Professional Documents
Culture Documents
TRAINING COURSE
1
PLANNING OF THE POWER
DISTRIBUTION NETWORK
For the correct sizing of a power network, the following
calculations have to be done:
SIZING CALCULATION of machine, transformer, etc.;
SHORT CIRCUIT CURRENT CALCULATION;
NEUTRAL SYSTEM;
LOAD FLOW;
MOTOR STARTING;
DYNAMIC STABILITY CALCULATION;
CALCULATION OF THE HARMONICS IN THE NETWORK;
RELAY COORDINATION.
2
TIME PHENOMENA IN AN
ELECTRICAL SYSTEM
zLOADS
for each user has to be established quality, availability and continuity of the
supply;
zPOWER SUPPLY
it has to be evaluated whether additional power supply coming from self-
production, reserve, emergency or safety is needed;
zNETWORK STRUCTURE:
choice of scheme, machines (and their size), devices, protection and control
have to be homogeneous.
These parameters influence the voltage levels, rated currents and
short circuit level of the network. 4
SINGLE RADIAL
The radial system in a multiple
voltage levels network has a “tree”
structure with possible busbars
feeding loads distributed along the
path.
ADVANTAGES:
- simple
- economic
DISADVANTAGES:
- maintenance (all network downstream
of the maintenance point has to be
put out of service)
- vulnerability (in case of failure, all
downstream network will be out of
service)
5
DOUBLE RADIAL
It‛s characterized by the redundancy of
a single radial system.
This redundancy can be extended up to
the single user, but most of the time it‛s
only up to one or more nodes (busbar) of
the distribution system.
It‛s mainly used in the network for
process industry where the service
continuity is a must.
ADVANTAGES:
- short out of service duration in case of
failure;
DISADVANTAGES:
- expensive to be realized.
6
RING MAIN SYSTEM
7
RING MAIN SYSTEM
This scheme is characterized by the presence of at list one feeder
more than the minimum necessary to connect the loads to the power
supply. Such a network can work either as open or close ring: with the
first configuration, in case of failure, the failing part has to be
disconnected and then the power supply can be re-connected; with the
close ring configuration it‛s only necessary to disconnect the part
where the failure occurred (the service continuity is assured).
It‛s mostly used in case of small users (small power required) at
considerable distance from each other.
ADVANTAGES:
- service continuity, when working in the close ring configuration
DISADVANTAGES:
- quite expensive to be realized
- complicated protection system
8
AUTOMATIC TRANSFER
STARTING STARTING
AUTOMATIC
BLOCK TRANSFER BLOCK
9
2
CALCULATION OF SHORT
CIRCUIT:
INFORMATION NECESSARY
FOR RELAY COORDINATION
1
SHORT CIRCUIT
Rated current Short circuit current
4
SHORT CIRCUIT CURRENT
It is important to calculate the short circuit
current (single phase and poly-phase) into the
different plant operating conditions.
• EN 60909-0 -2001-12
SHORT CIRCUIT CURRENT
CALCULATION IN A.C. THREE
PHASE NETWORK
8
Table n°1 standard EN 60909-0
Voltage factor
The introduction of the voltage factor ‘c‛ is necessary for various
reasons. These are:
9
Symmetrical and
asymmetrical short circuit
SIMMETRICAL ASIMMETRICAL
Without unidirectional component Presence of unidirectional component
I Asymmetrical peak
I
t
t
U U
t t
10
Ipothesis: prevalent inductive source
TYPE OF SHORT CIRCUIT FAULTS
SYMMETRICAL FAULT: IL1 = IL2 = IL3
ASYMMETRICAL FAULT:
IL1 = IL2
14
figure 2 standard EN 60909-0
GENERATOR DECREMENT SHORT CIRCUIT
The generator short current is not a fixed value but decrease during
the time.
The equation of the fault current (effective value, only symmetric
component) at the generator terminal (mainly inductive circuit) is as
follow:
1 1 t /T"d 1 1 t / T 'd 1
I (t) In e e
x"d x' d x' d xd xd
where: In = generator rated current;
X"d = subtransient reactance;
X'd = transient reactance;
Xd = synchronous reactance;
T"d = subtransient time constant;
T'd = transient time constant.
15
SOURCE OF SHORT CIRCUIT
CURRENT
16
CONTRIBUTION TO THE SHORT
CIRCUIT CURRENT
Motors contribute to the short circuit current, especially influencing the peak value.
Their contribute is in fact mainly during the subtransient phase, therefore they have to
be considered in the short circuit calculation. Their contribute and its duration depends
on the magnetic gap therefore from the energy not the running power.
z External network
cUn
I"k Ik=I”k
3 Rr Xr
2 2
z Synchronous machine
cUn
I"k Un cmax
3Kg RG2 XG2 with Kg
UkG 1 X"G senϕG
z Asynchronous machine
c Un
I"k
3 Rn2 Xn2
Ik=0 17
short circuit calculation
with power method
19
3
PHASE TO GROUND
FAULT:
DIFFERENT METHODS
AND RELEVANT
PROTECTION CRITERIA
GROUNDING
CAUSES OF FAULTS:
Mechanical
Insulation failure.
The phase to ground faults are the most pro a le faults and they ecame
always phase
to phase or three phase faults.
NEUTRAL STATE:
HV networks solidly grounded
MV networks in industrial plant generally resistance grounded. In
distri ution networks, insulated, solidly, resistance or
reactance grounded
LV networks generally solidly grounded (special cases insulated and for
industrial plant in some cases grounded with resistor).
Criteria of neutral state
The choice of the neutral state involve many pro ect choice
TECHNICAL overvoltages
ground fault current
choice of the e uipments
connection with the existing network.
COSTS
MANA EMENT service continuity
SEC RIT
NATIONAL AND LOCAL HA IT.
The choice of the neutral state, for the industrial plant, shall e done
according with the process responsi le.
