Functions and Compact NSX communication

characteristics RSU and RCU utilities

Two utilities, RSU and RCU, are available to RSU (Remote Setting Utility)
assist in starting up a communicating This utility is used to set the protection functions and alarms for each Masterpact and
installation. Compact NSX device.
After connection to the network and entry of the circuit-breaker Modbus address, the
They can be downloaded from the software automatically detects the type of trip unit installed.
Schneider Electric internet site and include There are two possible operating modes.
a "Live update" function that enables
immediate updating. Off-line with the software disconnected from the
communication network
For each selected circuit breaker, the user can do the following.
Determine the protection settings
The settings are carried out on a screen that shows the front of the trip unit. The
Micrologic setting dials, keypad and screen are simulated for easy use of all
DB112216

Micrologic setting functions.


Save and duplicate the protection settings
Each configuration created can be saved for subsequent device programming. It can
also be duplicated and used as the basis for programming another circuit breaker.

On-line with the software connected to the network


Similarly, for each selected circuit breaker, the user can do the following.
Display the current settings
The software displays the trip unit and provides access to all settings.
View the corresponding protection curves
A graphic curve module in the software displays the protection curve corresponding
to the settings. It is possible to lay a second curve over the first for discrimination
studies.
DB112217

Modify settings in a secure manner


b There are different levels of security:
v password: by default, it is the same for all devices, but can be differentiated for
each device
v locking of the Modbus interface module which must be unlocked before the
corresponding device can be set remotely
v maximum settings limited by the positions of the two dials on the trip unit.
These dials, set by the user, determine the maximum settings that can be made via
the communication system.
b Settings are modified by:
RSU: Micrologic Remote Setting Utility. v either direct, on-line setting of the protection settings on the screen
v or by loading the settings prepared in off-line mode. This is possible only if the
positions of the dials allow the new settings.
All manual settings made subsequently on the device have priority.
Program alarms
b Up to 12 alarms can be linked to measurements or events.
b two alarms are predefined and activated automatically:
v Micrologic 5: overload (Ir)
v Micrologic 6: overload (Ir) and ground fault (Ig)
b thresholds, priorities and time delays can be set for 10 other alarms. They may be
selected from a list of 91 alarms
Set the outputs of the SDx relays
This is required when the user wants to change the standard configuration and
assign different signals to the 2 outputs of the SDx relay.

RCU (Remote Control Utility)


DB112215

The RCU utility can be used to test communication for all the devices connected to
the Modbus network. It is designed for use with Compact NSX, Masterpact,
Advantys OTB and Power Meter devices. It offers a number of functions.
Mini supervisor
b Display of I, U, f, P, E and THD measurements for each device, via navigation
b Display of ON/OFF status
Open and close commands for each device
A common or individual password must first be entered.

RCU: Remote Control Utility for communication tests. When all functions have been tested, this utility is replaced by the supervision
software selected for the installation.