Professional Documents
Culture Documents
FPFM 87L‐21‐67N‐1
RELAY SETTINGS RED670
CT & VT DATA:
132KV CT1-1 Ratio = 1200 / 1A
CT Class = PX
CT Knee Point Voltage = 2100 V
CT Magnetizing Current ( mAmp ) = 66.7 mA
CT Resistance (Ohms) = 3 Ω
Maximum Through Fault Current, IK1max = 40000 A
Rated VT Primary Voltage ( PH-PH ) = 132000 V
Rated VT Secondary Voltage ( PH-PH ) = 115 V
Rated VT Primary Voltage ( PH-N ) = VPH-PH / √3 = 76210.2 V
Rated VT Secondary Voltage ( PH-N ) = VPH-PH / √3 = 66.3953 V
Factor for Primary Impedance to Secondary Impedance Conversion, UZ = [ US / UP ] x [ IP / IS ]
UZ = 1.04545
System reactance /Resitance ratio = 50 (As provided in P.R)
This setting shall take into account the fundamental frequency line charging current, and whether a power transformer is included in
the protected zone or not.
The positive sequence line charging current is calculated according to the following equation:
The differential current IdMin is the minimum differential current at which the relay will pickup. Its value must be greater than the
line Charging current.
Differential Current IdMin > Ic = 0.0050 x IB
If the charging current compensation is enabled, the setting of IdMin shall be: IdMin>Ic, and if it is disabled: IdMin>2.5xIc. In many
cases, the charging current will be quite small which will make the lower limit of the setting range i.e. 20% of IBase the practical
limit of sensitivity.
Differential Current IdMin = 0.2 x IB
2.2 EndSection1 set as a multiple of IBase
The default value 1.25 is generally recommended. If the conditions are known more in detail, other values can be chosen in order to
increase or decrease the sensitivity.
End section-1 = 1.25 x IB
2.3 EndSection2 set as a multiple of Ibase
The default value 3.00 is generally recommended. If the conditions are known more in detail, other values can be chosen in order to
increase or decrease the sensitivity.
End section-2 = 3.00 x IB
2.4 SlopeSection2 set as a percentage value: [Operate current/Restrain current]·100%
The default value 40.0 is generally recommended. for Slope Section -2
SlopeSection 2 = 40.00 %
2.5 SlopeSection3 set as a percentage value: [Operate current/Restrain current]·100%
Due to expected CT saturation during high through fault currents, a second slope is employed. This slope is typically set at 80%
SlopeSection 3 = 80.00 %
The set value is the ratio of the second harmonic of the differential current to the fundamental frequency of the differential current.
Transformer inrush currents cause high degrees of second harmonic in the differential current. The default value of 15% serves as a
reliable value to detect power transformer inrush currents as the content at this phenomenon is always higher than 23%.
Also CT saturation causes second harmonics of considerable value on the CT secondary side, which will contribute to the
stabilization of the relay at through fault conditions.
It is recommended to maintain a setting of 15% even no power transformer is included in the protected zone.
= 15.00 %
The set value is the ratio of the fifth harmonic of the differential current to the fundamental frequency of the differential current.
4 IMPEDANCE PROTECTION:
4.1 Distance protection ZM
The setting for distance protection functions are done in primary values. The instrument transformer ratio that has been set for the
analogue input card is used to automatically convert the measured secondary input signals to primary values used in the distance
protection function
b) Zone 2 reach has been proposed as 100% of Main line and 50% shortest line:
Zone 3 reach has been proposed as 120% of Main line and next longest line:
Zone 4 reach has been proposed ad 100% of UG1 with zero time
Limitations for RFPP shall be defined by the load impedance. The maximum load current on the transmission line has been
considered as 125% nominal loading of transmission line to cover emergency loading of the protected line in case of parallel line
tripping. The minimum load impedance presented to the relay may be calculatd as:
=
Minimum load impedance Zload Rated voltage / Maximum load current
