Fault Analysis and Evaluation E_wineve

Module for Power System


1MRB520153-Ben
Monitoring Page 1
Issued: August 2003
Changed since March 2003
Data subject to change without notice

Introduction High-voltage transmission and distribution tion directly after a line trip. Proper actions
networks are the backbone of modern power can immediately be arranged to shorten the
generation and distribution systems. Faults on outage time and restore electricity and full
the transmission system can lead to severe network availability.
economic losses. Rapid information about the
type and the location of the fault can assist In addition, protection engineers are using
the task of repair and maintenance, thereby E_wineve to analyze all generated distur-
minimizing the economic effects of power bance records, making good use of the highly
interruption. flexible evaluation and calculation features.
This leads to a better understanding of com-
The E_wineve fault analysis and evaluation plex effects in the network, weak spots in the
module belongs to the software suite "Power network are detected and settings are accu-
System Monitoring”, abbreviated PSM. rately adjusted or protection schemas are
After a line fault, it supports quickly the oper- improved, which in the long-term results in a
ator in the control centre with the localisation decreasing number of faults. Therefore higher
of the fault. This is the most relevant informa- reliability of the network is achieved.

User benefits The E_wineve fault analysis and evaluation The short report, generated by E_wineve
module reduces down time of the transmis- contains precise fault location and informa-
sion or distribution lines and supports the tion about the fault type. This reduces eco-
quick restoration of power. nomic impact of outages since the repair team
can reach the faulted section of line faster.
E_wineve assists the operator by generating This reduces the time to put the line back into
automatically a “short fault report” in case of service.
a line fault. It can be configured to print these
reports dependent on different configurable Seen in the long-term, E_wineve increases
conditions. Only relevant reports are gener- the reliability of the power network and mini-
ated and irrelevant reports are suppressed. mises the damage resulting from faults in
This supplies the operator with the right transmission and distribution systems and in
information at the right time during demand- power generation systems. This can be
ing situation after a line trips. achieved using the strong and user-friendly
analyzing functions of E_wineve. Calcula-
tions can easily be programmed using the
point and click icons. Related disturbance
ABB Switzerland Ltd Fault Analysis and Evaluation Module E_wineve
Utility Automation Systems
for Power System Monitoring 1MRB520153-Ben
Page 2

User benefits (cont’d) records can be merged and many other func- power system and might optimize the settings
tions can be applied to analyze disturbance of his assets, which results in a more robust
records. Using this information the protection power network.
engineer will uncover secondary effects in the

Application The E_wineve fault analysis and evaluation • COMTRADE IEEE C 37.111 - 1991
system can be used to evaluate disturbances • ABB proprietary formats
recorded in the following devices:
- INDACTIC format
• Dedicated disturbance recorders
- ABB INDACTIC 650 - EVE format
• Integrated disturbance recorders - REVAL format.
- ABB protection devices The E_wineve system can run on Microsoft
• 3rd party dedicated disturbance recorders Windows 2000 or Windows NT computer for
evaluation and analysis of faults in the fol-
• 3rd party integrated disturbance recorders lowing areas:
- protection devices.
• Distribution, transmission and sub-trans-
E_wineve can handle various standard and mission levels
proprietary file formats of the disturbance • Power supply of industrial plants and the
recording, for example: auxiliary supply of power plants
• Power generation systems, generator,
transformer and transmission protection
systems.

Functions E_wineve has a number of functions and fea- - cursor lines that can be positioned to a
tures tailored to the needs and requirements numeric time value
of the user: - zooming in/zooming out the interesting
• Visualization/display part of a display by expanding the ampli-
tude and/or time axis
• Merging of two disturbance record files
- display of individual signals or grouping
• Automatic fault location with automatic of several signals on one time axis, e.g.
printout of the "short fault report" all voltages on the same horizontal axis
• Manual fault location • Selection of the colors for each of the ana-
• Display and printout of the signal vectors log and digital signals from the standard
MS office color palette
• Application-specific mathematical calcu-
lation of the waveforms • User-customized view settings, for exam-
ple amplitude size, axis height, signal col-
• Information regarding pre-fault, fault and ors, time axis zoom, can be stored into 10
post-fault conditions so-called user profile layouts
• Time calculation based on the values of the • Opening the disturbance record file in the
digital signals
- ABB Indactic EVE format
• Selective printing of fault reports
- COMTRADE file format IEEE C37.111-
• Data base and statistical analysis of the 1991
fault location, fault types.
- REVAL format
Visualization/display • Saving the disturbance record file in
• In the file open menu selection of the dis- - the Indactic EVE format
turbance files to be displayed as per spe-
cific period of day, month or year - the COMTRADE file format IEEE
C37.111-1991
• On-screen analysis support by means of:
• Printout of the disturbance record file on
- simultaneous display of several distur- commercially available color printers or
bance record files plotters
ABB Switzerland Ltd Fault Analysis and Evaluation Module for E_wineve
Utility Automation Systems
Power System Monitoring 1MRB520153-Ben
Page 3

• Each individual oscillograph can be copied the documentation of fault records an easy
to another MS Windows program or office task (copy and insert bit maps).
application via the clipboard, thus making

Fig. 1 Visualization / display of a fault record

Merging of two disturbance record files Fault location


The merge function allows the combination The purpose of fault location is to determine
of data for the same fault, which has been fast and automatically the distance of the
recorded by different acquisition units. This fault from the substation and to print the
results in a new data set with selected results in the form of a "short fault report", an
measurements from an extended area that can easy to read one-page report containing all
be used for further analysis by additional facts. The fault location algorithm produces
functions, such as power analysis calculation accurate results even for high-impedance
and fault location. short circuits between lines or to earth. Line
parameters entered by the user are utilized for
• Merging of different recorded fault data
the fault location calculation.
for in-depth analysis
• Automatically triggered fault location with
• Automatic synchronization of both data
sets, i.e. the time axes of both data sets are an accuracy of better than 2% of the dis-
tance to fault
made to correspond exactly within
<0.1 ms with regard to the event e.g. in a • Calculation of the loop impedance of the
1½ breaker scheme faulted line
• Merging based on time or on the basis of a • Correct interpretation of short circuits to
common signal in both files earth, two- or three-phase short circuits,
symmetrical or asymmetrical lines, includ-
• Free selection of signals to be combined
ing consideration of parallel lines
• Storage of the new, combined data set for
further processing.
ABB Switzerland Ltd Fault Analysis and Evaluation Module for E_wineve
Utility Automation Systems
Power System Monitoring 1MRB520153-Ben
Page 4

Functions (cont´d) • Better accuracy of the results by means of - Number of the acquisition device
individual matching of input circuits, con- - Date and time on the disturbance record
sideration of mutual coupling impedance
and zero impedance, elimination of source - Information of the line name and line
impedance and fault resistance influence, length
and by multiple fault location calculations - The complete directory path and name
using different parameters (summer/winter of the disturbance fault record
etc.)
- Duration of the fault record
• Printout of fault history in tabular form for • Information regarding the trigger of the
use in graphical displays with typical
recording
spreadsheet programs such as Excel; dis-
play of time, distance to fault and imped- • Information regarding the disturbance and
ance vector of the line loop. location of the fault
- Fault type
The information printed out in the "short
report" (see Fig. 2) is the following: - Fault duration
- Impedance at the fault in polar and carte-
• Information about the fault record
sian format
- Name of the acquisition unit recording
- Distance to the fault.
the disturbance

Fig. 2 "Short Fault Report"


ABB Switzerland Ltd Fault Analysis and Evaluation Module for E_wineve
Utility Automation Systems
Power System Monitoring 1MRB520153-Ben
Page 5

Power analysis calculation • Sum, difference, multiplication and divi-


The power analysis calculation can be used to sion, average of input signals
derive useful data for in-depth fault analysis
• Pre-programmed function for calculation
by means of additional calculations and com-
bining of recorded signals. For example, the - RMS values
analysis of harmonics provides a measure of - impedance and power vectors
the quality of a voltage. It also permits the
calculation of the effective short-circuit pow- - harmonic contents
er which has led to a damage of switching - frequency deviation
elements, using the measured short-circuit
• Formula editor, on-line syntax check, and
currents and voltages. The loop impedance as test execution of the calculation program
a function of time (impedance and phase an-
gle) derived from the sequence of the voltage • Linking the stored calculation for auto-
and current is another possible calculation. matic execution.

