Professional Documents
Culture Documents
Research Article
China
E-mail: gao.sp2003@163.com
Abstract: Traditional high-voltage DC (HVDC) current differential protection has problems on identifying fault current and has
long delay. In this study, a novel current differential protection principle for HVDC transmission lines is proposed. By the
adoption of distributed parameter model, differential current criterion is formed at a selected point on the transmission line.
When fault occurs on DC line, setting point differential current reaches a high value. When no fault occurs or fault occurs outside
the DC line, setting point differential current reaches a small value. Comparing with the traditional current differential protection,
the proposed principle eliminates the impact of distributed capacitive current and has no requirement of delay. Comparing with
travelling wave protection, fault identification can be performed during both transient and steady states, and the proposed
method has reasonable sampling frequency requirements and has high reliability. Simulation analysis shows that the proposed
principle identifies faults reliably and rapidly. The proposed principle is theoretically novel and practically applicable.
iMP(lset, t) + iNP(l − lset, t) > I set (8) iM(lset, t) + iN (l − lset, t) > I set.2
(12)
T set > 250 ms
where pole index P is p or n. lset is the distance between setting
point and M end; l is the total length of protected line; Iset is setting
Bergeron model describes travelling wave propagation procedure
threshold. through the line. As DC current is stabilised, wave procedure is
vanished and model error can be neglected. During fault steady
Either mode criterion or polar criterion exceeds threshold, line state, short circuit current is generally stabilised under In, while Iset.
internal fault is identified. Otherwise it is non-fault or external fault
state. Fault pole is automatically selected by each polar criterion. If 2 can be calculated by
mode criterion is adopted, use voltage level to identify fault pole.
I set.2 ≤ krelknpI n (13)
3.3 Criterion settings
where krel is reliability coefficient and krel = 1.1–1.2; knp is
According to fault characteristic analysis in Section 3, as measurement error coefficient of HVDC diverters, which is <0.002
differential currents form fault transient and steady states are when line current is under 1.3In [1]. Iset.2 can be selected as
diverse, setting threshold should be adjusted to both states. follows:
1 Z c j + r j x/4 x x r jx
i jM(x, t) = uM j t + − iM j t + Z +
2Z c j Zc j vj vj cj 4
1 Z c j + r j x/4 x x r jx
− uM j t − + iM j t − Z − (5)
2Z c j Zc j vj vj cj 4
1 r jx r jx
− ⋅ u (t) − i (t)
2Z c j 2Z c j M j 4 Mj
1 Z c j + r j x/4 x x r jx
i jN (x, t) = uN j t + − iN j t + Zc j +
2Z c j Zc j vj vj 4
1 Z c j + r j x/4 x x r jx
− uN j t − + iN j t − Zc j − (6)
2Z c j Zc j vj vj 4
1 r jx r jx
− ⋅ u (t) − i (t)
2Z c j 2Z c j N j 4 Nj
1288 IET Gener. Transm. Distrib., 2017, Vol. 11 Iss. 5, pp. 1286-1292
© The Institution of Engineering and Technology 2017
I set.2 = 0.003I n (14) be selected at line end, and only one side fault current needs to be
calculated. For decreasing data window and increase rapidity,
As fault differential current is stabilised to 0.1In–0.15In, it is setting point should be selected at midpoint. In this paper, midpoint
unnecessary to select a very low value for Iset.2. The selection of is selected.
Iset.2 would only be <0.1In to prevent tripping rejection and provide
enough sensitivity, while still need to be high enough to prevent 5 Simulation analysis
false trip. For ensuing reliability, selection of Iset.2 is recommended PSCAD/EMTDC is used for power system simulation and
as follows: MATLAB is used for algorithm simulation.
