You are on page 1of 7

MAJAX-2 GENERAL SPECIFICATION

Majax-2 axial flow fans are manufactured in IMPELLER FINISH


diameters ranging from 315mm to 2000mm Majax-2 315-1000 and 1250-F hubs are electro-coated, Majax-2
(available in 2250mm on request), and incorporate 1250H hubs are aluminium cast, Majax-2 1600 to 2250 hubs are
manually adjustable pitch aluminium bladed fabricated and hot dip galvanised. Aluminium surface finishes are
impellers. The following configurations are left natural. All fasteners are zinc plated.
available: BALANCING
- Direct driven units with the impellers attached directly onto the Impellers are dynamically balanced to ISO 1940 grade G6,3.
shafts of totally enclosed motors mounted directly in the
airstream. CASINGS - DIRECT DRIVE
- Belt-driven units with the motors mounted out of the airstream Standard casing lengths (SL) usually cover the impeller and motor
on the outside of the fan casings. assemblies. External terminal boxes are provided on the casings of
- Bifurcated units with motors mounted in bifurcations, out of the fans fitted with standard totally enclosed motors (see brochure for
airstream. connection details). Where flame-proof motors are fitted, a length
- BELLAX fans with impellers attached directly onto the shafts of of armoured cable, which passes through the fan casing, is
totally enclosed motors and mounted on fibreglass plates with connected to the motor. The free ends of these cables are to be
bell shaped entries. connected to fittings appropriate to the installation.
- Majax-2 Plate mounted with the impellers attached directly onto Smoke extraction fans are fitted with external, certified terminal
the shafts of totally enclosed motors and mounted on carbon boxes and conduit for the selected application.
steel plates. Casings incorporate viewing ports unless access panels are
- Vertical jet, roof mounted extraction units, available in two provided.
ranges (HVJ-2 & HVJ-2S). See roof unit brochure for further
information. CASINGS - BELT DRIVE
Standard casing lengths cover the overall length of the impeller and
APPLICATIONS belt drive assemblies. Generally, motors would not project beyond
This range of fans is ideally suited for moving large volumes of air the casing flanges.
against low and medium pressures in the following applications: Standard belt drive fans incorporate casing access panels.
- General ventilation: kitchen canopies, supermarkets, airport
buildings, underground car parks, stairwell pressurization, FLANGE DIMENSIONS AND DRILLINGS
gymnasiums and stadium cloak rooms, industrial buildings, etc. Flange dimensions and drillings are in accordance with BS 6339.
- Air-conditioning. See brochure for details.
- Smoke control and exhausting heat from buildings.
- Condenser cooling. CASING FINISH
- Cooling towers. Casings are hot-dip galvanized to ISO 1461. All fasteners are zinc
Combinations of motor speeds, impeller blade pitch settings, and plated.
the number of blades per impeller (full and half solidity), provide
flexibility in terms of selection. Fans offering good efficiencies can
be selected over a range of volumes from 0,1m3/s to 85m3/s at total
pressures up to 1,0 kPa.

SIZES
The MAJAX-2 range is available in the following sizes:
- Standard direct drive fans in 12 sizes:
from 315mm to 2000mm (available in 2250mm on request).
- Standard belt drive fans in 11 sizes:
from 400mm to 2000mm.
- Bifurcated fans in 7 sizes:
from 400mm to 1250mm.
- BELLAX in 7 sizes:
from 315mm to 1000mm.
- Plate mounted axial fans in 8 sizes:
from 400mm to 1000mm.
- Vertical jet roof units:
HVJ-2 in 3 sizes from 630mm to 1000mm.
HVJ-2S in 7 sizes from 400mm to 900mm.

Sizes vary in accordance with the preferred increments covered in


ISO 497 - 1973 (E) R20. The sizes are: 315, 400, 500, 560, 630, 710,
800, 900, 1000, 1250, 1600, 2000 and 2250.