STATE OF THE NEUTRAL
IMPEDANCE SOLID
ISOLATED RO NDED RO NDED
INFLUENCE ON THE PHASE to
GROUND SHORT CIRCUIT
CURRENT
EARTH FAULTS EFFECTS:
400
350
SA E PHASES
300
250
200 NE TRAL TO RO ND
150
100
50 A LTED PHASE
0
P1 Portatile; 13/02/2004
ISOLATED NEUTRAL: SCHEMATIC
DIAGRAM
Ig = 2 cos30° Co U = 3Co E = 3 Io
ISOLATED NEUTRAL:
ADVANTAGES & DISADVANTAGES
ADVANTAGES:
- Limited fault current (only capacitive);
- Network still in service even after one phase-earth failure (only when
limited capacitive current). A second earth fault in another phase,
will create a multiphase short circuit and an immediate tripping is
needed.
DISADVANTAGES:
- Difficult fault detection;
- Possible intermittent discharge to earth (4-6 times the line voltage);
- High transient overvoltages and permanent overvoltages on the
healthy phases (line voltage);
- Risk of ferroresonance in the voltage transformers;
- Higher insulated equipment and therefore more expensive;
- Complex protection system.
Neutral insulated:
service continuity
SOLID GROUNDED: SCHEMATIC
DIAGRAM
SOLID GROUNDED:
ADVANTAGES & DISADVANTAGES
ADVANTAGES:
- no overvoltages;
- no need of ground fault protective relays;
- simple and selective protection system;
DISADVANTAGES:
- high fault current and relevant network perturbation (voltage
drop);
- no service continuity;
- high step and touch voltages close to the failure point
(grounding network sizing).
RESISTANCE GROUNDED:
SCHEMATIC DIAGRAM
IG = IC + IR IC = 3 Co E
IR = E / R
1 IR = IC
Where R = ------------
3 Co Ig = 1.41 IC
RESISTANCE GROUNDED:
ADVANTAGES & DISADVANTAGES
ADVANTAGES:
- fault current is limited by the impedance (energy at the failure
point is reduced);
- simple and selective protection system (fault current calculated
on the basis of the protection system);
- reduced overvoltages;
DISADVANTAGES:
- no service continuity (the faulted branch has to be removed);
- machine are less expensive (less insulation), but there are
additional costs for the grounding device.
METHODS OF RESISTANCE
GROUNDING
E AMPLES
DETERMINATION OF THE ground
(EARTH) FAULT CURRENT
The fault current If has to be determined taking into consideration that
•If --->0 it has to be the lowest possible to reduce the damages where
the failure occurred and to reduce the voltage fall in the
network;
•If >Ic the resistive component has to be greater than the capacitive
component in order to reduce overvoltages and avoid
intermittent arcs;
•If > .... it has to be great enough to assure the correct relays’
intervention selectivity
The first statement is obvious.
The second one is easy to calculate according with the network
configuration.
The third condition needs a protection coordination study, which depends
on the type of protection (range of setting of the relay and measuring
methods, either toroidal-ring CT’s or residual connected CT’s).
GENERATOR ground fault
withstand capability
MOTOR WITHSTAND capability for
internal ground fault
REACTANCE NEUTRAL (PETERSEN)
Normally the reactance is with taps (variable reactance).
The operating principle is based on the criteria to generate a
inductive current equal to the capacitive current. With this
solution, the current into the faulted point became equal to
zero.
In order to have the possibility to identify the faults, other
than the inductive component, also a resistive component is
generated.
ADVANTAGES:
- small grand fault current (limited by the resistance
component);
- high capability of arc self-extinguish;
- low costs for grounding network;
DISADVANTAGES:
- high cost (partially compensated by lower number of
shutdown);
- complex and expensive protection system;
- disturbances to the communication lines during faults.
Inductive and capacitive current
with compensated network
C
Network CAPACITIVE CURRENTS
CAPACITIVE CURRENTS
• In the case of a network with insulated neutral, the choice and setting
of the ground overcurrent protections require checks that depend on
the network layout, the characteristics of the protections and the
function they are intended to carry out within the protection system.
The condition to be satisfied is that the ground, non-directional relays
placed to protect each of the two lines trip only for faults on their own
line.
• This is why the setting value of the ground overcurrent relay tripping
threshold must be greater than the contribution of the line itself to the
fault current;
z I - - T T S S
z I - - I T S S
z I - - T I T T S S
z I - - T I TT S S
FUNCTION:
- reduce voltage and current values in the system to values that may be
detected by instruments and protection equipment.
- make the secondary instrument and protection circuits galvanically
independent from the primary power circuit, simultaneously ensuring greater
operator safety (a secondary point of the instrument transformer must always
be earthed).
T ;
ISI SS;
T ;
;
T T .
4
VOLTAGE TRANSFORMER
FOR INSTRUMENTS
PRECISION CLASSES
,
, T S TS
, I ST I S TS
S IT I ST TS
efinition example v v -
6
NOTES ON fERRORESONANCE
PHENOMENA ON VT
The ferroresonance phenomenon is a typical aspect of T inserted in cable
networks with an isolated or not effectively earthed neutral.
The cable capacity, along with the T inductance, constitutes an oscillating
circuit ( ). Thus conditions may occur on the circuit in which the circuit
goes into resonance (capacitive reactance saturated inductive reactance
of the T) and, although the cause of saturation may cease (for example,
an earth fault), transitory oscillation remains (thus at a multiple of the
mains frequency) of the reactive energy put into play by the components of
the oscillating circuits.
The frequency of this oscillation produces a permanent, high circulation of
current in the primary winding alone.
Since this current is only magneti ing, the secondary winding is barely
affected, thereby heating the primary circuit considerably but the
secondary circuit to a negligible degree.