Fig. 3 Power analysis calculation functions


ABB Switzerland Ltd Fault Analysis and Evaluation Module for E_wineve
Utility Automation Systems
Power System Monitoring 1MRB520153-Ben
Page 6

Functions (cont´d) The power analysis calculation can be utili- plotted as an impedance chart, whereby the
zed to calculate the polar impedance value trajectory of the fault impedance can be plot-
and the angle, and thereby to further calculate ted and coordinated with the setting of the
the cartesian impedance values - the real and protection relay.
imaginary values - R and jX. These values
can be exported to an Excel spreadsheet and

Fig. 4 Fault history in tabular form - exported to Excel

Expert fault reporting and time calculation • A typical recording contains the short cir-
function cuit time, type of fault, distance to the
The expert function is an extension of the fault, duration of the fault, short circuit
automatic fault location system. The expert impedance
function helps in executing additional calcu-
lations for working out the short-circuit dura- • Pre-fault, fault and post-fault values of the
tion as well as the line voltage and current voltages and currents, phase and angle val-
signal vectors. The results of such a calcula- ues for the time before and after the fault
tion take the form of printed summaries and occurred, as well as after a return to nor-
text files. (See Fig. 5: Expert fault location mal conditions
report). • Application-specific analysis of digital
signals using the formula editor, e.g. ana-
• Fast fault summary "short fault report" -
lysis of digital signals taking chronological
automatically printed out and stored as a
interdependence into consideration
text file
• Formula editor with BASIC-like syntax
• Selective printout of the fault report (see
Fig. 6).
ABB Switzerland Ltd Fault Analysis and Evaluation Module for E_wineve
Utility Automation Systems
Power System Monitoring 1MRB520153-Ben
Page 7

Fig. 5 Expert fault location report


ABB Switzerland Ltd Fault Analysis and Evaluation Module for E_wineve
Utility Automation Systems
Power System Monitoring 1MRB520153-Ben
Page 8

Functions (cont´d)

Fig. 6 Selective printing of fault report and time calculation formula editor

Data base and statistical analysis - Event number, event date and time
IndBase is a data base for the management - Trigger type
and statistical analysis of fault location results
and expert analysis. Each fault that occurs is - Fault distance, fault duration, fault type
managed as a data set, in which the most im- • Extended search functions in data base,
portant values are stored. query on the following (see Fig. 8):
• A typical recording contains the station - Station
number and name, event number and date, - Line
trigger type and criterion, line name, type
of fault, distance to fault and fault duration - Fault type
• The records in the data base can be sorted - Date from - to
out in ascending or descending order based - Fault distance
on 4 priority levels of sorting keys. The - Fault duration
keys can be selected from any of the fol-
lowing attributes (see Fig. 7): - Fault trigger types
- Disturbance record, fault location report, • File administration with editing function
directory path and file names for adding/deleting records, and storing the
configuration data for output of the records
- Station number, station name and line
of the data base on screen (see Fig. 9)
name
• Data export as text file.
ABB Switzerland Ltd Fault Analysis and Evaluation Module for E_wineve
Utility Automation Systems
Power System Monitoring 1MRB520153-Ben
Page 9

Fig. 7 Sort function of the expert data base

Fig. 8 Search function of the records in the data base


ABB Switzerland Ltd Fault Analysis and Evaluation Module E_wineve
Utility Automation Systems
for Power System Monitoring 1MRB520153-Ben
Page 10

Functions (cont’d)

Fig. 9 Configuration of the on-screen output of the disturbance records

Variants / The E_wineve evaluation system is available


packages in the following variants:

1. RelView
2. Professional
Expert
Statistical
Analysis
3. Expert

Expert
Time
Fault
Calculation
Reporting
Professional

Power Power
Fault Fault
Analysis Analysis
Location Location
Calculation Calculation
RelView

