SUMMARY - CALCULATION OF STAIRCASE PRESSURISATION FANS - MOHANADI

AS PER UAE FIRE AND SAFETY


TENDER SPECIFIED
CODE OF PRACTICE

AIR FLOW
SR NO REF DESCRIPTION SERVING AREA AIR FLOW (CFM) ESP (Pa) ESP (Pa)
(CFM)

VELOCITY OF AIR THROUGH ALL VELOCITY OF AIR THROUGH ALL


OPEN DOORS - NOT SPECIFIED OPEN DOORS - 1.00 m/s

NOT
1 PRF-01 STAIRCASE PRESSURISATION FAN STAIRCASE-01 17250 20969 512
SPECIFIED

NOT
2 PRF-03 STAIRCASE PRESSURISATION FAN STAIRCASE-02 17250 21113 508
SPECIFIED
REPLY TO CONSULTANT COMMENTS
PROJECT NAME : COMMERCIAL BUILDING FOR HEIRS OF RASHED SAEED ALI AL MOHANADI
CALCULATION OF STAIRCASE PRESSURISATION FANS
TECHNICAL
EQUIPMENT / COMMENT
SUBMITTAL STATUS ADCE'S COMMENTS REPLY TO ADCE'S COMMENTS
LOCATION NO.
REV NO.

The calculation through open door shall consider the UAE


3 C 1 Complied
STAIRCASE code requirements 3 doors opened with velocity 1 m/s.
PRESSURISATION
FANS We belive that the basis of selecting the fan based on the
Fan selection is based on the
CALCULATIONS air flow through open door only is not right and the Fan
2 summation of air flow through
shall be selected on the summation of air flow through
opened and closed doors only.
opened and closed doors.
REPLY TO CONSULTANT COMMENTS
PROJECT NAME : COMMERCIAL BUILDING FOR HEIRS OF RASHED SAEED ALI AL MOHANADI
CALCULATION OF STAIRCASE PRESSURISATION FANS
EQUIPMENT / TECHNICAL COMMENT REPLY TO CONSULTANTS
STATUS CONSULTANTS COMMENTS
LOCATION SUBMITTAL REV NO. NO. COMMENTS

STAIRCASE
PRESSURISATION 0 C 1 Staircase area to be as per drawing Complied. Area calculation included
FANS CALCULATION

2 Velocity of air to be 1 m/s Complied


REPLY TO CONSULTANT COMMENTS
PROJECT NAME : COMMERCIAL BUILDING FOR HEIRS OF RASHED SAEED ALI AL MOHANADI
CALCULATION OF STAIRCASE PRESSURISATION FANS
TECHNICAL
EQUIPMENT / COMMENT
SUBMITTAL STATUS ADCE'S COMMENTS REPLY TO ADCE'S COMMENTS
LOCATION NO.
REV NO.

