You are on page 1of 2

TOMA

FACTOR DE POTENCIA
LÁMPARAS CORRIENTE TOMAS ESPECIALES POTENCIA POR FASE

CALIBRE CONDUCTOR AWG


POTENCIA TOTAL
S

CALCULO CORRIENTE
1000 W GFCI

CORRIENTE
Refri, Lava Y
CIRCUITO

TENSION
DUCHAS
Plancha

HORNO

ESTUFA
100 W
150 W

200 w

BREAKER
60 W

THHN

FASE 1 A

FASE 2 B

FASE 3 C
1500 W

4500 W

8000 W
4000 w
PUNTOS

1,3,5 1 1 8000 208 22.22 10 2666.66667 2666.667 2666.667 27.77859


2.4 1 1 4500 208 15.31 12 2250 2250 19.13628
6.8 1 1 4500 208 15.31 12 2250 2250 19.13628
7.9 1 1 4000 208 13.61 12 2000 2000 17.01003
10.12 1 1 4000 208 13.61 12 2000 2000 17.01003
11 1 0.91 1500 120 12.50 12 1500 15.625
13 3 1 1 1600 120 13.33 12 1600 16.66667
14 4 1 1 1800 120 15.00 12 1800 18.75
15 4 1 1 1800 120 15.00 12 1800 18.75
16 3 1 1 1600 120 13.33 12 1600 16.66667
17 3 1 1 1600 120 13.33 12 1600 16.66667
18 1 1 1500 120 12.50 12 1500 15.625
19 3 1 1 1600 120 13.33 12 1600 16.66667
20 2 1 1 1400 120 11.67 12 1400 14.58333
21 7 1 1400 120 11.67 12 1400 14.58333
22 7 1 1400 120 11.67 12 1400 14.58333
23 1 1 6 1 1060 120 8.83 12 1060 11.04167
24 10 3 4 1 1500 120 12.50 12 1500 15.625
25 0 0 120 0.00 12 0
26 0 0 120 0.00 12 0
11 4 10 36 7 2 2 2 1 44760 14926.7 14917 14917

Diferencia entre la total y


la distribuida en las fases 0 44760
11 4 10 36 7 2

Promedio de fase 14920 -6.66667 3.3333 3.3333 Diferencia con re


promedio por
jorgemedinaarticulacionsena@gmail.com 0.07% 0.00% 0.07% Porcentaje de des
Porcentaje de caída de voltaje
Coseno o factor de potencia

Caída de voltaje fase neutro


Reactancia inductiva Ω/Km

Caida de voltaje fase fase


Longitud en Kilómetros

CUMPLIMIENTO DE LA
Longitud en metros

Impedancia Ω/ km
Ángulo de desfase

resistencia Ω/Km

Impedancia total
BREAKER

NORMA
Voltios

Voltios
Seno
3X30 30 0.03 1 0 0 3.94 0.164 3.94 0.1182 2.627 4.55 2.2% SI
2X20 24 0.024 1 0 0 6.56 0.177 6.56 0.1574 2.41 4.175 2.0% SI
2X20 40 0.04 1 0 0 6.56 0.177 6.56 0.2624 4.017 6.958 3.3% SI
2X20 20 0.02 1 0 0 6.56 0.177 6.56 0.1312 1.785 3.092 1.5% SI
2X20 15 0.015 1 0 0 6.56 0.177 6.56 0.0984 1.339 2.319 1.1% SI
1X20 18 0.018 0.91 24.495 0.415 6.56 0.177 6.043 0.1088 1.36 1.36 1.1% SI
1X20 21 0.021 1 0 0 6.56 0.177 6.56 0.1378 1.837 1.837 1.5% SI
1X20 17 0.017 1 0 0 6.56 0.177 6.56 0.1115 1.673 1.673 1.4% SI
1X20 14.5 0.0145 1 0 0 6.56 0.177 6.56 0.0951 1.427 1.427 1.2% SI
1X20 25 0.025 1 0 0 6.56 0.177 6.56 0.164 2.187 2.187 1.8% SI
1X20 30 0.03 1 0 0 6.56 0.177 6.56 0.1968 2.624 2.624 2.2% SI
1X20 28 0.028 1 0 0 6.56 0.177 6.56 0.1837 2.296 2.296 1.9% SI
1X20 26 0.026 1 0 0 6.56 0.177 6.56 0.1706 2.274 2.274 1.9% SI
1X15 27 0.027 1 0 0 6.56 0.177 6.56 0.1771 2.066 2.066 1.7% SI
1X15 31 0.031 1 0 0 6.56 0.177 6.56 0.2034 2.373 2.373 2.0% SI
1X15 34 0.034 1 0 0 6.56 0.177 6.56 0.223 2.602 2.602 2.2% SI
1X15 21 0.021 1 0 0 6.56 0.177 6.56 0.1378 1.217 1.217 1.0% SI
1X20 25 0.025 1 0 0 6.56 0.177 6.56 0.164 2.05 2.05 1.7% SI
1X15 0 0 0 0 0 0 0 0.0% SI
1X20 0 0 0 0 0 0 0 0.0% SI

Diferencia con respecto al


promedio por fase
Porcentaje de desequilibrio