Visualization/ Visualization/ Visualization/


Merge Merge
Display Display Display

Fig. 10 Variants / Packages of E_wineve

RelView Professional
The RelView variant is the basic entry level The Professional variant provides advanced
of the E_wineve. The functionality comprises functionality in addition to the features avail-
the display/view of the fault records, analog able with the RelView variant.
and digital signals.
ABB Switzerland Ltd Fault Analysis and Evaluation Module for E_wineve
Utility Automation Systems
Power System Monitoring 1MRB520153-Ben
Page 11

The advanced functionalities are: Expert


The Expert variant is an advanced extension
• automatic or manual fault location - "short of the Professional variant, and provides
fault report" functionality for quick overview and analysis,
• merge of two or more fault recorders into a and statistical information of system-wide
new file faults in the transmission and distribution net-
work.
• batch-mode: disturbance record file oscil-
lography - analog and digital signals - is
The additional functionality comprises the
automatically printed out
selective printout of the fault location report,
• power analysis calculation. calculation of the operating times of the
switchgear and the protection equipment.
Any desired power analysis calculation can
be programmed and the values can be dis- In addition all the system-wide fault reports
played as a function of time, along with the can be stored in the data base and evaluated
original analog and digital signals. The calcu- as per user-specific search and sort criteria.
lated signals are stored along with the origi-
nal signals.

Ordering Description SW variant License type Ordering number


information Software installation CD all all 1MRB260034R0099
License key RelView Single-user 1MRB260034R0001
Professional Single-user 1MRB260034R0011
Professional Multi-user license 1MRB260034R0012
Expert Single-user license 1MRB260034R0021
Expert Multi-user license 1MRB260034R0022
30-day Trial license key Expert Single-user On request:
SA-LEC-Support@ch.abb.com
User manual ENGLISH 1MRB520290-Uen
GERMAN 1MRB520290-Ude

Remarks:
• This data sheet considers E_wineve version 1.0 to 1.4 of software suite Power System Moni-
toring PSM V1.0 to PSM V1.4.
• The successor of the software described here is PSM 505, V1.5. See Chapter “Other relevant
documents”.
ABB Switzerland Ltd Fault Analysis and Evaluation Module E_wineve
Utility Automation Systems
for Power System Monitoring 1MRB520153-Ben
Page 12

Technical data Hardware platform and operating system Minimum requirements:


Intel Pentium - 333 MHz CPU
128 MBytes RAM
100 MBytes storage for SW (disturbance files and
fault report files not included)
CD-ROM drive
Keyboard, Mouse
Monitor resolution 1024 by 768 pixels with 65535
colors
Operating system:
Microsoft Windows NT 4.0 WS SP 5
Microsoft Windows 2000 SP3
Microsoft Windows XP
Application software E_wineve RelView
Professional
Expert
Languages English, German
Fault / disturbance record file formats Indactic EVE formats (Indactic 65/650)
RE.216/316*4 EVE format
REB500 COMTRADE format
COMTRADE (IEEE C37.111-1991)
REVAL format
Functions Event display: value cursor
time cursors
time scaling
grouping of signals
individual color
multi-event display
Calculations: arithmetic operations
(+, -, *, /)
trigonometric operations (sine, cosine)
harmonics (vector and angle)
impedance (vector and angle)
power (power vector)
distortion
true RMS
phase angle
frequency deviation
Fault location: automatic mode(distance protocol)
distance to fault as a table (distance and
impedance)

Other relevant Indactic 650 - Fault Recording System for Professional Fault Analysis 1MRB520255-Ben
documents SMS 530 - Substation Monitoring System 1MRB520268-Ben
IT
Inform Power System Monitoring
PSM 505 - Stand-alone Fault Analysis and Evaluation Tool 1MRB520376-Ben

ABB Switzerland Ltd


Utility Automation Systems
Brown-Boveri-Strasse 6
CH-5400 Baden/Switzerland
Tel. +41 58 585 77 44
Fax +41 58 585 55 77
E-mail: substation.automation@ch.abb.com

www.abb.com/substationautomation

Printed in Switzerland (0308-0400-0)

You might also like