Refer to marks-ups on the submittal and update the


1 C 1 Updated
numbers where applicable
To avoid confusion, omit stairwall area per floor and
2 Updated
provide only the total wall area used in the calculation
Since the staircase door design, is to open to inside
3 staircase, the leakage area for single leaf door can be Complied
redused to 0.01 m2, refer to BS 5588-4-1998 appendix D
for the values
For leakage area through walls, we don't recommend to
use the figures listed in ASHRAE standards, the
STAIRCASE 4 calculation method should not mix two standards Complied
PRESSURISATION together. All required information can be found in BS
FANS CALCULATION 5588-4-1998 appendix D
FOR STAIRCASE 1
Since the building is fully protected by automatic sprinkler
5 system, the pressure difference can be reduced to 12.5 Used 50 Pa
Pa, however, we recommed the use of 50 Pa as required
by BS 5588
Submit Door opening calculation and ensure that the
6 assumed pressure will not result a door opening force Calculated
higher than 133 N
The air flow used in the ESP calculations (18500 CFM) is
7 not matching the calculation result (22500 CFM). Update Updated
the air flow through ducts, fittings and air terminal and
revise the fan selection accordigly.
STAIRCASE Refer to comments above and mark-ups on the submittal
1 Updated
PRESSURISATION and incorporate for staircase 2 calculations
FANS CALCULATION For staircase 2 flow calculations, leakage area through
FOR STAIRCASE 2 2 Incorporated
windows should be incorporated.
EXTERNAL STATIC PRESSURE CALCULATION FOR PRF-01
INITIAL SIZE FINAL SIZE INITIAL FINAL STRAIGHT S.P LOSS/
VOLUME S.P TO CHANGE
SR NO DUCT WORK REF IN (INCH) IN (INCH) VELOCITY VELOCITY EQUIVALENT 100FT LENGTH QTY
OF AIR IN VELOCITY
PRESSURE PRESSURE LENGTH OF DUCT
W H W H CFM (hv1) (hv2) (iwg) (FT) (iwg)
1 Grille 36 18 36 18 3500 1
2 VCD 36 18 36 18 3500 1
3 Straight 36 18 36 18 3500 1.3 0.108 1
4 Straight 16 30 16 30 3500 12 0.074 1
5 Contraction 20 30 16 30 3500 0.0440 0.0687 0.0252 1
6 Straight 20 30 20 30 4375 12 0.062 1
7 Contraction 36 20 30 20 4375 0.0477 0.0687 0.0214 1
8 Straight 36 20 36 20 5250 12 0.057 1
9 Contraction 40 20 36 20 5250 0.0557 0.0687 0.0133 1
10 Straight 40 20 40 20 6125 12 0.06 1
11 Contraction 44 20 40 20 6125 0.0626 0.0758 0.0134 1
12 Straight 44 20 44 20 7000 12 0.062 1
13 Contraction 50 20 44 20 7000 0.0633 0.0818 0.0188 1
14 Straight 50 20 50 20 7875 12 0.058 1
15 Contraction 54 20 50 20 7875 0.0687 0.0802 0.0117 1
16 Straight 54 20 54 20 8750 12 0.06 1
17 Contraction 60 20 54 20 8750 0.0687 0.0849 0.0164 1
18 Straight 60 20 60 20 9625 13 0.057 1
19 Straight 60 20 60 20 10500 13 0.067 1
20 Straight 60 20 60 20 11375 13 0.079 1
21 Straight 60 20 60 20 12250 13 0.091 1
22 Straight 60 20 60 20 13125 13 0.104 1
23 Straight 60 20 60 20 14000 13 0.117 1
24 Straight 60 20 60 20 14875 13 0.132 1
25 Straight 60 20 60 20 15750 13 0.147 1
26 Straight 60 20 60 20 16625 13 0.163 1
27 Straight 60 20 60 20 17500 13 0.18 1
28 Straight 60 20 60 20 18375 13 0.198 1
29 Straight 60 20 60 20 19250 13 0.217 1
EXTERNAL STATIC PRESSURE CALCULATION FOR PRF-01
INITIAL SIZE FINAL SIZE INITIAL FINAL STRAIGHT S.P LOSS/
VOLUME S.P TO CHANGE
SR NO DUCT WORK REF IN (INCH) IN (INCH) VELOCITY VELOCITY EQUIVALENT 100FT LENGTH QTY
OF AIR IN VELOCITY
PRESSURE PRESSURE LENGTH OF DUCT
W H W H CFM (hv1) (hv2) (iwg) (FT) (iwg)
30 Straight 60 20 60 20 21000 13 0.257 1
31 Straight 60 20 60 20 21000 13 0.257 1
32 Straight 60 20 60 20 21000 7 0.257 1
33 Elbow 60 20 48 38 21000 14 0.257 1
34 NRD 48 38 48 38 21000 1
35 Straight 48 38 48 38 21000 6 0.257 1
36 Contraction 44 44 48 38 21000 0.1521 0.1714 0.0196 1
37 Contraction 48 48 44 44 21000 0.1074 0.1521 0.0456 1
38 MVCD 48 48 48 48 21000 1
39 Louvers 48 48 48 48 21000 1
40 Pressure to be Maintained
TOTAL STATIC PRESSURE =
TOTAL STATIC WITH 10% SAFETY FACTOR =