IMPELLERS
Impellers incorporate die-cast aluminium alloy blades of aerofoil
section, which are clamped in split steel hubs (Majax-2 1250H
impellers have split aluminium cast hubs). Blade pitch adjustment is
achieved by slackening the hub clamping bolts and setting the
blades to the required pitch prior to re-tensioning the clamp bolts.
MOTORS PERFORMANCE
Up to frame size 160, pad mounted motors are used in most direct All performance data is based on tests carried out in accordance
driven fans. For all other applications foot mounted motors are with BS 848: Part 1 - Test method No. 1. Ratings are based on
used. Both pad and foot mounted motors are totally enclosed. standard air density of 1,20kg/m3 corresponding to an air
Minimum protection is IP55 for pad and foot mounted motors. temperature of 20°C, a barometric pressure of 101,325 kPa and a
Standard motors have Class F insulation. Standard voltages are 400 relative humidity of 62%. Power values given reflect fan shaft power
volt three phase and 220/230 volt single phase, 50Hz. Electrical without provision for drive losses.
performance complies with IEC 34.
Motors with non-standard classes of insulation, special grease for SOUND DATA
high/low temperature operation, flameproof construction, special The sound data indicated on the performance graphs are "In-duct"
voltages, multi-speed, etc., may be available on application. values obtained from tests conducted in accordance with BS 848:
Part 2 - In-duct method. The higher values on the Sound Level
MOTOR SUPPORTS contours are Overall Sound Power Levels (suffixed dBW), and the
Direct driven fans up to size 1000, driven by pad mounted motors lower values are Average Sound Pressure Levels, under free field
up to frame 132, have motors mounted in plates suspended in conditions, at a distance of 3 impeller diameters from the fan inlet or
rubber mountings to minimize noise and vibration. All other pad outlet. Sound Power Levels are given in decibels re: 10-12 Watts.
mounted motors are mounted by means of support rods. Sound Pressure Levels are given in decibels re: 2 x 10-5 Pa.
An octave band analysis can be obtained by subtracting the
Belt driven fans utilize foot mounted motors fitted to motor supports spectrum constants, tabulated on each performance graph, from the
mounted externally on the fan casings. Overall Sound Levels.
A-Scale levels are obtained by subtracting an A-Scale correction
DIRECTION OF AIR FLOW constant, given on each performance graph, from the Overall Sound
Forms B, BD and BU are standard arrangements for direct drive Level.
fans, having motors mounted downstream of the fan impellers. "Free-field" sound levels incorporating inlet/outlet end reflection
losses, are obtained by subtracting the following constants from the
"In-duct" Octave Band Sound Levels.