The abnormal heating of the windings always produces high internal
pressure, which eventually ruptures the outer housing. 7
ELIMINATION OF FERRORESONANCE
PHENOMENA ON VT
The main measures to be taken in order to avoid
ferroresonance phenomena are
I I S TI T ;
T I S TI ;
T ;
T I T;
T S T;
T T S TI ;
T T S T- I IT T;
T I T;
T ;
ISI SS;
T ; 9
.
MAGNETIZATION CURVE
AND CT SCHEME
10
MAGNETIZATION CURVE FOR
INSTRUMENT AND PROTECTION CT
11
CURRENT TRANSFORMERs FOR INSTRUMENTs
PRECISION ,
CLASSES: , T S TS
, I ST I S TS
S IT I ST TS
12
Error of CURRENT
TRANSFORMERS
The (for both protection and
instrument T) is
T
100 1
e% 2
( Kn is ip ) dt
Ip T 0
with
n transformer ratio;
Ip effective primary current value;
ip instantaneous primary current value;
is instantaneous secondary current value;
t period. 13
CURRENT TRANSFORMERS FOR
PROTECTION
PRECISION CLASSES:
z T
z
z (at l)
z T
z ST I TI
z (at l)
ccuracy limit factor ( l) follows the precision class, and defines the overcurrent that the
T can sustain without reach the set error limits (precision current limit Ipl)
ormal values - - -
efinition example -
14
CURRENT TRANSFORMERS
according standard iec 60044-6
T are divided into the following classes
16
CT DEFINITIONS IN CLASS PX
(old TYPE X according with Standard BS 3938
superceded by Standard 7626:1993 )
CLASS PX T - T , I T
I T S
z I T S;
z S T S;
z I T T ( k);
z S SIST ;
z TI TI T ( ormally at k ).
Sct TS - S TI ;
Sn T T ;
Sr T T T T;
Sct Sn 0.8 20
F ' l Fl 15 284
Sct Sr 0 .8 0 .3
changing the secondary resistance of the T
T ct . r . l
Sct Sn 0.4 20
F ' l Fl 15 437
Sct Sr 0.4 0.3
19
REAL ACCURACY limit factor with
unidirectional component
If unidirectional component is present in the current,
the real precision limit factor changes as follows (in
simplified form)
1
F ''l F 'l
1 X R
20
CT TEST REPORT
T ST T
.
IT I
T
Ik . k
Ip . k
21
CT REQUIRMENTS
urrent transformers ( T) to be used with protection devices must
satisfy the following requirements
- they must not saturate before the protections are sure to trip
(indicatively speaking, normally twice the setting for the overcurrent
protections);
- they must not saturate within a time interval shorter than the sampling
time of the protection, to ensure proper functioning of the relay;
The true precision limit factor (F'I) may be verified by analy ing the
secondary circuit of the T (secondary T resistance, wiring,
protection) to determine the secondary current value at which the knee
voltage k of the T is reached (all resistances should obviously be
considered at a value of ). 22
ELECTROMAGNETIC CT
(ROGOWSKY COIL)
Takes advantage of the mp re theorem to bind the voltage at the
terminals of the secondary winding to the flow that develops in the non-
magnetic material by effect of the electromagnetic field created by the
primary current. roduces a signal in proportion to the derivation of the
current. equires an electronic integrator.
on-linearity and saturation conditions do not exist, since there is no
magnet involved. There is also no hysteresis.
The main disadvantage is the low secondary power; it therefore may not
be used with traditional electromechanical or solid-state relays.
ADVANTAGES:
z electrical insulation
z thermal stability
23
CT AND VT FOR DIGITAL
PROTECTIONS
IT I IT T TI S, T S ST TS
SI T S I ST T T TI
S S. I I I T T, T T ISI
SS S I SI T S ST T
T S I I TI .
EXAMPLE:
- T l . and
- T l . and
24
GROUND FAULT
MEASURING METHOD
25
CONNECTION OF RING CURRENT
TRANSFORMER
26
5
fusES
1
STANDARD AND FUSE
CLASSIFICATION
REFERENCE STANDARD: EN 60282
FIRST CHARACTER
- g BREAKING CAPABILITY ON FULL RANGE
- a BREAKING CAPABILITY WITH REDUCED RANGE
SECOND CHARACTER
- G GENERAL PURPOSE
- M MOTOR PROTECTION
2
FusES: definiTIONS 1
Breaking Current
Effective value of the tide interrupted presumed that a fuse is able
to interrupt to the established tension and under conditions
prescribed of use and of behavior.
Current interrupted presumed
Valued presumed current in correspondence of the instant in
which a fuse begins the arc during an interruption.
Interrupted limited current
Maximum instant value reached by the current during the
operation of interruption of a fuse.
Minimum interruption current
Least value of presumed current, that a cartridge is able to
interrupt to one determined voltage and under conditions defined
of use and of behavior.
3
FusES: definiTIONS 2
Characteristic time/current
Curved showing the duration (for example the duration of
prearcing or the duration of operation) in operation of the effective
value of the symmetrical component of the presumed current, in
you define conditions of operation.
Duration of prearcing (latest of fusion)
Interval of time among the beginning of an intense current
sufficiently to provoke the fusion of the element or the meltable
elements and the instant in which it has beginning an arc.
Duration of arc
Interval of time between the instant of beginning of the arc and the
instant of final extinction of the arc.
Recovery Voltage
Tension that introduces to the heads of a fuse after the
4
interruption of the current.
FUSES DEFINITIONS
TIME
SHORT CIRCUIT START
ARCING TIME
5
CHARACTERISTICS OF
FUSES
It is a protection, not an apparatus of manoeuvre (but it can be
him associate);
It gathers in itself the function of relay (cheap) and the function
of interrupter (it has a very elevated power of interruption) it is
not restored;
It directly intervenes interrupting the circuit when the current is
over a determined value for a certain time in conformity to the
curve of intervention.
