

Lacation

Sheet Nº:

TABLE REFERENCE

ITEM AREA OR QUANTITY

SOLAR GAIN-GLASS (Btu/hr)

GLASS 0 SQ FT X
GLASS 0 SQ FT X
GLASS 0 SQ FT X
GLASS 0 SQ FT X
SKYLIGHT 0 SQ FT X

SOLAR & TRANS. GAIN-WALLS & ROOF (Btu/hr)

WALL 0 SQ FT X
WALL 0 SQ FT X
WALL 0 SQ FT X
WALL 0 SQ FT X
ROOF - SUN 0 SQ FT X
ROOF - SHADED 0 SQ FT X

TRANS. GAIN-EXCEPT WALLS & ROOF (Btu/hr)

ALL GLASS 0 SQ FT X
PARTITION 426.74 SQ FT X
CEILING 0 SQ FT X
FLOOR 0 SQ FT X
INFILTRATION 0 CFM X

INTERNAL SENSIBLE HEAT (Btu/hr)

PEOPLE 25 RATE METABOLIC


POWER 430 WATTS
LIGHTS 1443 WATTS
APPLIANCE ETC. 0 X
ADDITIONAL HEAT GAIN 0 X

SUB TOTAL 1 ( Btu/hr)

STORE 0 SQ FT X

SUB TOTAL 2 ( Btu/hr)

SAFETY FACTOR 10 %

ROOM SENSIBLE HEAT (Btu/hr)

SUPPLY DUCT "MAS" SUPPLY DUCT


HEAT GAIN % 0 LEAK LOSS %
OUTDOOR AIR 750 CFM X
EFFECTIVE ROOM SENSIBLE HEAT(Btu/hr)

LATENT HEAT (Btu/hr)

OUTDOOR AIR 750 CFM X


PEOPLE 25 RATE METABOLIC
STEAM 0 Lbs/hr
APPLIANCE ETC. 0 X
ADDITIONAL HEAT GAIN 0 X
VAPOR TRANS. 0 SQ FT X

SUB TOTAL 3 ( Btu/hr)

SAFETY FACTOR 5 %

ROOM LATENT HEAT (Btu/hr)

SUPPLY AIR DUCT LEAK LOSS 0


OUTDOOR AIR 750 CFM X
EFFECTIVE ROOM LATENT HEAT(Btu/hr)
EFFECTIVE ROOM TOTAL HEAT(Btu/hr)

OUTDOOR AIR HEAT (Btu/hr)

SENSIBLE 750 CFM X

LATENT 750 CFM X


RETURN DUCT RETURN DUCT
0
HEAT GAIN % + LEAK GAIN %
HP DEHUM. &
0
PUMP % + PIPE LOSS %

SUB TOTAL 4 ( Btu/hr)

GRAND TOTAL HEAT


JOSE ALBERTO BALDES

E REFERENCE

SUNGAIN OR TEMP. DIFF

-
S (Btu/hr)
FACTOR
0 BTU/hr X 0
0 BTU/hr X 0
0 BTU/hr X 0
0 BTU/hr X 0
0 BTU/hr X 0

-
S & ROOF (Btu/hr)
FACTOR
0 ºF X 0
0 ºF X 0
0 ºF X 0
0 ºF X 0
0 ºF X 0
0 ºF X 0

1,782
S & ROOF (Btu/hr)
FACTOR
13.5733333333 BTU/hr X 0
13.5733333333 ºF X 0.3077
13.5733333333 ºF X 0
13.5733333333 ºF X 0
13.5733333333 ºF X 1.08

EAT (Btu/hr) 14,516

325 BTU/hr
1467.16 BTU/hr
4923.516 BTU/hr
Correction Factor of Appliance 0
Correction Factor of Additional heat gain 0

Btu/hr) 16,298

0 X 0

Btu/hr) 16,298

AT (Btu/hr) 17,928

"MAS" FAN
0 H.P 0
20.36 ºF X B.f 0.15
20,401 X 1.08

tu/hr) 84,729

140.4 GR/lbs X 0.68


525 BTU/hr
0 BTU/hr
Correction Factor of Appliance 0
Correction Factor of Additional heat gain N/A
140.4 GR/lbs X 0

Btu/hr) 84,729

T (Btu/hr) 88,965

%
140.4 GR/lbs X B.f 0.15
99,706 X 0.68
L HEAT(Btu/hr) 120,108

T (Btu/hr) 11,084

20.36 ºF X B.f 0.15


X 1.08
140.4 ºF X B.f 0.15
X 0.68
0

Btu/hr) 11,084

131,192 BTU/hr

11 T.R