AD
OCTAVE BAND MEAN FREQUENCY
A AU FAN 1000 &
SIZE 63 125 250 500 ABOVE
315 14 9 5 2 0
400 13 8 3 1 0
B BD BU
500 11 6 2 0 0
560 10 5 2 0 0
Forms A, AD and AU are standard arrangements for belt drive fans, 630 9 5 1 0 0
having the bearing and drive assemblies mounted upstream of the
800 7 3 1 0 0
fan impellers. These forms can also be used on direct drive fans.
Mechanical details and bearing selections on all MAJAX-2 fans, 1000 6 1 0 0 0
whether direct or belt drive, are suitable for any of these attitudes. 1250 5 1 0 0 0
However, impellers require changing from Form A to Form B 1600 3 0 0 0 0
running. 2000 2 0 0 0 0
BEARING LIFE (L10) REVERSAL OF AIR FLOW
Direct driven 2 pole units are designed to have a 20 000 hour The direction of air flow of a standard impeller can be reversed by
statistical bearing life, and 4,6 and 8 pole units are designed to have changing the direction of fan rotation. Equal volume flow in either
a 40 000 hour statistical bearing life. Belt driven units are designed direction can be provided by means of special blade adjustments.
to have a statistical 40 000 hour bearing life. The approximate resultant fan performance for the above
conditions when compared with standard fan performance is as
follows:
TEMPERATURE LIMITATIONS
MAJAX-2 fans are suitable for operating within the following
temperature ranges: STANDARD REVERSIBLE
- Standard direct drive fans: - 20°C to + 50°C. IMPELLER IMPELLER
- Standard belt drive fans: - 10°C to + 50°C. Volume Reduction 30% 15%
- Bifurcated fans: - 20°C to + 200°C. Pressure Reduction 55% 25%
- BELLAX: - 20°C to + 50°C.
Impellers from 500 to 1000 have been successfully tested in Power Reduction 25% 20%
accordance with BS 7346 : Part 2: 1990 at 300°C for 2 hours.
Impeller diameter 1600 has been successfully tested in accordance OPTIONAL FEATURES
with BS 7346: Part 2: 1990 at 300°C for 1 hour. Mounting feet, counter flanges, wire screens, conical inlets, anti-
vibration mountings, casing access panels & flexible connections.
MOISTURE TREATMENT Hand, motor or airstream operated dampers.
Standard fans are suitable for continuous operation in relative Cylindrical attenuators of matching sizes.
humidities up to 95%. Special treatment of fans is available to render Non-standard casing lengths & special protective coatings.
them suitable for continuous operation in moisture laden Belt guards & belt fairings (belt drive fans).
atmospheres. This treatment involves additional mechanical and
electrical sealing procedures.
All technical information contained herein is subject to change without prior notice.
FAN DIRECT DRIVE BELT DRIVE Mass Mass
SIZE FAN SPEED (rpm) - MOTOR POWER (kW) MOTOR POWER B C D F G H I J K L
A 2 POLE 4 POLE 6 POLE 8 POLE (kW)