It limits the value of peak of the presumed current.
BEFORE MELTING
AFTER MELTING 7
EXPLODED FUSE
In= rated
current;
I1=current
least of
interruption
(2÷6 In)
I2=current of
arc that
produces the
condition of
maximum
energy
(20÷100 In);
I3=current
that furnishes
the maximum
ability of
interruption
(20÷508 kA).
CURRENT VERSUS TIME
CHARACTERISTIC
Pre-arcing
time
[s]
9
foreseen short circuit current (RMS) [A]
CURRENT LIMITING EFFECTS
Limited
peak current
[kA]
10
foreseen short circuit current (RMS) [A]
CONTACTOR PLUS FUSES
COORDINATION
Fuse melting (breaking) curve
t
Contactor breaking current
ta
I>
I
11
FUSE CURRENT SELECTION
MOTOR FEEDER:
- The nominal current of the fuse has to be great than at least 1.3
- 1.6 times (it depends on the builder) the nominal current of the
motor.
- The nominal current of the fuse has to be such to be allowed the
foreen startings (it is necessary to know: current starting, time
of starting, number of startings /hour. to See charts of selection
of the builders).
TRANSFORMER FEEDER:
- The fuse has to be able to bear the tide of magnetization.
- The fuse has to be able to bear brief overloads (generally
defined equal to 5 times the rated current of the transformer for
5 seconds).
12
6
PROTECTION SYSTEM:
GENERAL INFORMATION
ABOUT ELECTRICAL
PROTECTIVE RELAYS
1
EFFECTS OF INCORRECT
PROTECTION TRIPPING
2
DISTURBANCES IN DISTRIBUTING
ELECTRICAL POWER
z S SS
- causes internal short-circuit
external network faults or maneuvers
- solutions appropriate network layout
emergency power supply
protection coordination
z T S
- causes short-circuit
starting large motors
- problems motors stall
contacts de-energi ed
- solutions adequate si ing of transformers and conductors, careful
selection of motor starter, coordinated protections. 3
THE PROTECTION SYSTEM
This must limit personal in ury and damage to the system
z llow various operating conditions.
z nsure continuous service for those areas of the system
not affected by faults.
z ctivate the necessary automated mechanisms.
z The protection system is the overall group of
- relays with adequate setting ranges;
- instrument transformers;
- opening alarm logics that contribute to system protection;
- moving parts;
- auxiliary power supply system.
The relay itself is only one component of the protection
system. 4
PECULIAR FETURES OF THE
PROTECTION SYSTEM
z Dependency:
it may be called upon to work following a brief or long interval after
installation. In any case, it must work whenever it is called upon to do so.
z Safety:
it must not be tripped when not needed (it must not trip during
transients). It must allow various operating conditions and activate the
necessary automated mechanisms.
z Selectivity:
it must trip only when necessary, ensuring continued service with
minimum network down-time.
z Speed:
represented by brief fault intervals and limited machinery damage.
z Simplicity:
measured by the amount of equipment necessary to protect the network.
z Economy:
assessed as the cost of the protection system in relation to the cost of
malfunctions. 5
ELECTRICAL SYSTEM FAULTS
z OVERCURRENTS - nomalous overheating of the conductors and machines
educed life-span
z CURRENT UNBALANCES
- otor overheating
elted conductors
The effects of a fault are essentially electrical, thermal and mechanical in nature.
6
ClassificaTION OF TH FAULTS
FOR DURATION
- T - STI IS it disappears before the intervention of the
instant protections ( ms);
FOR TYPOLOGY
In base to the typology of the faults they distinguish in single phase7to
ground, phase to phase and phase to phase to ground.
PRINCIPAL CAUSES OF FAULTS
- SI I S TI it can for instance be caused by the superficial
pollution on the insulators (single phase to ground or phase to phase to ground
fault);
- S it is the most frequent cause for the lines in cable, besides possible
overvoltages of inside origin and to degradation of the cable insulation are
8
often sub ect to due breakdowns to obs of excavation.
GENERAL CRITERIA FOR THE
PROTECTION SYSTEM
9
CRITERIA FOR CHOOSING
A PROTECTION SYSTEM
Standards;
z acceptable risk (consequences of the fault);
z short-circuit currents (maximum and minimum);
z neutral status;
z self-production;
z coordination with the existing system;
z network configurations and operating criteria;
z habits.
Objective:
- to achieve the best possible technical-economic compromise, allowing
adequate protection from significantly probable faults;
- ensure that the investment is proportional to the Importance of the
system. 10
RELIABILITY AND AVAILABILITY
OF THE PROTECTION SYSTEM
I I IT S
z T IT
- I I ;
- I S I I TI S;
z T IT
- T I I TI S;
-T T STS;
z S ST T
- ST TI ;
- ISSI I ;
- I T . 11
PeCULIARITIES OF THE PROTECTION
SYSTEM
T I I I IT T T, T S
S T I TI S
T S I T ;
T S I T ;
T S I T I T ;
T S S S ;
T S S IT I T ( ean Time etween ailure);
T S S IT TT ( ean Time To epair);
T S IT TI S T I STI .
12
ELECTRICAL PROTECTION:
LOGICAL SCHEME
13
ELECTRICAL PROTECTION
rotection may be either direct (fuse, thermomagnetic release, etc.) or
indirect (protection relay powered by instrument transformers, T
and or T).
z OPERATING CHARACTERISTIC: I IT TI
I S TI
TI
I ST T S
z INTERFACE WITH CIRCUIT BREAKER: I T
I I T
z AUXILIARY SUPPLY:
T S
z TECHNOLOGY: TT I
ST TI
I IT 15
Time [s]
CURVES
CURRENT-
TIME FOR A
THERMO-
MAGNETIC
RELEASE
16
Current [A x 100]
Operating characteristic of electronic
releases installed on lv circuit breakers
t
z Thermal protection adjustable L Stage L
17 I
PROTECTION RELAYS
REFERENCE STANDARDS
I T
OBSOLETE
18
IEC 60255
19
RELAY sYMBOLS
elay or similar device.