TOTAL STATIC WITH 10% SAFETY FACTOR =


TOTAL S.P
LOSS
(iwg)
0.043
0.201
0.001
0.009
0.025
0.008
0.021
0.007
0.013
0.007
0.013
0.008
0.019
0.007
0.012
0.007
0.016
0.007
0.009
0.010
0.012
0.014
0.015
0.017
0.019
0.021
0.024
0.026
0.028
TOTAL S.P
LOSS
(iwg)
0.034
0.034
0.017
0.036
0.321
0.015
0.020
0.046
0.201
0.321
0.201
1.867
2.054
in WG

512
Pascals
EXTERNAL STATIC PRESSURE CALCULATION FOR PRF-03
INITIAL SIZE FINAL SIZE INITIAL FINAL STRAIGHT S.P LOSS/
VOLUME S.P TO CHANGE
SR NO DUCT WORK REF IN (INCH) IN (INCH) VELOCITY VELOCITY EQUIVALENT 100FT LENGTH QTY
OF AIR IN VELOCITY
PRESSURE PRESSURE LENGTH OF DUCT
W H W H CFM (hv1) (hv2) (iwg) (FT) (iwg)
1 Grille 42 18 42 18 4375 1
2 VCD 42 18 42 18 4375 1
3 Contraction 42 18 38 16 4375 0.0433 0.0669 0.0241 1
4 Straight 38 16 38 16 4375 15 0.066 1
5 Elbow 38 16 38 16 4375 11 0.066 1
6 Straight 38 16 38 16 4375 2.0 0.066 1
7 Elbow 38 16 38 16 4375 11 0.066 1
8 Straight 38 16 38 16 4375 12 0.066 1
9 Contraction 38 18 38 16 4375 0.0529 0.0669 0.0143 1
10 Straight 38 18 38 18 5250 13 0.067 1
11 Straight 38 18 38 18 6125 12 0.09 1
12 Contraction 38 20 38 18 6125 0.0840 0.1037 0.0201 1
13 Straight 38 20 38 20 7000 12 0.087 1
14 Contraction 38 22 38 20 7000 0.0906 0.1097 0.0194 1
15 Straight 38 22 38 22 7875 12 0.085 1
16 Contraction 38 24 38 22 7875 0.0964 0.1147 0.0187 1
17 Straight 38 24 38 24 8750 12 0.082 1
18 Contraction 38 26 38 24 8750 0.1014 0.1190 0.0180 1
19 Straight 38 26 38 26 9625 13 0.08 1
20 Contraction 38 28 38 26 9625 0.1058 0.1227 0.0172 1
21 Straight 38 28 38 28 10500 13 0.077 1
22 Contraction 38 30 38 28 10500 0.1097 0.1259 0.0166 1
23 Straight 38 30 38 30 11375 13 0.075 1
24 Contraction 38 32 38 30 11375 0.1131 0.1287 0.0159 1
25 Straight 38 32 38 32 12250 13 0.073 1
26 Contraction 38 34 38 32 12250 0.1162 0.1312 0.0153 1
27 Straight 38 34 38 34 13125 13 0.072 1
28 Contraction 38 36 38 34 13125 0.1190 0.1334 0.0147 1
29 Straight 38 36 38 36 14000 13 0.070 1
EXTERNAL STATIC PRESSURE CALCULATION FOR PRF-03
INITIAL SIZE FINAL SIZE INITIAL FINAL STRAIGHT S.P LOSS/
VOLUME S.P TO CHANGE
SR NO DUCT WORK REF IN (INCH) IN (INCH) VELOCITY VELOCITY EQUIVALENT 100FT LENGTH QTY
OF AIR IN VELOCITY
PRESSURE PRESSURE LENGTH OF DUCT
W H W H CFM (hv1) (hv2) (iwg) (FT) (iwg)