315 0.25 to 0.75 0.08 to 0.55 0.06 to 0.55 - - 315 355 380 8 11 - - 22 27 -
0.55 to 2.2 0.18 to 0.55 0.12 to 0.55 - 0.25 to 0.75 400 512 22 38 51
400 - - - 1.1 to 1.5 - 450 485 8 13 585 500 - - 60
- - - 2.2 to 4.0 - 627 - - 91
0.75 to 2.2 0.18 to 1.5 0.12 to o.55 - 0.25 to 0.75 400 573 22 47 62
500 3.0 to 4.0 - - - 1.1 to 1.5 400 626 22 75 71
560 607 12 13 500
- - - - 2.2 to 4.0 - 688 - - 103
- - - - 5.5 to 7.5 - 725 - - 135
1.1 to 2.2 0.37 to 1.5 0.12 to 0.55 - 0.25 to 0.75 400 627 500 22 44 67
3.0 to 4.0 - - - 1.1 to 1.5 400 680 500 22 79 76
560 5.5 to 7.5 - - - 2.2 to 4.0 500 620 667 12 13 722 500 22 110 108
- - - - 5.5 to 7.5 - 759 500 - - 139
- - - - 11.0 to 15.0 - 874 740 - - 246
- 0.37 to 1.5 0.12 to 1.1 - 0.25 to 0.75 400 666 22 47 71
630 3.0 to 4.0 2.2 to 3.0 - - 1.1 to 1.5 400 718 22 81 80
690 737 12 13 500
5.5 to 7.5 - - - 2.2 to 4.0 500 761 22 116 112
11.0 - - - 5.5 to 7.5 630 798 34 167 145
- 0.55 to 1.5 0.55 to 1.2 0.27 0.55 to 0.75 400 689 22 54 75
710 - 2.2 to 4.0 1.5 to 2.2 0.75 to 1.5 1.1 to 1.5 400 742 22 89 84
770 817 16 13 500
- 5.5 to 7.5 3.0 to 5.5 - 2.2 to 4.0 500 804 22 123 116
- - - - 5.5 to 7.5 - 841 - - 149
- 0.75 to 1.5 0.55 to 1.1 0.27 0.75 400 737 22 64 87
800 - 2.2 to 4.0 1.5 to 2.2 0.75 to 1.5 1.1 to 1.5 400 790 22 98 95
860 907 16 13 500
- 5.5 to 7.5 3.0 - 2.2 to 4.0 500 852 22 132 129
- 11.0 - - 5.5 to 7.5 710 889 34 223 161
- 1.1 to 1.5 0.55 to 1.1 - 0.75 400 810 500 22 86 110
900 - 2.2 to 4.0 1.5 to 2.2 0.75 to 1.5 1.1 to 1.5 400 863 500 22 123 120
- 5.5 to 7.5 3.0 to 5.5 2.2 to 3.0 2.2 to 4.0 500 970 1039 16 13 905 500 22 160 152
- 11.0 to 15.0 - - 5.5 to 7.5 630 942 500 34 233 184
- - - - 11.0 to 15.0 - 1066 740 - - 324
- - 1.1 - 1.1 to 1.5 400 915 500 22 94 131
- 3.0 to 4.0 1.5 to 2.2 0.75 to 1.5 2.2 to 4.0 400 957 500 22 133 164
- 5.5 to 7.5 3.0 to 5.5 2.2 to 3.0 5.5 to 7.5 560 994 500 22 180 194
1000 - 11.0 to 15.0 7.5 to 11.0 4.0 11.0 to 15.0 770 1070 1141 16 15 1119 740 34 279 362
- 18.5 to 22.0 - - 18.5 to 22.0 770 1159 740 34 337 412
- - - - 30.0 - 1172 990 - - 573
- - - - 37.0 - 1238 990 - - 670
- - 3.0 to 5.5 - 5.5 to 7.5 560 1172 710 22 300 330
- 11.0 to 15.0 7.5 to 11.0 - 11.0 to 15.0 800 1250 800 34 420 454
- 18.5 to 22.0 15.0 - 18.5 to 22.0 800 1290 800 34 480 513
1250 H - 30.0 18.5 to 22.0 - 30.0 850 1320 1392 20 15 1312 850 42 540 612
- 37.0 to 45.0 30.0 - 37.0 to 45.0 1000 1378 850 - 670 704
- 55.0 to 75.0 - - 55.0 to 75.0 1000 1514 1000 - 879 1101
- 90.0 - - - 1120 - - - 1112 -
- - 2.2 1.1 to 1.5 - 560 - - 22 195 -
1250 F - - 3.0 to 5.5 2.2 to 3.0 - 560 - - 22 243 -
- - 7.5 to 11.0 4.0 to 7.5 - 800 1320 1392 20 15 - - 34 363 -
- - 15.0 11.0 - 800 - - 34 418 -
- - 18.5 to 22.0 - - 850 - - 42 478 -

All technical information contained herein is subject to change without prior notice.
FAN DIRECT DRIVE BELT DRIVE Mass Mass
SIZE FAN SPEED (rpm) - MOTOR POWER (kW) MOTOR POWER B C D F G H I J K L
A 2 POLE 4 POLE 6 POLE 8 POLE (kW)

- - 11 4.0 to 7.5 5.5 to 7.5 740 1350 740 34 514 431


- - 15.0 11.0 11.0 to 15.0 740 1431 990 34 572 616
1600 - - 18.5 to 22.0 15.0 15.0 to 22.0 990 1471 990 42 708 672
1680 1743 24 19
- - 30.0 18.5 to 22.0 30.0 1190 1500 990 - 905 779
- - 37.0 to 45.0 30.0 to 37.0 37.0 to 45.0 1190 1566 990 - 1072 867
- - 55.0 to 75.0 - 55.0 to 75.0 1490 1704 1190 - 1313 1280
- - - 11.0 18.5 to 22.0 740 1670 990 34 737 841
- - - 15.0 30.0 990 1704 990 42 883 958
- - - 18.5 to 22.0 37.0 to 45.0 1190 1770 990 - 1127 1045
2080 2173 24 19
2000 - - - 30.0 to 37.0 55.0 to 75.0 1190 1914 1190 - 1274 1480
- - - 45.0 to 55.0 90.0 to 110.0 1490 1968 1190 - 1593 1792
- - - 75.0 - 1490 - - - 1806 -