ST I - The asterisk must be replaced by
graphic symbol distinctive symbols indicating the
characteristic si e and its means of
variation, energy transmission direction,
* setting range, reset ratio, delayed action,
delay value.
umerical codes are sometimes used to indicate protection devices, for
example overcurrent, undervoltage, etc., numerical coding was
introduced with into the I from standard. Into standard
- change the symbol.
CONSUMPTION
-AUXILIARY CIRCUIT - - L L
-INSTRUMENT CIRCUIT H H L L
SETTING RANGE L M H H
MAINTENANCE H H M L
ELECTROMAGNETIC COMPATIBILITY - - M H
PROTOCOL COMPATIBILITY - - - H
COST M H L H 23
ADVANTGES USING MICROPROCESSOR-
BASED PROTECTION DEVICES
z more accurate measuring methods;
z supervision of operating conditions;
z standardi ation of equipment with fewer types less cabling;
z remote setting;
z direct display of settings and measurements;
z reduced number and performance of instrument transformers;
z possibility of including special functions;
z improved selectivity with dedicated systems;
z analysis of phenomena with reconstruction of fault operating
parameters;
z enabled communication with improved data acquisition;
z support for programming calculated scheduled maintenance;
z on line network calculations;
z rapid commissioning. 24
TYPES OF PROTECTION DEVICES
(APPLICATIONS)
z one protection devices (e.g. residual-current or impedance);
z achine protection devices (e. g. reverse power);
25
PROTECTION DEVICES AND
THEIR FAULTS
MTBF MDT
Conventional
protection devices
MTTR
MDT
Digital protection
devices (in self-
test mode)
MTBF
igital protection devices are self-controlling
T mean down-time
TT mean troubleshooting and time to repair 26
T mean time between faults
BLOCK DIAGRAM
OF A DIGITAL PROTECTION
S
A/I MUX A/D
H Analog-digital
conversion
COM
I>
MMI Numerical
DSP U<
SCS/S signal
Z<
1 DiffGen on
2 Current on
COM MS analysis
3 BinInp 2 off
etc.
trip
Binary
B/I signal
etc.
B/O process
27
RELAY operating curves
DEFINITE TIME-DELAY INVERSE TIME-DELAY
t t
t1
t1 t2
I1 I1 I2 I
Instrument relays with definite time-delay: … operating times may be
considered to be independent from the operating values of the
characteristic specification.
I
ith indirect relays the opening time of the operating part comes
from the trip time of the relay added to the operating time of the
circuit brea er and any au iliary relays included.
30
TIME-CURRENT CURVE
FOR THERMAL RELAY
STANDARD IE .
t
I 2 Ip2
t ln 2 2 τ
I k Ib
Ip pre-load current
old curve I let-through current
arm curve Ib base current
t trip time
I 31
DIRECTIONAL PROTECTION
OPERATING DIAGRAM
In
TRIPPING AREA
NON-TRIP AREA
I
rit
I n
33
DIFFERENTIAL PROTECTION operating
criteria (kirchoff law)
id i1 i2
34
“SELF-BALANCING”
DIFFERENTIAL PROTECTION
35
OVERFLUXING PROTECION
V%
VOLTAGE
PROTECTION
f%
FREQUENCY
36
Underimpedance PROTEction
(DISTANce relay)
X
X
zone 3
zone 2
zone 1
Trip area
R 0 R
37
Application of
UNDERIMPEDANCE relay
The relays measure the mains impedance and trip hen
the impedance falls belo the set value.
These relays are normally used to protect lines and in
this case are no n as distance relays since the
impedance of a line is proportionate to its length.
The center of the circumference trape oids are used
for more comple protections varies based on the relay
application.
38
RE-CLOSING RELAYS
close
A open
TR rapid re-closing pause time
TR slo re-closing pause time
TN neutrali ation time after rapid re-closing
TN neutrali ation time after slo re-closing.
39
7
ELECTRICAL EQUIPMENT
PROTECTION
1
TYPICAL LINE FAULTS
OVERLOAD: A SES current greater than the rated si ed value
EFFE TS overheating that induces precocious aging
of the insulating materials of the cables.
3
DISTANCE relay defINITIONS
z one of distance protection
- first one generally covers of the trip line ithout intentional delays
- second one covers more than of the line delayed tripping
- third one covers more than the second one of the line delayed tripping
- one A covers more than of the line also no n as the accelerated
one. Tripping is instantaneous hen a signal is received from the opposite
end
- start-up one usually not directional. overs more than one has a long
delay
z verreach
a length or impedance setting greater than the length impedance of the line
z nderreach
a length or impedance setting lo er than the length impedance of the line
z hec line function
hen the circuit brea er closes the instantaneous one briefly covers more
than of the line. The loc against reclosing is normally provided hen this
function is implemented.
TIME
SOURCE
DISTANCE
Distance relays ith several steps are used to protect lines to identify
both internal and e ternal approaching faults for the protected one.
7
ROTATING MACHINE:
DIRECT SEQUENCE CURRENT
HARMONIC N. 7 (DIRECT SEQUENCE)
TIME
8
ROTATING MACHINE:
ZERO SEQUENCE CURRENT
HARMONIC N. 3 (ZERO SEQUENCE)
TIM E
9
ROTATING MACHINE:
INVERSE SEQUENCE CURRENT
HARMONIC N. 5 (NEGATIVE SEQUENCE)
TIME
10
SYNCHRONOUS GENERATOR
The manufacturing specifications and si e of the alternator depend on
the primary motor and the type of service for hich it is foreseen
12
GENERATOR FAULT CURRENT
The symmetrical short-circuit current decreases over time.
