Open-core power voltage transformers: Concept,


properties, and application

(http://www.amazon.com/Chernobyl-dead-Essays-energy-renewable-ebook/dp/B014PY5DHG)

The power voltage transformer, which is a single-phase unit used for direct conversion of power from
high to low voltages, is becoming more and more relevant for substation applications. This article aims
to present the properties and advantages of the open-core design concept, which has been functioning
very well for a number of years in inductive voltage and combined instrument transformers, enhancing
the transformer reliability and operational safety.

A power voltage transformer is a single-phase unit used for direct transformation of power from a high,
transmission level voltage (up to 550 kV) to a low voltage (under 1 kV). Typical power ratings of open-core
power voltage transformers are in the range from 10 to 167,5 kVA. The basic concept of these transformers is
that they are instrument transformers by design and power or distributive transformers in application. This
means that these transformers are designed using the principles and according to standards relevant for
instrument transformers, retaining the same insulation requirements, short-circuit withstand capabilities and the
ability of permanent operation at increased voltages (usually 1,2 times the rated voltage) [1 – 3].

This approach eliminates the necessity for complex and expensive protection and monitoring systems and by
default assumes a long-term, maintenance-free operation. On the other hand, the function of these
transformers is inherited from power transformers as they are used to supply power for various applications,
which stem precisely from the way these transformers are designed. In some cases, these transformers can
serve a dual function, incorporating both power transmission and measurement or protection utilisation in one
enclosure. The open-core design, available only with paper-oil as the main insulation, provides several extra
benefits when viewed both from designer and user standpoints, such as: ferroresonance immunity, inherent
explosion safety and decrease of inrush current.

Transformer concept and component overview

An example of an open-core power transformer can be seen in Fig. 1. The transformer is designed around an
open core, which is basically a pole in the centre of the transformer. The main magnetic flux passes through
the surrounding non-magnetic material.

http://www.ee.co.za/article/open-core-power-voltage-transformers-concept-properties-ap... 2016/11/10
Open-core power voltage transformers: Concept, properties, and application - EE Publish... Page 4 of 17

http://www.ee.co.za/article/open-core-power-voltage-transformers-concept-properties-ap... 2016/11/10
Open-core power voltage transformers: Concept, properties, and application - EE Publish... Page 5 of 17

(http://www.ee.co.za/wp-content/uploads/2015/01/07-tt-otok-open-core-power-Fig.01.gif)

1. Primary terminal; 2. Bellows cover; 3. Stainless steel bellows; 4. Heat sink; 5. Insulator; 6.
Mineral oil; 7. Main insulation; 8. Primary winding; 9. Secondary winding; 10. Open-core; 11.
Terminal boxes; 12. Transformer bases.
Fig. 1: Transformer cross-section, with an outline of the main components.

The design of all other components is dictated by the open core. This is most apparent with the design of the
primary winding and the main insulation cylinder. The open core allows the primary winding to be divided into
serially connected sections which are completely exposed to the natural oil flow, as well as the construction of
the capacitively graded main insulation, which is essential in order for the transformers to comply with the
requirements for higher voltage levels. Furthermore, the capacitive screens from the main insulation are
connected to the sections of the primary winding, thus assuring a constant synergy between the two, leading to
transformer insusceptibility towards overvoltages [4]. This also allows for the total control of parameters during
the design process.

Additionally, as the main insulation is geometrically cylindrical, this also draws some technological benefits,
such as the ability to produce the main insulation by machine, thus greatly speeding up the production process
and reducing the amount of human intervention. This ensures uniformity and high precision during in-factory
production processes [5].

The active part of the transformer is placed into a porcelain or composite insulator, essentially making the
transformer its own bushing, contributing to the slender design of the transformer and consequently decreasing
the overall weight and dimensions, while improving the weight distribution along the transformer. The tall, lean
build also positively influences the leakage reactance and the impedance voltage of these units [6]. The
aforementioned concept also eliminates practically all metallic constructive components in the path of the main
or the leakage magnetic flux, which could potentially lead to increased additional stray losses [7]. The only
metal components in the path of the flux are the insulator flanges, whose losses are controlled during the
electrical design process [6]. The impedance voltage of these units is comparable to that of closed core
transformers of the same ratings.

Open-core design specific features

http://www.ee.co.za/article/open-core-power-voltage-transformers-concept-properties-ap... 2016/11/10
Open-core power voltage transformers: Concept, properties, and application - EE Publish... Page 6 of 17

The main advantages of the open-core concept are:

Ferroresonance immunity
Inherent explosion safety

Inrush current decrease

Insusceptibility to overvoltages

Ferroresonance immunity

Ferroresonance can be defined as a non-linear resonant phenomenon which manifests in oscillations between
the non-linear inductance of the transformer and grid capacitance. This phenomenon can lead to increased
voltages or currents appearing across the transformer, possibly resulting in damage to the transformer itself [8].
This has been found to be an issue with closed core inductive voltage transformers in service.