In PSCAD, a±500 kV bipolar HVDC transmission system
I set.2 = max {(1.5 − 2)I cd0, 0.05I n} (15) model shown in Fig. 1 was built, where nominal DC current is 2
kA and transmission line length is 1000 km. Energy of HVDC
where Icd0 is the differential current of non-fault steady state. Icd0 is lines is distributed majorly on 0 Hz, while still some distribution on
related to the real-time imbalanced current caused by measurement other frequencies. Line parameters under 0 Hz is used for Bergeron
error. model calculation. In order to verify that energy distribution on
other frequencies will not affect tripping results, frequency-
dependent parameters line model is used, and line tower structure
4 Discussion on related issues is presented in [10].
4.1 Sampling frequency selection Data generation frequency in PSCAD is 10 kHz, and faults
occur at 0.5 s with duration of 0.5 s. Differential current of
Microcomputer protection devices adopted in modern power traditional differential protection is given for comparison.
systems compute with discrete data. Therefore, (5) and (6) can be
written in discrete form as follows: (see (16) and (17)) (see (17))
5.1 Validation verifications
where Ts is sampling interval and Ts = 1/fs, fs is sampling
frequency. nx is obtained as follows: To verify validation and accuracy of Bergeron model for HVDC
line differential protection, the most critical external fault, i.e.
x metallic ground fault occur outside rectifier DC relay device, is
nx = (18) selected. Calculations cover the whole line, where IMjN is the
v jT s
calculation results at N side using M side voltage and current, INjM
where square brackets represent rounding function. is the calculation results at M side using N side voltage and current,
The meaning of nx is that: under discrete computation with a mode index j = 1 or 0. Transient calculation results are used for
verification, and simulations are shown below.
fixed sampling frequency fs, only several points of current
Simulation results in Fig. 4 indicate that: (i) 1-model calculation
distribution along the line can be calculated. fs related to the results are accurate; (ii) transient 0-mode calculation are not very
density of calculable points. As shown in (18), nx is actually the accurate, this is because 0-mode parameters are unstable and will
nearest point of distance x, which means if fs is selected higher, the normally have huge error. For mode criterion adopted, 1-mode
position of nx will be closer to the actual position of distance x and criterion and voltage level are used to identify fault pole and is not
ijM and ijN will be more accurate, thus the imbalanced current affected by 0-mode data. For polar criterion adopted, there will be
within setting point differential current will be less significant. inaccuracy occurring at reconverted polar currents at setting point.
To ensure dependability, imbalanced current should be limited With Bergeron model integrated travelling wave propagation
up to 50 A, while sampling frequency should be no <6 kHz procedure in time domain, currents at setting point obey KCL at all
according to simulations. Data interpolation should be used to time, and so does their integrations. A mean filter is valid for
guarantee differential current accuracy while lower sampling decrease 0-mode calculation error. In this paper, mean filter with
frequency is selected. For HVDC transmission systems, sampling 10 ms window is adopted for fault simulation below.
devices of 10 kHz are adopted for travelling wave protection. The
proposed method can utilise those sampling devices and meet the 5.2 Setting point randomness verifications
dependability requirement.
To verify the randomness of setting point, metallic ground fault
occurring outside the rectifier DC relay device is selected as most
4.2 Setting point selection serious external fault, and DC line ground fault by 500 Ω at 10 km
Theoretically, differential current at any random point on the line from M side is selected as most undistinguishable internal fault. As
can be calculated, the selection of setting point can be random. For setting point varies, maximum transient differential current
decreasing the amount of digital calculations, setting point should distribution along the line is calculated and shown below.
