5.6.3 TRANSFORMER PERCENT DIFFERENTIAL

PATH: SETTINGS ÖØ GROUPED ELEMENTS Ö SETTING GROUP 1(6) Ö TRANSFORMER Ö PERCENT DIFFERENTIAL

„ PERCENT PERCENT DIFFERENTIAL Range: Disabled, Enabled


„ DIFFERENTIAL FUNCTION: Disabled
PERCENT DIFFERENTIAL Range: 0.050 to 1.000 pu in steps of 0.001
MESSAGE
PICKUP: 0.100 pu
PERCENT DIFFERENTIAL Range: 15 to 100% in steps of 1
MESSAGE
SLOPE 1: 25%
PERCENT DIFFERENTIAL Range: 1.000 to 2.000 pu in steps of 0.001
MESSAGE
BREAK 1: 2.000 pu
PERCENT DIFFERENTIAL Range: 2.000 to 30.000 pu in steps of 0.001
MESSAGE
BREAK 2: 8.000 pu
PERCENT DIFFERENTIAL Range: 50 to 100% in steps of 1
MESSAGE
SLOPE 2: 100%
INRUSH INHIBIT Range: Disabled, Adapt. 2nd, Trad. 2nd
MESSAGE
FUNCTION: Adapt. 2nd
INRUSH INHIBIT Range: Per phase, 2-out-of-3, Average
MESSAGE
MODE: Per phase
INRUSH INHIBIT Range: 1.0 to 40.0% of f0 in steps of 0.1
MESSAGE
LEVEL: 20.0% fo 5
OVEREXCITN INHIBIT Range: Disabled, 5th
MESSAGE
FUNCTION: Disabled
OVEREXCITN INHIBIT Range: 1.0 to 40.0% of f0 in steps of 0.1
MESSAGE
LEVEL: 10.0% fo
PERCENT DIFF BLOCK: Range: FlexLogic™ operand
MESSAGE
Off
PERCENT DIFFERENTIAL Range: Self-reset, Latched, Disabled
MESSAGE
TARGET: Self-reset
PERCENT DIFFERENTIAL Range: Disabled, Enabled
MESSAGE
EVENTS: Disabled

The calculation of differential (Id) and restraint (Ir) currents for the purposes of the percent differential element is described
by the following block diagram, where “Σ” has as its output the vector sum of inputs, and “max” has as its output the input of
maximum magnitude; these calculations are performed for each phase.
The differential element design in G30 assumes that CT polarities at both sides of the GSU are used to provide forward
metered power. This essentially means that CTs should be wired to provide a 180° phase shift between the LV and HV
sides of the GSU currents. If there is an additional phase shift caused by the wye-delta connection of the transformer, then
it has to be accounted for in the SYSTEM SETUP ÖØ TRANSFORMER menu. Please refer to section 9.1.1 for additional infor-
mation. The differential current is calculated as shown below after magnitude and phase compensation for all windings.

I d = I 1 comp – I 2 comp (EQ 5.25)

The restraint current is calculated as a maximum of the same internally compensated currents.

I r = K × max ( I 1 comp , I 2comp ) (EQ 5.26)

The element operates if Id > PKP and Id > Ir, where PKP represents a differential pickup setting and K is a restraint factor.

GE Multilin G30 Generator Protection System 5-115


5.6 GROUPED ELEMENTS 5 SETTINGS

Winding 1 Winding 2 Winding ‘n’


current
waveform
current
waveform ... current
waveform

Magnitude Magnitude Magnitude


phase angle, and phase angle, and phase angle, and
zero sequence zero sequence zero sequence
compensation compensation compensation
(as required) (as required) (as required)