MVA Rating of Line (SEC provided data) = 267 MVA
Maximum load Current Iload =
MVA rating of Line/√3 x rated Voltage
Maximum load Current Iload = 1167.82 A
Overloading of OHL Iload1 = 125 % ILoad
Overloading of OHL Iload1 = 1459.78 A
Zload = Vph / √3 x Iload1
Minimum load impedance, = 52.2068 Ω
Load impedance Angle θ (PF Considered as 0.85) acos (PF)
Load impedance Angle θ = 31.79 degree
Load impedance
= 48.5965560777209+19.0769119776451i
RLZ1 = 0.28343 Ω
Set Resistive value should be less than 3 x X1Z1 to avoid the over reaching problem
Rarc = 6.864 Ω
RLZ4 = 0.0049 Ω
≥ 1.3x ( 6.8640+ 0.0049)
= 8.9296 Ω
Set Resistive value should be less than 3 x X1Z4 to avoid the over reaching problem
≥ 1.3 x( Rarc+Rtf+R1Z1)
Rarc
= 6.864 Ω
Rtf
= 5 Ω
RlZ1
= 0.28343 Ω
≥ 1.3 x( 6.864+5+0.2834)
RFPE1 (Resistive reach of zone1 for Ph-E faults) = 15.7917 Ω
≥ 1.3 x( Rarc+Rtf+R1Z2)
Rarc = 6.864 Ω
Rtf = 5 Ω
RlZ2 = 0.47238 Ω
≥ 1.3 x( 6.864+5+0.4724)
RFPE1 (Resistive reach of zone1 for Ph-E faults) = 16.0373 Ω
≤ 11.4185 Ω
Set Resistive value should be less than 4.5 x X1Z2 to avoid the over reaching problem
≥ 1.3 x( Rarc+Rtf+R1Z3)
Rarc = 6.864 Ω
Rtf = 5 Ω
RlZ3 = 0.90696 Ω
≥ 1.3 x( 6.864+5+0.907)
Set Resistive value should be less than 4.5 x X1Z3 to avoid the over reaching problem
≥ 1.3 x( Rarc+Rtf+R1Z4)
Rarc = 6.864 Ω
Rtf = 5 Ω
RlZ4 = 0.0049 Ω
≥ 1.3 x( 6.864+5+0.0049)
For normal overhead lines, the angle for the loop impedance for phase to earth fault defined as:
Φloop = arctan((X1L+XN)/(R1L+RN)
53.0571 degree
The reactive reach in forward direction must as minimum be set to cover the measuring zone used in the Teleprotection schemes,
mostly zone 2. For clearance labels PHS and Zm is introduced to distinguish between setting parameter for PHS and zone
measurement Zm. The minimum recommended reactive reach may be proposed as follows:
1. X1PHS > 1.44 * X1ZM
1. X0PHS > 1.44 * X0ZM
X1ZM= X12( the reactive reach for the Zone Covered by PHS) = 3.14417 Ω
X1PHS > 1.44 * X1ZM = 4.5276 Ω
X0ZM= X02( the reactive reach for the Zone Covered by PHS) = 11.3886 Ω
X0PHS > 1.44 * X0ZM = 16.3995 Ω
The reactive reach in reverse direction is automatically set to the same reach as for forward direction. No additional setting is
required.
RFREZM = RFPE2 = 10 Ω
RFRVPEmin= 1.2 * RFPEZM = 12 Ω
The fault resistance reaches in forward direction RFFwPP, must cover RFPPZm with at least 25% margin. RFPPZm is the setting of
fault resistance for phase-to-phase fault for the longest overreaching zone to be covered by PHS. The minimum recommended reach
can be calculated as:
RFFwPP > 1.25 * RFPPZM
RFPPZM = RFPP2 7 Ω
RFFwPP= 1.25 * RFPPZM 8.75 Ω
Phase-to-phase fault in reverse direction:
Reactive reach
The reactive reach in reverse direction is the same as for forward so no additional setting is
required.
Resistive reach
The resistive reach in reverse direction must be set longer than the longest reverse zones. In blocking schemes it must be set longer
than the overreaching zone at remote end that is used in the ommunication scheme.
RFRvPPmin > 1.25 * RFPEZM
RFPPZM = RFPP2 =7 Ω
RFRvPPmin= 1.25 * RFPPZM = 8.75 Ω
Resistive reach with load encroachment characteristic
The procedure for calculating the settings for the load encroachment consist basically to define the load angle ARGLd, the blinder
RLdFw in forward direction and blinder RLdRv in reversedirection.
Load Encroachment
The maximum load current on the transmission line has been considered as 125% nominal loading of transmission line to cover
emergency loading of the protected line in case of parallel line tripping.
=
Load impedance Zload
48.5965560777209+19.0769119776451i
Rlmin = 48.5966 Ω
RLdfw = 80% OF RLmin = 38.8772 Ω
The resistive boundary RLdRv for load encroachment characteristic in reverse direction can be calculated in the same way as RLdFw.
Directional Earth fault element is intended for the detection of low fault currents, which are encountered during a condition like a
broken conductor fallen on the ground, and the fault current is low enough, not to be detected by the distance elements. For networks
with high earth loop resistance, I0 & V0 polarization is recommended