The follo ing e uation sho s the progress of a dead short current over
time at the terminals of a generator in no-load conditions only the
symmetrical component is sho n
1 1 1 1 1
I(t) In et T"d et T'd
x"d x' d x' d xd xd
here In rated alternator current
d subtransient reactance
d transient reactance
d synchronous reactance
T subtransient time constant
T transient time constant.
The e uations for calculating the time constants of an impedance for
do nstream faults the impedance e uations for cable or transformer are
not ritten since they must obviously be added together are as follo s
X "d X reactance bet een the generator and the
T"d T"do fault point
X 'd X
X'd X T do subtransient open-circuit time constant
13
T ' d T ' do
Xd X T do transient open-circuit time constant.
Capability curves
Active current
underexcitation axe Iw overexcitation
Iw
Operation
practical limit
Rated operating point
(cosϕ = 0.88)
InW
Turbine power
limits
Stability
limit
In
ϕ
Reactive current
axe Iq
u Inq Iq
14
Xd
Rotating machine: negative
sequence capability
I2
1.6 In
1.4
1.2
0.8
0.6
0.4
0.2
Time (s)
0
0 20 40 60 80 100 120 140
15
Rotating machine: negative
sequence current
2
MAXIMUM I2/In FOR MAXIMUM (I 2/In) t FOR
TYPE OF MACHINE PERMANENT SERVICE OPERATION IN FAULT
CONDITION
SALIENT POLE
motors 0.10 20
CILINDRICAL
16
Rotating machine: zero
sequence capability
Effect of arc burning on stator core
laminations during earth fault
17
GENERATOR INTERNAL FAULTS
- SHORT-CIRCUIT: A SES phase-phase short-circuit or bet een the turns of the
same phase
EFFE TS - short-circuit current variable over time and based on
the energi ing system
- overheated indings.
- EARTH FAULT: A SES accident contact bet een the stator inding stator earth
or rotor inding rotor earth and earth magnetic circuit or
chassis
EFFE TS - in the case of a stator phase-earth fault the current
value of the fault depends on ho the neutral is
earthed
- in the case of rotor phase-earth fault no problems occur
at the first fault but the machine is less energi ed at
the second fault the field circuit has an insulated
neutral .
- LOSS OF FIELD: A SES fault in the field circuit or at the voltage regulator
EFFE TS - loss of synchrony
- absorption of all or part of the reactive energy from the
net or
- overheating of the stator and rotor current induced by
the rotary magnetic field 18
- voltage drop at the generator terminals.
GENERATOR EXTERNAL FAULT
SHORT-CIRCUIT: A SES - accidental phase-phase contact do nstream from
the generator terminals
EFFE TS - short-circuit current variable over time and based on
the energi ing system.
OVERLOAD: A SES - increased demand for electrical po er
EFFE TS - increase in the active current delivered thus
overheating the stator
- absorption of reactive current from the net or
thus overheating the stator and rotor
- reduced rotation speed and fre uency in island .
UMBALANCE: A SES - supply of an unbalanced load
- short-circuit bet een turns of the same phase
EFFE TS - currents in reverse se uence
- rotor overheated.
FREQUENCY A SES - speed regulator fault f fn or f fn
CHANGE: - po er delivered higher than rated level f fn .
EFFE TS - overheating in motors if f fn
- motor slo do n if f fn ith diminished
performance.
VOLTAGE A SES - voltage regulator fault n or n
CHANGE: - loss of energi ing V Vn .
EFFE TS - abnormal stress on insulation if n
- functional problems in motors if n 19
FAULTS IN THE generator
PRIMARY MOTOR
REVERSE POWER FLOW: A SES lac of energy from the primary
motor steam diesel etc.
21
Small l.v. generators
For the protection of the LV small
generator care shall be ta en to
- The LV generator circuit brea er
cannot find fault inside the
generator in stand alone operation
- If the generator and transformer
star point are both connected to
ground homopolar current can
circulate through the ground
connection. This current can reach
up to the of the generator
current. onse uently verification
shall be done that the ground fault
current protection shall have
third harmonic filter
- The T that supply the
overcurrent protection for the
generator V shall be located
22
on
generator star point side.
ASYNCHRONOUS MOTOR faults
In a statistical study carried out in the nited States on a family of
appro imately machines or ing from years under broadly
different climatic conditions and a ide range of applications it as found
that
- number of motors sub ect to faults appro imately
y analy ing the type of fault per component you can observe that of faults in
the stator are caused by insulation defects hile the remainder are due to defects
in the pac binding eys etc.
here the rotor is concerned half the faults are caused by defects regarding the
cage bars d.c. rings and the remainder regarding other components shaft pac .
The greatest number of faults ere caused by bearings by sliding
bearings by roller bearings by sealed bearings thrust bearings 23 oil
and other causes.
TORQUE-SPEED AND CURRENT-SPEED
CURVES FOR AN ASYNCHRONOUS MOTOR
25
Motor INTERNAL FAULTS
SHORT-CIRCUIT: A SES phase-phase contact or bet een the turns of
the same phase
EFFE TS - circulation of a very high current function of
the fault point and the po er supply net or
- electrodynamic strain
- melting of conductor materials and damage to
insulation.
EARTH FAULT: A SES accidental contact bet een the stator inding
stator earth or rotor inding rotor earth and
the magnetic circuit or chassis
EFFE TS - damage to the blade pac
- field circuit umbalance.