1 Z c j + r j x/4 r jx
i jM[x, t] = uM j[t + nxT s] − iM j[t + nxT s] Z c j +
2Z c j Zc j 4
1 Z c j + r j x/4 r jx
− uM j[t − nxT s] + iM j[t − nxT s] Z c j − (16)
2Z c j Zc j 4
1 r jx r jx
− ⋅ u [t] − i [t]
2Z c j 2Z c j M j 4 Mj
1 Z c j + r j x/4 r jx
i jN [x, t] = uN j[t + nxT s] − iN j[t + nxT s] Z c j +
2Z c j Zc j 4
1 Z c j + r j x/4 r jx
− uN j[t − nxT s] + iN j[t − nxT s] Z c j − (17)
2Z c j Zc j 4
1 r jx r jx
− ⋅ u [t] − i [t]
2Z c j 2Z c j N j 4 Nj
IET Gener. Transm. Distrib., 2017, Vol. 11 Iss. 5, pp. 1286-1292 1289
© The Institution of Engineering and Technology 2017
Fig. 4 Simulation results for Bergeron model valid verification
6 Conclusions
In this paper, through control characteristic analysis and fault
characteristic analysis, existing problems of traditional differential
protection are analysed. A novel HVDC differential protection
scheme is proposed. The new approach uses distributed parameter
line model to calculate differential current in time domain.
Combined criterions with a high value short delayed threshold and
a low value long delayed threshold are introduced.
Comparing with travelling wave protection, the proposed
approach is not limited by wave head and can identify internal
faults during both transient and steady states, while also has high
tolerance to high ground resistance. Comparing with traditional
current differential protection, the proposed approach adopted
distributed parameter model and is not affected by distributed
capacitive current. Its reliability is greatly increased.
The proposed approach with combined high-value and low-
Fig. 10 Results of differential current when ground fault by 500 Ω occurs value thresholds ensures both rapidity and sensitivity as well as
beyond the line in inverter side security for the HVDC differential current protection scheme. The
adoption of Bergeron model and combined thresholds is an
high security, while differential current by traditional differential improvement to the theory of HVDC differential current protection
protection exceeds 500 A and possibly leads to false trip. and the proposed approach is applicable in practice.
IET Gener. Transm. Distrib., 2017, Vol. 11 Iss. 5, pp. 1286-1292 1291
© The Institution of Engineering and Technology 2017
[11] Kimbark, E.W.: ‘Direct current transmission’ (Wiley, New York, 1971), vol. [17] Li, B., Zhang, S., Crossley, P.A., et al.: ‘The scheme of single-phase adaptive
1, pp. 274–275 reclosing on EHV/UHV transmission lines’. IET 9th Int. Conf. on
[12] Naidoo, D., Ijumba, N.M.: ‘HVDC line protection for the proposed future Developments in Power System Protection, 2008, Glasgow, UK, March 2008,
HVDC systems’. 2004 Int. Conf. on Power System Technology, November pp. 116–120
2004, pp. 1327–1332 [18] Zhang, J., Yuan, Z.H., Guo, Z.Z.: ‘Study of the entire current differential
[13] Naidoo, D., Ijumba, N.M.: ‘A protection system for long HVDC transmission protection of EHV transmission lines based on electronic transducer’. IEEE
lines’. Inaugural IEEE PES 2005 Conf. and Exposition in Africa, July 2004, Power and Energy Society General Meeting – Conversion and Delivery of
pp. 150–155 Electrical Energy in the 21st Century, 2008, 20–24 July 2008, pp. 1–5
[14] Keswani, R.A.: ‘Identification of Fault in HVDC converters using wavelet [19] Li, B., Chang, W.H., He, J.L., et al.: ‘Special problems in current differential
based multi-resolution analysis’. IEEE First Int. Conf. on Emerging Trends in protection based on Bergeron model’. Power and Energy Engineering Conf.,
Engineering and Technology, 2008, pp. 954–959 2009, APPEEC 2009, Asia-Pacific, 27–31 March 2009, pp. 1–4
[15] Zheng, G., Jiali, H.: ‘New principle of pilot relay protection of transmission
lines’, Autom. Electr. Power Syst., 2004, 28, (11), pp. 1–5
[16] Yuping, Z., Tonghua, W., Yan, D., et al.: ‘Applied criterion of current
differential protection based on Bergeron model’, Autom. Electr. Power Syst.,
2004, 28, (23), pp. 50–55
1292 IET Gener. Transm. Distrib., 2017, Vol. 11 Iss. 5, pp. 1286-1292
© The Institution of Engineering and Technology 2017