30 Contraction 38 38 38 36 14000 0.1215 0.1354 0.0142 1
31 Straight 38 38 38 38 14875 13 0.069 1
32 Contraction 38 40 38 38 14875 0.1238 0.1372 0.0136 1
33 Straight 38 40 38 40 15750 13 0.068 1
34 Contraction 38 42 38 40 15750 0.1259 0.1388 0.0132 1
35 Straight 38 42 38 42 16625 13 0.066 1
36 Contraction 38 44 38 42 16625 0.1278 0.1403 0.0127 1
37 Straight 38 44 38 44 17500 13 0.065 1
38 Contraction 38 46 38 44 17500 0.1296 0.1416 0.0123 1
39 Straight 38 46 38 46 18375 13 0.064 1
40 Contraction 38 48 38 46 18375 0.1312 0.1429 0.0119 1
41 Straight 38 48 38 48 19250 13 0.063 1
42 Straight 38 48 38 48 21000 13 0.075 1
43 Straight 38 48 38 48 21000 13 0.075 1
44 Straight 38 48 38 48 21000 7 0.075 1
45 Elbow 38 48 38 48 21000 20 0.075 1
46 Straight 38 48 38 48 21000 3 0.075 1
47 NRD 38 48 38 48 21000 1
48 Straight 38 48 38 48 21000 2 0.075 1
49 Contraction 44 44 38 48 21000 0.1521 0.1714 0.0196 1
50 Contraction 48 48 44 44 21000 0.1074 0.1521 0.0456 1
51 MVCD 48 48 48 48 21000 1
52 Louvers 48 48 48 48 21000 1
53 Pressure to be Maintained
TOTAL STATIC PRESSURE =
TOTAL STATIC WITH 10% SAFETY FACTOR =
EXTERNAL STATIC PRESSURE CALCULATION FOR PRF-03
INITIAL SIZE FINAL SIZE INITIAL FINAL STRAIGHT S.P LOSS/
VOLUME S.P TO CHANGE
SR NO DUCT WORK REF IN (INCH) IN (INCH) VELOCITY VELOCITY EQUIVALENT 100FT LENGTH QTY
OF AIR IN VELOCITY
PRESSURE PRESSURE LENGTH OF DUCT
W H W H CFM (hv1) (hv2) (iwg) (FT) (iwg)
TOTAL STATIC WITH 10% SAFETY FACTOR =
TOTAL S.P
LOSS
(iwg)
0.052
0.201
0.024
0.010
0.007
0.001
0.007
0.008
0.014
0.009
0.011
0.020
0.011
0.019
0.011
0.019
0.010
0.018
0.010
0.017
0.010
0.017
0.010
0.016
0.010
0.015
0.009
0.015
0.009
TOTAL S.P
LOSS
(iwg)
0.014
0.009
0.014
0.009
0.013
0.009
0.013
0.009
0.012
0.008
0.012
0.008
0.010
0.010
0.005
0.015
0.002
0.301
0.001
0.020
0.046
0.201
0.321
0.201
1.854
2.039
in WG
TOTAL S.P
LOSS
(iwg)
508
Pascals
STAIRWELL PRESSURIZATION CALCULATION FOR STAIRCASE 1 - MO

FAN - PRF-1

I
a)

b)

c)

d)
e)
STAIRWELL PRESSURIZATION CALCULATION FOR STAIRCASE 1 - MO

FAN - PRF-1

II

a)

b)
STAIRWELL PRESSURIZATION CALCULATION FOR STAIRCASE 1 - MO

FAN - PRF-1

c)

d)

e)
f)
STAIRWELL PRESSURIZATION CALCULATION FOR STAIRCASE 1 - MOHANA

FAN - PRF-1

According to UAE FIRE AND SAFETY CODE OF PRACTICE (Sec 23.2.2)


