PV System Load Estimation Worksheet

DC  Watts  Use       Hrs  Use       Days  Watt Hours  Watt Hours 


Individual Loads Qty X AC Volts Volts X Amps = Watts AC DC X /Day X /Wk ÷ 7 Days = AC DC
CFL 15 X 120 X 0.125 = 225.00 0 X 4 X 7 ÷ 7 = 900.00 0.00
E/S Fridge 1 X 120 X 1.058 = 126.96 0 X 9 X 7 ÷ 7 = 1142.64 0.00
Clothes Washer 1 X 120 X 12.09 = 1450.80 0 X 0.5 X 4 ÷ 7 = 414.51 0.00
Gas Dryer 1 X 120 X 2.5 = 300.00 0 X 1 X 4 ÷ 7 = 171.43 0.00
TV 1 X 120 X 1.09 = 130.80 0 X 4 X 7 ÷ 7 = 523.20 0.00
VCR 1 X 120 X 0.33 = 39.60 0 X 2 X 3 ÷ 7 = 33.94 0.00
Laptop Computer 1 X 120 X 0.33 = 39.60 0 X 8 X 5 ÷ 7 = 226.29 0.00
Microwave 1 X 120 X 11.66 = 1399.20 0 X 0.082 X 7 ÷ 7 = 114.73 0.00
Test 1 X 120 X 0 = 0.00 0 X 0 X 0 ÷ 7 = 0.00 0.00
X X = 0.00 0 X X ÷ 7 = 0.00 0.00
X X = 0.00 0 X X ÷ 7 = 0.00 0.00
X X = 0.00 0 X X ÷ 7 = 0.00 0.00
X X = 0.00 0 X X ÷ 7 = 0.00 0.00
X X = 0.00 0 X X ÷ 7 = 0.00 0.00
X X = 0 X X ÷ 7 = 0.00 0.00
X X = 0.00 0 X X ÷ 7 = 0.00 0.00
X X = 0.00 0 X X ÷ 7 = 0.00 0.00
X X = 0.00 0 X X ÷ 7 = 0.00 0.00
X X = 0.00 0 X X ÷ 7 = 0.00 0.00
X X = 0.00 0 X X ÷ 7 = 0.00 0.00
X X = 0.00 0 X X ÷ 7 = 0.00 0.00
X X = 0.00 0 X X ÷ 7 = 0.00 0.00
X X = 0.00 0 X X ÷ 7 = 0.00 0.00
X X = 0.00 0 X X ÷ 7 = 0.00 0.00
X X = 0.00 0 X X ÷ 7 = 0.00 0.00
X X = 0.00 0 X X ÷ 7 = 0.00 0.00
X X = 0.00 0 X X ÷ 7 = 0.00 0.00
X X = 0.00 0 X X ÷ 7 = 0.00 0.00
X X = 0.00 0 X X ÷ 7 = 0.00 0.00
X X = 0.00 0 X X ÷ 7 = 0.00 0.00
AC Total Connected Watts: 3711.96 AC Average Daily Load: 3526.75
 AC kWh / Month: 105.80
DC Total Connected Watts: 0 DC Average Daily Load: 0.00
 DC kWh / Month: 0
PV System Battery Sizing Worksheet
AC Average Daily Load  Inverter  DC Average Daily  DC System  Average Amp 
(wt‐hr/day) ÷ Efficiencey + Load (wt‐hr/day) ÷ Voltage = hours/day

33936.00 ÷ 0.90 + 0.00 ÷ 24 = 1571.11

Average Amp‐hours    Days of  % Discharge Limit  Battery AH  Batteries in 


/day × Autonomy ÷ on Battery ÷ Capacity = Parallel

1571.11 × 3 ÷ 0.50 ÷ 350 = 27

Battery  Batteries in  Total      


DC Voltage System ÷ Voltage = Batteries in Series × Parallel = Batteries

24 ÷ 24 = 1 × 27 = 26.933333

 
PV Panel Array Sizing Worksheet
Average Amp‐Hrs /  Battery  Array Peak 
day ÷ Efficiencey ÷ Peak Sun Hrs/day = Amps

1571.11 ÷ 0.80 ÷ 4.00 = 490.97

Peak Amps /  Module Short 
Array Peak Amps ÷ Module = Modules in   Parallel
Circuit Current

490.97 ÷ 5.00 ÷ 98.2 5.3

Nominal 
Modules in  Total      
DC Voltage System ÷ Module  = Modules in Series × Parallel = Modules
Voltage

24.00 ÷ 24 = 1.00 × 98 = 98.19

Panel Specification Make: Model:

 
PV Controller Sizing Worksheet
Module Short    Circuit  Modules in  Array Short  Controller  Listed Desired 
Current × Parallel × 1.25 = Circuit Amps Array Amps Features

Temp 
5.30 × 98.2 × 1.25 = 650.54 40.0 A Compensation, 
digtal Volt Meter

DC Total Connected  DC System  Maximum DC    Load  Controller 


Watts ÷ Voltage = Amps Load Amps

0.00 ÷ 48 ÷ 0.0

Controller Specification Make: Model:

PV Inverter Sizing Worksheet
Estimated Surge 
AC Total Connected  Watts (In Rush =Min 
DC System Voltage
Watts of 3‐6  times Total 
Connected Watts  )

3711.96 48 11135.88

Inverter Specification Make: Model: