You are on page 1of 3

1

Phasor Measurements Units for Wide Area


Measurements in Smart Grids – A Review
Jayanth Bhargav

Abstract: A power grid must ensure reliability and safety, which necessitates continuous monitoring and control. Due to
slew in time caused by state estimators, the concept of estimation is now being replaced by direct measurements. Phasor
measurement units (PMU’s) are electronic devices that directly measure the voltage magnitudes and phase angles when
connected to a node or bus of a power system. The analysis of the PMU data will directly give the state and information
about the operational stability of the dynamic power system.
Index Terms— Phasor, SCADA, Frequency Deviation, Total Vector Error, Data Concentrators,

II. SYSTEM OPERATIONAL PARADIGM


I. INTRODUCTION1 The requirements of a real time monitoring and control
system for the grid requires the following:
T HE power industry is now making a transition from the 1. Sense the electrical parameters that decide the
stability of the system at required nodes or buses of
traditional grids and control methodologies to more efficient
and reliable strategies and technologies for faster and effective the power system
control of dynamic operation of power systems. The need 2. Communicate the measurements to a single point to
for more electric power, integration, efficient operation and facilitate complete data acquisition for analysis
management of renewable energy systems and optimal usage 3. Compute on the data to analyze the operation of the
strategies for ageing assets is required. The first step towards system
faster decision and control is being implemented by replacing 4. Visualize and simulate the power flow in the system
state estimation by direct measurements. The phasor for the obtained computational results
measurement units (PMU’s) or Synchrophasors are devices 5. Control the system to stabilize it and make it operate
that measure and transmit the measurements remotely. They
in the defined range
measure voltage magnitudes and phase angles when connected
to a node or bus of a power system. This facilitates wide area
III. COMPARISON OF SCADA AND PMU
measurements and data acquisition at a much faster rate as
compared to traditional state estimation techniques. The Supervisory Control and Data Acquisition (SCADA) is a
advantage of PMU’s is that there is very less tine slew except system, which is being used currently in control of power
for the latency in communication. The figure below shows system. It contains the indications of the equipment’s and
the block level conceptualization of a Phasor Measurement voltage and load data of the system. However, it has many
shortcomings as compared to PMU’s. The following table
Unit. compares the various aspects of PMU’s and SCADA
systems.

Table 1: Comparison of SCADA and PMU attributes

Attribute SCADA PMU


Resolution 1 Sample per 2-4 10-60 samples/s,
min, steady state dynamic
observability observability
Measurement Voltage Voltage
Figure 1: Block Diagram of PMU Magnitude Magnitude and
Phase
Data No Time Stamped
Synchronization and synchronized The decentralization of data access makes it easier to
Area of Control Local Monitoring Wide Area observe the system operation at every level and take
and Control Measurements, appropriate control actions at local levels to avoid the faults
Monitoring and to propagate to other parts of the systems. The internal
Control communication between PDC’s at different levels also
ensures that local control is more effective and islanding of
power systems for safety can be made possible. The time
frames at which the different levels of PDC’s operate is as
IV. PMU INTEGRATION
indicated in Fig.3.
The PMU’s are integrated into the system through
measuring instruments like Current Transformers and The PDC aligns all the information by time from multiple
Potential Transformers. Below is a figure that describes measuring units and transmits the aggregated time
how PMU’s are connected in the grid. synchronized data set as a single data stream. It archives
data and process the information and also exchanges
records with PDCs at other locations of the grid.
Communication systems installed with the PMU’s link
multiple PMUs to a PDC (or PDCs to other PDCs) for real
time data transfer for the purpose of local data analysis and
master data analysis. A secure VPN connection from a
communications center is ensured for data security and
protecting the system from any cyber threats.

The captured phasors are to be time-tagged based on the


time of the UTC time reference. The Time Stamp is an 8-
byte message consisting a 4 byte “Second Of Century
– SOC”, a 3-byte Fraction of Second and a 1-byte Time
Quality indicator. The SOC time-tag counts the number of
seconds that have occurred since inception of PMU, With
Figure 2: PMU connected to grid 3-bytes for the Fraction of Second, one second can be
broken down into 16,777,216 counts or about 59.6 ns/count
V. MEASUREMENTS AND DATA CONCENTRATION and the Time Quality byte contains information about the
status and relative accuracy of the source clock
The data collected by PMU’s are communicated to Phasor
Data Concentrators either by wired or wireless
communication systems. The data acquisition and
transmission occur at various levels. Local data, regional
data and wide area measurement data are available at
different levels of the Phasor Data Concentrators (PDC’s).
The PDC’s communicate with individual PMU’s, with
other PDC’s and also with the Master Data Concentrator.
The figure below describes the topology of PDC’s.

Figure 4: Time-synchronized Measurement of Phasors

Figure 3: Phasor Data Concentrator Network Topology


3

VI. PERFORMANCE CRITERIA functionalities. Phasor measurement data with GPS signal
Accuracy for the Synchrophasor is measured by a value can provide synchronized measurements that will give a
termed the “Total Vector Error” or TVE. TVE is defined as real-time tracking of power flow in the system. It is very
the square root of the difference squared between the real beneficial for studying fault propagation and time delays
and imaginary parts of the theoretical actual phasor and the associated with the faults in various parts of the system.
estimated phasor to the ratio of magnitude of the theoretical
phasor and presented as a percentage. PMU that must Measurements of the phases directly facilitate computation
maintain less than a 1% TVE under conditions of ±5 Hz of of the power transfer between buses directly. They have
off-nominal frequency, 10% THD, and 10% out-of-band very high sampling rate (approximately 30 samples per
influence signal distortion. second) and provide the grid operators an extended
visibility beyond their own operating region. This ensures
the grid stability and reliability. Disturbance monitoring
will be possible on real-time basis from transient and steady
state responses.

VIII. CHALLENGES
While PMU’s help in faster data acquisition and wide area
operation and control of power grids, implementation of
PMU’s to make the grids more sensitive to dynamics has its
own challenges. Visualization of PMU data from a large
number of PDC’s becomes difficult as the amount of
measurements increase. Managing large amounts of data
requires memory and robust computation systems. The
Figure 5: PMU Accuracy Estimation Communication of PMU data on real time is expensive due
to complexities involved in communication network to
VII. DATA ANALYTICS ensure data security. Optimal Placing of PMU’s is
necessary to ensure minimum investment and maximum
The measurements obtained from PMU’s are used to
outcome of PMU based Grid control. Transition from
analyze the system behavior patterns and monitor the presently available technology to PMU’s calls for high
system on real-time basis. The following information of the initial investment. The PDC’s are prone to Cyber Attacks
power system are made available by PMU’s: and cost of securing the PDC data increases the cost of the
1. Positive sequence voltages and currents overall system.
2. Phase voltages and currents
3. Local frequency REFERENCES
4. Local rate of change of frequency [1] AG. Phadke "Synchronized Phasor measurements" <em>IEEE
5. Circuit breaker and switch status Computer Applications in Power</em> Apr. 1993.
The PMU’s continuously compare the phase angles [2] S.M. Mazhari H. Monsef H. Lesani A. Fereidunian "A multi-
objective PMU placement method considering measurement
between two nodes of the system. If the phase difference redundancy and observability value under contingencies" <em>IEEE
between two nodes of the system is found to be changing Trans. Power Syst.</em> vol. 28 pp. 2136-2146 2013.
with time, then it physically implies that the frequency of [3] F. J. Martin F. Garcia-Lagos G. Joya F. Sandoval "Genetic
algorithms for optimal placement of phasor measurement units in
AC is varying. This information will be indicated in the electrical networks" <em>IEE Electronic Letters</em> vol. 39 june
PDC units immediately so that load shedding can be done. 2003.
[4] D. J. Gaushell H. T. Darlington "Supervisory control and data
The data available at the Phasor Data Concentrators can be acquisition" <em>Proc. IEEE</em> vol. 75 no. 12 pp. 1645-1658
1987.
used for analytics and system behavioral pattern studies. [5] L. Wu L. Xia M. Zhao J. Sha "Research on Data Compatibility of
The availability of large amounts of data with time PMU/SCADA Mixed Measurement State Estimation" in
stamping will be an added advantage for novel controller Communications and Information Processing. Communications in
Computer and Information Science Berlin Heidelberg:Springer vol.
designs. Artificial Neural Networks (ANN’s) can be built 288 2012.
which can be trained with the data. The ANN’s will be able [6] M Zhou VA Centeno AG Phadke Y Hu D Novosel HA Volskis "A
to predict, control and analyze the dynamic operation and preprocessing method for effective PMU placement studies"
<em>Third international conference on electric utility deregulation
faults of the power system precisely. and restructuring and power technologies 2008 (DRPT2008)</em>
pp. 2862-7 2008.
The global behavior of the grid may be understood and [7] 11. J Huang N E. Wi "Fault-tolerant placement of phasor
measurement units based on control reconfigurability" <em>Control
analyzed from local measurements of the power system. Eng Pract</em> vol. 21 pp. 1-11 2013.
Phasor measurement data obtained from PDC’s can be used [8] M. Nazari-Heris B. Mohammadi-Ivatloo <em>Application of
to supplement and enhance the existing control algorithms heuristic algorithms to optimal PMU placement in electric power
systems: an updated review Renew Sustain Energy Rev</em> vol.
and strategies in the control centers and provide new 50 pp. 214-228 2015.

You might also like