The flow velocity shall be attained when a combination of two doors from any two
successive stories and the main discharge door are fully open. Magnitude of the
velocity averaged over the full area of each door shall not be less than 1.0 m/s

DESCRIPTION
Total no.of floors
Total Stairwell wall area (Refer wall area calculation attached)
Total Exterior Building Wall Area
Total Lift Well Wall Area

TOTAL AIR SUPPLY REQUIREMENT WITH ALL DOORS CLOSED (Qs)


Total Leakage through Closed Door gaps (Q dc)
Leakage area for Single Leaf opening into a pressurised space
Leakage area for all Single Leaf opening into a pressurised space (26 Nos)
Total Leakage through Door Gaps (Qdc) = 0.839 x A x sqrt (delta P)
{= 0.83 x 0.26 x sqrt (50)}
Total leakage Rate via gaps around Windows (Q wi)
Total leakage Area via gaps around Windows (A wi) @ 3.6 x 10-5 m2 per m Length

Total Leakage through Gaps around Windows (Qwi) = 0.839 x A x (delta P) 0.625

{= 0.83 x 0.0 x (50)0.625}


Total leakage rate via Lift Landing Doors (Q ld)
Total leakage rate via other areas containing machanical extraction system (Q t)

Total leakage rate via walls (Qwa)


Exterior Building Wall Area(Leakage area ratio A/A w=0.00021)
STAIRWELL PRESSURIZATION CALCULATION FOR STAIRCASE 1 - MOHANA

FAN - PRF-1
Internal and stair wall Area(Leakage area ratio A/Aw=0.00011)
Lift well wall Area(Leakage area ratio A/Aw=0.00084)
Total leakage Area via walls (Awa)
{= (0.00021x 0) + (0.00011 x 1409) + (0.00084 x 0)}
Total Leakage through Walls (Qwa) = 0.839 x A x sqrt (delta P)
{= 0.83 x 0.155 x sqrt (50)}
TOTAL AIR SUPPLY REQUIREMENT WITH ALL DOORS CLOSED (Qs =Qdc+Qwi+Qld+Qt+Qwa)

Considering 50% Safety for unidentified leakage areas


{ = 2.44 x 1.5}

TOTAL AIR SUPPLY REQUIREMENT WITH DOORS OPEN (Qsdo)

Total air flow needed through open door to prevent smoke infiltration into stairwell
(Qdo)
The total no of doors considered open
(Fire Affected Floor, Above Floor and 2 Doors on Ground Floor)
Velocity of air through open Stairwell door to prevent smoke infiltration into Stairwell

Considering 4 open doors, Door area


{ = 1 x 2.2 x 4 }
Total air flow needed through open door to prevent smoke infiltration into stairwell

{ = 1 x 8.8 }

Total Leakage through Closed Door gaps (Q dc)


Leakage area for Single Leaf opening into a pressurised space
Leakage area for all Single Leaf opening into a pressurised space (22 Nos)
Total Leakage through Closed Door Gaps (Q dc) = 0.839 x A x sqrt (delta P)
{= 0.83 x 0.22 x sqrt (12.5)}
STAIRWELL PRESSURIZATION CALCULATION FOR STAIRCASE 1 - MOHANA

FAN - PRF-1

Total leakage Rate via gaps around Windows (Q wi)


Total leakage Area via gaps around Windows (A wi) @ 3.6 x 10-5 m2 per m Length

Total Leakage through Gaps around Windows (Qwi) = 0.839 x A x (delta P) 0.625

{= 0.83 x 0.0 x (12.5)0.625}


Total leakage rate via Lift Landing Doors (Q ld)
Total leakage rate via other areas containing machanical extraction system (Q t)