LOSS OF FIELD: A SES fault in the energi ing circuit only for
synchronous machines
EFFE TS - loss of synchrony
- absorption of the reactive energy needed for
operation from the net or
REPEATED START-UP: A SES consecutive repeated start-ups of the 26
motor
EFFE TS overheating mainly in the rotor circuit
Motor EXTERNAL FAULTS
(POWER SUPPLY NETWORK)
UNBALANCE: A SES - non-symmetrical supply voltages
- umbalanced or distorting loads on the
po er supply busbars of the motor
- lac of a phase e.g. fuse tripped
- harmonic distortion present in the voltage
EFFE TS - reverse se uence current
- rotor overheated
VOLTAGE DROP: A SES voltage drop e.g. caused by re-acceleration
or malfunction in the tap changer on the
transformers
EFFE TS - reduced motor tor ue and machine rotation
speed
- increase in the absorbed current causing
overheating.
27
FAULTS IN THE operating MACHINE
OVERLOAD: A SES increase in stall tor ue applied to the motor a le
EFFE TS - increase in the absorbed current causing overheating
- reduced electrical life-span of the machine.
LOAD LOSS: A SES problems ith the machine tool e.g. vacuum in a pump
EFFE TS machine overheating if the fluid cools .
REVERSE POWER FLOW: A SES reduced supply voltage only for synchronous
machines
EFFE TS the synchronous machine driven in rotation by the inertia of
the rotary masses delivers energy to ards the net or28 .
ELECTRICAL PROTECTION DEVICES OF
ASYNCHRONOUS MOTOR
rotective functions supplied by
T s and VT s.
Thermal protection device
connected to the temperature
sensors is not sho n
ndervoltage
ndercurrent
Negative se uence current
Too long starting and loc ed
rotor during running
Thermal overload
Short circuit could be ta en
over by fuses
N round fault overcurrent
Repeated start-ups
Differential. 29
CHARACTERISTICS OF THE TRANSFORMER
inrush CURRENT
The duration and value of the inrush current of a
transformer depend on
- the instant hen the transformer is connected
- supply net or short circuit po er
- resistance bet een the supply source and transformer
- rated transformer po er
- construction specifications of the transformer
- magnetic material of the core and its saturation
- any residual flu .
30
TRANSFORMER inrush CURRENT value
Io
I
1 Io X
here
I inrush current
Io inrush current ith infinite source po er
X source reactance in . . compared to the rated po er of the
transformer.
The table belo sho s the minimum and ma imum percentage values of the
harmonic distortion present in the inrush current during the initial phases
of the connection transient. The value that the harmonic distortion can
reach in e ceptional conditions is sho n in brac ets
31
WAVEFORM OF THE TRANSFORMER
inrush CURRENT
32
TRANSFORMER inrush CURRENT
The effective transformer inrush current may be calculated using the
follo ing e uation
t τ
K In e
I
2
The characteristic values for parameters K and τ are as follo s for the
most common transformer si es
Sn K τ
VA s
.
.
.
.
.
. 33
TYPICAL TRANSFORMER FAULTS
OVERLOAD: A SES increased loads or absorbed po er
EFFE TS overcurrent ith overheating reducing
the electrical life-span of the machine.
not noted
- verpressure uchol
- Thermal protection using sensors
- verflo magnetic circuit protection
- Ma imum ground current of enclosure .35
TRANSFORMER symmetrical and
asymmetrical faults
36
CONNECTING THE PROTECTION TO THE
STAR point OF THE TRANSFORMER
37
Capacitor faults and protections
OVERLOAD:
A SES voltage increase
EFFE TS - increased voltage gradient
and conse uent life
reduction
- increased absorbed
current.
SHORT CIRCUIT:
A SES insulation failure
EFFE TS dielectric punching.
EARTHFAULT:
A SES insulation failure
EFFE TS dielectric punching.
UNBALANCE:
A SES short circuit in one or
multiple capacitor elements
EFFE TS unbalanced load and
conse uent starpoint
shifting.
OTHER: current pea function of
and of the source impedance
at the capacitor ban
insertion ith an high
damping rate. 38
8
RELAY SELECTIVITY
CRITERIA
1
SELECTIVITY
z From the preface to the boo A LIED AND R TE TIVE RELAYIN
i1 i2
The protection trips hen the current flo s in a certain direction and
the current module e ceeds the setting.
5
APPLICATIONS FOR DIRECTIONAL
PROTECTION DEVICES
These protections are generally used ith ring net or s or parallel sources.
6
CURRENT-TYPE SELECTIVITY
I2 t B
A A
tB
I1
tA
B
B 1 A 2
The tripping selectivity is obtained by ad usting the upstream protection to a value
greater than the overcurrent that may circulate in the do nstream device
The current margin is generally - bet een indirect protection devices 7and
- bet een overcurrent releases.
TIME-TYPE SELECTIVITY
t
B tA A
tB B
IA/IB I1 I
B t
tA A Ti
circuit breaker B opening time (in BT 20ms)
tB B Tev
relay B error ( 10% tB)
9 t
B A 0
TIME STEP DEFINITION
For direct protection devices, the manufacturer provides the selectivity tables.
For selectivity between fuses and protection devices, the time margin to be considered is :
DT = 0.4 x Tf + 0.15 s with: Tf = fuse blow time;
For indirect protection devices with definite time-current curves, the time margin between
two protection devices in series( DT) should be calculated as follows:
DT = Te + Ta + Ti + To +Tm
Te = sum of the time errors of the relays downstream and upstream;
Ta = time for the auxiliary (lock) relays inserted in the opening circuit;
Ti = opening time for the circuit-breaker downstream;
To = 'overshoot' inertia time of the protection device upstream;
Tm = safety margin;
Indicatively speaking, the time margins to be considered with indirect protection devices are
as follows:
- 200-250 ms for tripping times of up to 500 ms;
- 250-300 ms for tripping times of between 500 and 1000 ms.
For indirect protection devices with inverse time-current curves, one doesn't need to take
the difference in times at the same current into account, but the difference in the times
considered between the current with the maximum positive tolerance upstream and the
current with the maximum negative tolerance downstream, in addition to the sum of the time
errors of the relays.