Decaying dc Decaying dc Decaying dc


offset filter offset filter offset filter

Discrete Fourier Discrete Fourier Discrete Fourier


Transform Transform Transform

∑ MAX

5 Differential Restraint
phasor phasor

828714A1.CDR

Figure 5–49: PERCENT DIFFERENTIAL CALCULATIONS


The G30 percent differential element is based on a configurable dual-breakpoint / dual-slope differential restraint character-
istic. The purpose of the preset characteristic is to define the differential restraint ratio for the transformer winding currents
at different loading conditions and distinguish between external and internal faults. Differential restraint ratio variations
occur due to current unbalance between primary and secondary windings and can be caused by the following:
1. Inherent CT inaccuracies.
2. Onload tap changer operation: it adjusts the transformer ratio and consequently the winding currents.
3. CT saturation.
10

Breakpoint 2
8

6
Transition region
Id (Ir)

(cubic spline) Slope 2


region
4

Breakpoint 1

2
Pickup

0 2 4 6 8 10
Ir
828750A1.CDR

Figure 5–50: PERCENT DIFFERENTIAL OPERATING CHARACTERISTIC

5-116 G30 Generator Protection System GE Multilin


5 SETTINGS 5.6 GROUPED ELEMENTS

• PERCENT DIFFERENTIAL PICKUP: This setting defines the minimum differential current required for operation. It is
chosen, based on the amount of differential current that might be seen under normal operating conditions. Two factors
may create differential current during the normal transformer operation: errors due to CT inaccuracies and current vari-
ation due to onload tap changer operation.
A setting of 0.1 to 0.3 is generally recommended (the factory default is 0.1 pu).
• PERCENT DIFFERENTIAL SLOPE 1: This setting defines the differential restraint during normal operating conditions
to assure sensitivity to internal faults. The setting must be high enough, however, to cope with CT saturation errors dur-
ing saturation under small current magnitudes but significant and long lasting DC components (such as during distant
external faults in vicinity of generators).
• PERCENT DIFFERENTIAL BREAK 1 and PERCENT DIFFERENTIAL BREAK 2: The settings for break 1 and break
2 depend very much on the capability of CTs to correctly transform primary into secondary currents during external
faults. Break 2 should be set below the fault current that is most likely to saturate some CTs due to an AC component
alone. Break 1 should be set below a current that would cause CT saturation due to DC components and/or residual
magnetism. The latter may be as high as 80% of the nominal flux, effectively reducing the CT capabilities by the factor
of 5.
• PERCENT DIFFERENTIAL SLOPE 2: The slope 2 setting ensures stability during heavy through fault conditions,
where CT saturation results in high differential current. Slope 2 should be set high to cater for the worst case where
one set of CTs saturates but the other set doesn't. In such a case the ratio of the differential current to restraint current
can be as high as 95 to 98%.
• INRUSH INHIBIT FUNCTION: This setting provides a choice for 2nd harmonic differential protection blocking during
magnetizing inrush conditions. Two choices are available: “Adapt. 2nd” – adaptive 2nd harmonic, and “Trad. 2nd” – tra-
ditional 2nd harmonic blocking. The adaptive 2nd harmonic restraint responds to magnitudes and phase angles of the
2nd harmonic and the fundamental frequency component. The traditional 2nd harmonic restraint responds to the ratio
of magnitudes of the 2nd harmonic and fundamental frequency components. If low second harmonic ratios during
magnetizing inrush conditions are not expected, the relay should be set to traditional way of restraining. 5
• INRUSH INHIBIT MODE: This setting specifies mode of blocking on magnetizing inrush conditions. Modern transform-
ers may produce small 2nd harmonic ratios during inrush conditions. This may result undesired tripping of the pro-
tected transformer. Reducing the 2nd harmonic inhibit threshold may jeopardize dependability and speed of protection.
The 2nd harmonic ratio, if low, causes problems in one phase only. This may be utilized as a mean to ensure security
by applying cross-phase blocking rather than lowering the inrush inhibit threshold.
If set to “Per phase”, the relay performs inrush inhibit individually in each phase. If used on modern transformers, this
setting should be combined with adaptive 2nd harmonic function.
If set to “2-out-of-3”, the relay checks 2nd harmonic level in all three phases individually. If any two phases establish a
blocking condition, the remaining phase is restrained automatically.
If set to “Average”, the relay first calculates the average 2nd harmonic ratio, then applies the inrush threshold to the
calculated average. This mode works only in conjunction with the traditional 2nd harmonic function.
• INRUSH INHIBIT LEVEL: This setting specifies the level of 2nd harmonic component in the transformer magnetizing
inrush current above which the percent differential element will be inhibited from operating. The value of the INRUSH
INHIBIT MODE setting must be taken into account when programming this value. The INRUSH INHIBIT LEVEL is typically
set to 20%.
• OVEREXCITATION INHIBIT MODE: An overexcitation condition resulting from an increased volts/hertz ratio poses a
danger to the protected transformer, hence the volts/hertz protection. A given transformer can, however, tolerate an
overfluxing condition for a limited time, as the danger is associated with thermal processes in the core. Instantaneous
tripping of the transformer from the differential protection is not desirable. The relay uses a traditional 5th harmonic
ratio for inhibiting its differential function during overexcitation conditions.
• OVEREXCITATION INHIBIT LEVEL: This setting is provided to block the differential protection during overexcitation.
When the 5th harmonic level exceeds the specified setting (5th harmonic ratio) the differential element is blocked. The
overexcitation inhibit works on a per-phase basis.