Total leakage rate via walls (Qwa)


Exterior Building Wall Area(Leakage area ratio A/A w=0.00021)
Internal and stair wall Area(Leakage area ratio A/Aw=0.00011)
Lift well wall Area(Leakage area ratio A/Aw=0.00084)
Total leakage Area via walls (Awa)
{= (0.00021x 0) + (0.00011 x 1409) + (0.00084 x 0)}
Total Leakage through Walls (Qwa) = 0.839 x A x sqrt (delta P)
{= 0.83 x 0.155 x sqrt (12.5)}

TOTAL AIR SUPPLY REQUIREMENT WITH ALL DOORS OPENED (Qsdo


=Qdo+Qdc+Qwi+Qld+Qt+Qwa)

Since Qsdo is Greater than Qs, Qsdo is selected for Fan Selection

{ = 9.9 x 1000 }
{ = 9900 x 2.118 }

STAIRWELL PRESSURISATION FAN CFM SELECTED


E 1 - MOHANADI

Calculation Unit
25
1408.70 sq m
0.00 sq m
0.00 sq m

0.01 sq m
0.26 sq m

1.53 cu.m/s

0.0000 sq m

0.00 cu.m/s
0 sq m

0 sq m
sq m
0 sq m
E 1 - MOHANADI

1409 sq m
sq m

0.1550 sq m

0.91 cu.m/s

2.44 cu.m/s

3.653 cu.m/s

4 Nos

1.00 m/s

8.80 sq.m

8.80 cu.m/s

0.01 sq m
0.22 sq m

0.65 cu.m/s
E 1 - MOHANADI

0.0000 sq m

0.00 cu.m/s
0 sq m

0 sq m
sq m
0 sq m
1409 sq m
0 sq m

0.1550 sq m

0.45 cu.m/s

9.90 cu.m/s

9.90 cu.m/s
9900 LPS
20969 CFM

20969
STAIRWELL PRESSURIZATION CALCULATION FOR STAIRCASE 2 - M

FAN - PRF-3

I
a)

b)

c)

d)
e)
STAIRWELL PRESSURIZATION CALCULATION FOR STAIRCASE 2 - M

FAN - PRF-3

II

a)

b)
STAIRWELL PRESSURIZATION CALCULATION FOR STAIRCASE 2 - M

FAN - PRF-3

c)

d)

e)
f)
STAIRWELL PRESSURIZATION CALCULATION FOR STAIRCASE 2 - MOHAN

FAN - PRF-3

According to UAE FIRE AND SAFETY CODE OF PRACTICE (Sec 23.2.2)


The flow velocity shall be attained when a combination of two doors from any two
successive stories and the main discharge door are fully open. Magnitude of the
velocity averaged over the full area of each door shall not be less than 1.0 m/s

DESCRIPTION
Total no.of floors
Total Stairwell wall area (Refer wall area calculation attached)
Total Exterior Building Wall Area
Total Lift Well Wall Area
Total Window perimeter

TOTAL AIR SUPPLY REQUIREMENT WITH ALL DOORS CLOSED (Qs)


Total Leakage through Closed Door gaps (Q dc)
Leakage area for Single Leaf opening into a pressurised space
Leakage area for all Single Leaf opening into a pressurised space (26 Nos)
Total Leakage through Door Gaps (Qdc) = 0.839 x A x sqrt (delta P)
{= 0.83 x 0.26 x sqrt (50)}
Total leakage Rate via gaps around Windows (Q wi)
Total leakage Area via gaps around Windows (A wi) @ 3.6 x 10-5 m2 per m Length

Total Leakage through Gaps around Windows (Qwi) = 0.839 x A x (delta P) 0.625

{= 0.83 x 0.0029 x (50)0.625}


Total leakage rate via Lift Landing Doors (Q ld)
Total leakage rate via other areas containing machanical extraction system (Q t)

Total leakage rate via walls (Qwa)