Indicatively speaking, the time margins to be considered with indirect protection devices are
as follows:
- 250-300 ms for tripping times of up to 500 ms; 10
- 300-400 ms for tripping times of between 500 and 1000 ms.
MIXED CURRENT AND
TIME SELECTIVITY
t B A t B A
A
B
A tA
pilot-wire
connection
B tB
The protection device trips when the current exceeds the setting value and no locking signals
arrive from other logically-interconnected protection devices.
The advantage lies in being able to apply only current-type selectivity with elements arranged
in series (essentially creating one selectivity). 12
This is applied to both phase and earth protection devices.
LOGICAL SELECTIVITY CIRCUIT BREAKER ‘D’
13
SELECTIVITY DIAGRAM (TCC)
14
CHARACTERISTCS OF COORDINATION SHEET
the sheet is bi-logarithmic;
the sheet must note the reference voltage;
the maximum fault overcurrent must be noted for both phase-phase and phase-earth faults;
the coordination curves must be represented at the voltage indicated on the coordination
sheet;
protection devices working at different voltages must be designed taking into account the
ratio between voltages;
the coordination curves must extend in abscissa up to the maximum fault overcurrent in the
point where they are connected;
when showing the time-current curves for the protection devices at different voltage l evels
(upstream or downstream of a transformer) in a coordination diagram, one must take into
account how the modules and se uences of the currents change in relation to the
transformer connection unit;
when a protection device has several functions (for instance, overload and short-circuit
protection), the time-current curves of its functions should be truncated at the crossover
point for easier understanding of the diagram;
when reading coordination diagrams, one must pay close attention to the actual fault
elimination time for each curve shown. ote that:
- for direct protection devices, the curve time corresponds to the total fault clearing time;
- for indirect protection devices, the time shown represents the moment when the
protection device sends an opening command to the circuit-breaker.
the coordination diagram for the protection devices must also show the time-current curves
of the undervoltage relays involved in the selectivity 15
SYSTEM DATA NEEDED TO STUDY
PROTECTION COORDINATION
z I DI ;
z T- I IT T TI ( and I );
z T T T DF T T ( and I );
z I IFI TI ;
z T TI I ;
z I T TT F IFI TI ;
z T TI IFI TI ( F T DT ).
16
TCC DRAWINGS
17
9
ProTECTIVE RELAY TEST
(START-UP TEST)
1
TEST ON PROTECTIVE SYSTEM
IT T D :
T T T :
T T T TI F T FT ID F
D I T I T :
T I T D I T IF FT T
memo
The system of protection they are not only the relays, but:
- Instrument transformers;
- wiring;
- rotective relay;
- Tipping circuits;
- larm circuits;
- auxiliary supply;
- onitoring system;
- system of automation 2
verificATIONS AT THE PLANT
STARTUP
hen a plant is put in service for the first time, it is
necessary to do:
z I TI FT T F T TI
z FT I T FI TI
z T T D T( IT )
z D T T FT
z I T T FT
z IT T I I I FT
z T FT T I I D I IT
3
Operations of periodic
verification (maintenance)
hen in a plant it effects the ordinary or extraordinary
maintenance, it is necessary to do:
I I TI
I T T FT T
T T FI TI
D T T FT
T FT T I I D I IT
4
Tests on protection
system
zPRIMARY TESTS (PRIMARY INJECTION):
T T T T. T FI T
I T TI D TI T TT I IT
F T DIFI D
5
FREQUENCY IN THE CONTROLS
OF THE PROTECTION SYSTEM
THE FREQUENCY WITH WHICH IT EFFECTS THE
MAINTENANCE OF THE PROTECTIONS, DEPENDS
FROM:
CONDITIONS OF INSTALLATION;
AVAILABILITY OF PERSONNEL ET RESOURCES;
AVAILABILITY OF PLANT SHUTDOWN;
RISK ARRIVING FROM A FAILURE OF THE SYSTEM OF
PROTECTION;
AVAILABILITY OF TEST RELAY APPARATUSES;
RELAY TECHNOLOGY:
- ELECTROMECHANICAL RELAY EVERY 6 MONTHS;
- ELECTRONIC RELAY EVERY 1 YEAR;
- MICROPROCESOR RELAY EVERY 5 YEARS (GIVES VARYING I
OPERATION OF THE CONSTRUCTIVE CHARACTERISTICS).
6
general notes related to the
tests on the protections
T T F T IT D
T I I FI
- D FT TF I T D
-F TI D TI DI
- T T TF I TT D T
T
IF T TD 'T F I T T, T IF T
I IT I T D FT T IT T IT I
T TI
T I T I , IF I IT D, F F
D TT I T T I I IT F
7
10
EXAMPLE OF
SELECTIVITY
1
PROTECTION ONE LINE DIAGRAM
2
MOTOR PROTECTION: SETTING TABLE
3
MOTOR PROTECTION: SELECTIVITY CURVES
4
TRANSFORMER PROTECTION: SETTING TABLE
5
6
CAPACITOR PROTECTION: SELECTIVITY CURVES
8
TAKREER RELAY SELECTIVITY STUDY
9
SUBSTATION 1400 132/33 Kv
SELECTIVITY VERIFICATION: SETTING TABLE
10
SUBSTATION 1400 132/33 Kv:
SELECTIVITY VERIFICATION: SELECTIVITY CURVES
11
SUBSTATION 1400 33/11 Kv
SELECTIVITY VERIFICATION: SETTING TABLE
12
SUBSTATION 1400 33/11 Kv
SELECTIVITY VERIFICATION: SELECTIVITY CURVES
13
SUBSTATION 1400 33/0.415 Kv
SELECTIVITY VERIFICATION: SETTING TABLE
14
SUBSTATION 1400 33/0.415 Kv
SELECTIVITY VERIFICATION: SELECTIVITY CURVES
15
SUBSTATION 402 3.3/0.415 KV
SELECTIVITY VERIFICATION: SETTING TABLE
16
17