FAN
FAN C D E F MASS FAN
FAN MASS
MASS
SIZE
SIZE Kg SIZE
SIZE BS
315 355 320 8 11 1.52 (ØA)
(ØA) Kg
400 450 405 8 13 2.64 315 120 1.60
500 560 507 12 13 4.12 400 120 2.77
560 620 567 12 13 4.56 500 120 4.33
630 690 637 12 13 5.08 560 120 4.79
710 770 717 16 13 5.68 630 120 5.33
800 860 807 16 13 12.68 710 120 5.96
900 970 909 16 13 18.28 800 120 13.31
1000 1070 1011 16 15 20.7 900 120 19.19
1250 1320 1262 20 15 25.52 1000 120 21.74
1600 1680 1613 24 19 32.28 1250 160 26.80
2000 2080 2013 24 19 49.56 1600 160 33.89
2000 160 52.04

FAN C D E MASS FAN


FAN MASS
MASS
SIZE P Q R SIZE
SIZE S
(ØA) KG (ØA)
(ØA) Kg
315 56 422 372 3.99 315 220 13
400 71 524 474 6.09 400 260 18
500 90 648 598 9.11 500 300 25
560 100 720 670 10.39 560 310 29
630 112 804 754 12.04 630 345 34
710 125 905 855 15.38 710 385 48
800 140 1006 956 17.85 800 430 58
900 162 1170 1090 31.18 900 480 85
1000 181 1286 1206 35.67 1000 530 102
1250 224 1603 1503 50.41 1250 655 157
1600 280 2050 1920 89.09 1600 830 340
IVC dimensions available on request
2000 355 2537 2407 142.22 2000 1030 421

FAN
FAN T U V W X Y MASS
MASS
SIZE
SIZE Kg
315 35 20 11 125 140 240 0.41
400 40 22 13 162 180 285 0.59
500 40 22 13 232 250 355 1.28
560 39 22 13 232 250 385 1.91
630 39 22 13 262 280 420 2.20
710 39 22 13 282 300 465 2.21
800 39 22 13 332 350 518 3.81
900 54 30 15 355 380 595 4.86
1000 59 35 15 385 410 653 7.59
1250 60 35 15 525 555 812 13.05
1600 75 40 19 590 625 1035 20.54
2000 75 40 19 790 825 1234 29.19

All technical information contained herein is subject to change without prior notice.
Majax-2 (2 Pole - 2880 r/min Performance Curves)

Majax-2 (4 Pole - 1440 r/min Performance Curves)


Majax-2 (6 Pole - 960 r/min Performance Curves)

Majax-2 (8 Pole - 720 r/min Performance Curves)


Majax-2 (10 Pole - 580 r/min Performance Curves)

TYPICAL ELECTRICAL CONNECTIONS


SINGLE PHASE FANS 3 PHASE FANS - STAR WIRED

L N E L1 L2 L3 E

L3

W1

L N V1 L2

W2
U1 U2 V2

L1

380-415V 3 Ph 50Hz

3 PHASE FANS - 3 PHASE FANS -


DELTA WIRED UP TO 7.5kW DELTA WIRED 11kW & ABOVE
L1 L2 L3 E L1 L2 L3 E

L1 L2 L3
L3
U1 V1 W1

U1 V1 W1
W1 U2
V2 V1
L2
U1 W2
U2 W2 V2
L1
U2 W2 V2

380-415V 3 Ph 50Hz 380-415V 3 Ph 50Hz


Factory Fitted Link Wires Factory Fitted Link Wires