Exterior Building Wall Area(Leakage area ratio A/A w=0.00021)
STAIRWELL PRESSURIZATION CALCULATION FOR STAIRCASE 2 - MOHAN

FAN - PRF-3
Internal and stair wall Area(Leakage area ratio A/Aw=0.00011)
Lift well wall Area(Leakage area ratio A/Aw=0.00084)
Total leakage Area via walls (Awa)
{= (0.00021x 267) + (0.00011 x 1074) + (0.00084 x 0)}
Total Leakage through Walls (Qwa) = 0.839 x A x sqrt (delta P)
{= 0.83 x 0.1742 x sqrt (50)}
TOTAL AIR SUPPLY REQUIREMENT WITH ALL DOORS CLOSED (Qs =Qdc+Qwi+Qld+Qt+Qwa)

Considering 50% Safety for unidentified leakage areas


{ = 2.58 x 1.5}

TOTAL AIR SUPPLY REQUIREMENT WITH DOORS OPEN (Qsdo)

Total air flow needed through open door to prevent smoke infiltration into stairwell
(Qdo)
The total no of doors considered open
(Fire Affected Floor, Above Floor and 2 Doors on Ground Floor)
Velocity of air through open Stairwell door to prevent smoke infiltration into Stairwell

Considering 4 open doors, Door area


{ = 1 x 2.2 x 4 }
Total air flow needed through open door to prevent smoke infiltration into stairwell

{ = 1 x 8.8 }

Total Leakage through Closed Door gaps (Q dc)


Leakage area for Single Leaf opening into a pressurised space
Leakage area for all Single Leaf opening into a pressurised space (22 Nos)
Total Leakage through Closed Door Gaps (Q dc) = 0.839 x A x sqrt (delta P)
{= 0.83 x 0.22 x sqrt (12.5)}
STAIRWELL PRESSURIZATION CALCULATION FOR STAIRCASE 2 - MOHAN

FAN - PRF-3

Total leakage Rate via gaps around Windows (Q wi)


Total leakage Area via gaps around Windows (A wi) @ 3.6 x 10-5 m2 per m Length

Total Leakage through Gaps around Windows (Qwi) = 0.839 x A x (delta P) 0.625

{= 0.83 x 0.0029 x (12.5)0.625}


Total leakage rate via Lift Landing Doors (Q ld)
Total leakage rate via other areas containing machanical extraction system (Q t)

Total leakage rate via walls (Qwa)


Exterior Building Wall Area(Leakage area ratio A/A w=0.00021)
Internal and stair wall Area(Leakage area ratio A/Aw=0.00011)
Lift well wall Area(Leakage area ratio A/Aw=0.00084)
Total leakage Area via walls (Awa)
{= (0.00021x 267) + (0.00011 x 1074) + (0.00084 x 0)}
Total Leakage through Walls (Qwa) = 0.839 x A x sqrt (delta P)
{= 0.83 x 0.1742 x sqrt (12.5)}

TOTAL AIR SUPPLY REQUIREMENT WITH ALL DOORS OPENED (Qsdo


=Qdo+Qdc+Qwi+Qld+Qt+Qwa)