GE Multilin G30 Generator Protection System 5-117


5.6 GROUPED ELEMENTS 5 SETTINGS

The relay produces three FlexLogic™ operands that may be used for testing or for special applications such as building
custom logic (1-out-of-3) or supervising some protection functions (ground time overcurrent, for example) from the 2nd har-
monic inhibit.

SETTING
PERCENT DIFFERENTIAL SETTINGS
FUNCTION: PERCENT DIFFERENTIAL
Disabled = 0 PICKUP:
Enabled = 1 PERCENT DIFFERENTIAL
SLOPE 1:
FLEXLOGIC OPERANDS
SETTING PERCENT DIFFERENTIAL
XFMR PCNT DIFF PKP A
BREAK 1:
PERCENT DIFF BLOCK: XFMR PCNT DIFF PKP B
PERCENT DIFFERENTIAL
XFMR PCNT DIFF PKP C
Off = 0 SLOPE 2:
PERCENT DIFFERENTIAL
ACTUAL VALUES FLEXLOGIC OPERANDS
BREAK 2:
XFMR PCNT DIFF OP A
DIFF PHASOR AND RUN
XFMR PCNT DIFF OP B
Iad
Iad XFMR PCNT DIFF OP C
Ibd AND
Icd Iar
AND RUN
Ibd
FLEXLOGIC OPERAND
ACTUAL VALUES
AND OR XFMR PCNT DIFF OP
REST PHASOR Ibr
AND RUN
Iar Icd
Ibr
Icr AND
Icr

SETTING SETTING

5 INRUSH INHIBIT
FUNCTION:
INRUSH INHIBIT LEVEL:

Disabled =0 INRUSH INHIBIT MODE:


FLEXLOGIC OPERANDS
Adapt. 2nd
=1 RUN
Trad. 2nd Iad2 > LEVEL XFMR PCNT DIFF 2ND A

RUN
ACTUAL VALUES XFMR PCNT DIFF 2ND B
Ibd2 > LEVEL
DIFF 2ND HARM RUN
Icd2 > LEVEL XFMR PCNT DIFF 2ND C
Iad2
Ibd2
Icd2

SETTING
OVEREXC ITN INHIBIT SETTING
FUNCTION: OVEREXC ITN INHIBIT
Disabled = 0 LEVEL: FLEXLOGIC OPERANDS
5th = 1 RUN
Iad5 > LEVEL XFMR PCNT DIFF 5TH A

ACTUAL VALUES RUN


Ibd5 > LEVEL XFMR PCNT DIFF 5TH B
DIFF 5TH HARM
RUN
Icd5 > LEVEL XFMR PCNT DIFF 5TH C
Iad5
Ibd5
Icd5
828001A6.CDR

Figure 5–51: PERCENT DIFFERENTIAL SCHEME LOGIC