Since Qsdo is Greater than Qs, Qsdo is selected for Fan Selection

{ = 9.97 x 1000 }
{ = 9969 x 2.118 }

STAIRWELL PRESSURISATION FAN CFM SELECTED


2 - MOHANADI

Calculation Unit
25
1074.03 sq m
267.09 sq m
0.00 sq m
80.80 m

0.01 sq m
0.26 sq m

1.53 cu.m/s

0.0029 sq m

0.03 cu.m/s
0 sq m

0 sq m
sq m
267 sq m
2 - MOHANADI

1074 sq m
0 sq m

0.1742 sq m

1.02 cu.m/s

2.58 cu.m/s

3.865 cu.m/s

4 Nos

1.00 m/s

8.80 sq.m

8.80 cu.m/s

0.01 sq m
0.22 sq m

0.65 cu.m/s
2 - MOHANADI

0.0029 sq m

0.01 cu.m/s
0 sq m

0 sq m
sq m
267 sq m
1074 sq m
0 sq m

0.1742 sq m

0.51 cu.m/s

9.97 cu.m/s

9.97 cu.m/s
9969 LPS
21113 CFM

21113
STAIRCASE INNER WALL AREA
STAIRCASE-1 STAIRCASE-2

SR NO FLOOR STAIRWALL STAIRWALL EXTERIOR BUILDING WALL

LENGTH WIDTH HEIGHT AREA LENGTH WIDTH HEIGHT AREA LENGTH HEIGHT

1 BASEMENT-04 ( A ) 5100 2400 3300 49.50 4300 2900 3300 37.95 2900 3300

2 BASEMENT-03 ( B ) 5100 2400 3300 49.50 4300 2900 3300 37.95 2900 3300

3 BASEMENT-02 ( C) 5100 2400 3300 49.50 4300 2900 3300 37.95 2900 3300

4 BASEMENT-01 ( D 5100 2400 5400 81.00 4300 2900 5400 62.10 2900 5400

5 GROUND (E) 5100 2400 4000 60.00 4300 2900 4000 46.00 2900 4000

6 MEZZANINE ( F ) 5100 2400 4800 72.00 5850 2900 4800 70.08 2900 4800

7 TYPICAL - 18 NOS ( G ) 5300 2400 3600 55.44 4300 2900 3600 41.40 2900 3600

8 ROOF (H) 5300 2400 3200 49.28 4300 2900 3200 36.80 2900 3200

WALL AREA (SQMT) = (A+B+C+D+E+F+(GX18)+H) 1408.70 1074.03


RCASE-2

R BUILDING WALL WINDOW

AREA LENGTH HEIGHT PERIMETER

9.57 0.00

9.57 0.00

9.57 0.00

15.66 0.00

11.60 800 1600 4.80

13.92 800 1200 4.00

10.44 800 1200 4.00

9.28 0.00

267.09 80.8
STAIRWELL PRESSURISATION CALCULATION - DOOR OPENING
FORCE (MOHANADI)
As per BS 5588-4:1998: The maximum pressure differential across a door opening into a pressurised
space is determined using the flooowing equation:

2(Fo - Fdc) x (W-D)


P =
AxW
Where
P is the pressure difference across the door (in Pa)
Fo is the force needed to open the door against the differential pressure

Fdc is the force required to open the door without a pressure differential applied across
the door. E.g. The door closer mechanism etc (in N)
W is the width of the door (in M)
A is the area of cross section of the door (in m2)
d is the distance from the door knob to the knob side of the door (in m)

If at design stage, the force required to overcome the door closer is unknown, a maximum pressure
differential of 60 Pa may be utilised for design purpose.

I STAIRCASE -01

P - 60 Pa
Fdc - Unknown, Hence P = 60 Pa
W - 1m
A - 1 x 2.2 = 2.2 m2
d - 0.1 m

Fo = (P x A x W)
2 x (W-d)

(60 x 2.2 x 1)
=
2 x (1 - 0.1)
73.33333 N

The permissible limit to door opening force as per BS 5588-4:1998 is 100N


Since the calculated value of Fo = 73.33 N is less than the permissible limit Relief Vents are not required
for this system

II STAIRCASE -02

P - 60 Pa
Fdc - Unknown, Hence P = 60 Pa
W - 1m
A - 1 x 2.2 = 2.2 m2
d - 0.1 m

Fo = (P x A x W)
2 x (W-d)

(60 x 2.2 x 1)
=
2 x (1 - 0.1)
73.33333 N

The permissible limit to door opening force as per BS 5588-4:1998 is 100N


Since the calculated value of Fo = 73.33 N is less than the permissible limit Relief Vents are not required
for this system