The open magnetic core can, for calculation purposes, be substituted with a closed core with an equivalent air
gap. The width of the air gap can be determined using both analytical and numerical approaches [9]. For power
voltage transformers this value typically ranges from 10 to 30 mm, depending on the core geometry. This air
gap influences the magnetising curve of the transformer, making it more linear and smoothing the curve knee-
point. The comparison of typical magnetising curves for open and closed core transformers can be seen in Fig.
2.

(http://www.ee.co.za/wp-content/uploads/2015/01/07-tt-otok-open-core-power-Fig.02.gif)

Fig. 2. Comparison of the open and cor network capacitance.

When the grid capacitance range is added to the same chart (Fig. 2), it is apparent that the probable range of
intersection between the magnetising curve and capacitance, which is a prerequisite for ferroresonance, is
vastly smaller (non-existent even) for open-core transformers than for closed-core transformers. Although this

http://www.ee.co.za/article/open-core-power-voltage-transformers-concept-properties-ap... 2016/11/10
Open-core power voltage transformers: Concept, properties, and application - EE Publish... Page 7 of 17

chart is based on instrument transformers, the same logic extends to power voltage transformers as both types
share the same common denominator [6].

This fact has been recognised by the IEC, so the recent technical report by the IEC 61869 workgroup, which
deals with topics connected to ferroresonance of inductive transformers, recommends the inclusion of an air
gap into the core of any inductive transformer to decrease or eliminate ferroresonance [10].

Ferroresonance immunity of open-core transformers is verified with multiple criteria, including digital
simulations of most common situations for ferroresonance inception in transmission networks, most importantly
the situation when a transformer is energised through a capacitor for field grading optimisation of the open
circuit breaker [8]. However, the most important criterion is field experience with open-core inductive voltage
transformers, where no fault has ever been recorded that could be connected to ferroresonance.

Inherent explosion safety

Protection from transformer explosions is usually associated with SF6 insulated transformers, because of the
rupture disc incorporated into the design of their enclosure [11]. This concept successfully mitigates the effect
of the internal fault.

The open-core concept introduces explosion safety to paper-oil insulated power voltage transformers. The
explosion safety principle eliminates the possibility of internal arcing under normal operating conditions. This
feature is one of, if not the most important asset of open-core power voltage transformers, which ensures a
better operational security and reliability.

The primary winding consists of multiple independent sections (whose number is dictated by the voltage level
and/or power rating of the transformer). This fact causes the transformer to be insusceptible to internal arcing.

If a fault originates from inside the transformer, then it is most probably located in the primary winding, either
between turns or layers of one section or between two adjacent sections. In either of these cases, due to the
sectioned design, the fault remains localised to only one section and does not spread through the entire
winding.

The grid voltage is then distributed across all other sections, thus limiting the fault current and preventing a
direct short circuit connection between high voltage and ground. Even if the fault is located in the main
insulation, due to the fact that screens from the insulation cylinder are galvanically connected to the
corresponding primary winding sections, the fault again remains localised to one section of the winding, while
the rest of the sections prevent a catastrophic breakdown of the transformer. This feature makes the power
voltage transformers comparable to capacitive voltage transformers, in that their insulation also consists of
many elements (capacitive) connected in series and prevents direct line-to-ground faults in the same way.
Essentially, this means that an internal fault is reduced from a fast and disruptive occurrence to a slower,
noticeable phenomenon.

These hypotheses were confirmed by testing open-core inductive voltage transformers, where a worst case
scenario was simulated. One winding section was intentionally short circuited. The transformer was then
subjected to its rated voltage while electrical parameters and pressures inside the transformer were monitored.
While the transformer was connected to a high voltage, the primary current (mainly consisting of the
magnetising current), was increased approximately two-fold and remained well in the value range of mA,
meaning that it did not venture into ranges associated with network short-circuits (values in kA). Furthermore,

http://www.ee.co.za/article/open-core-power-voltage-transformers-concept-properties-ap... 2016/11/10
Open-core power voltage transformers: Concept, properties, and application - EE Publish... Page 8 of 17

the increased thermal stress of the faulty winding caused an increased release of gasses from the transformer
oil, which led to an increase in volume and consequently to a pressure rise inside of the transformer. When the
oil pressure exceeded the design value of the intentional weak spot of the transformer (bellows and bellows
cover), a controlled release of pressure occurred in the dilatation bellows, without any oil spill, resulting only in
detaching the bellows cover from the transformer.

This occurrence is illustrated in Figs. 3 and 4. Conveniently, the connection of the primary terminal is
established by means of the bellows cover, meaning that its detachment also disconnects the transformer from
the grid, thus providing an automatic disconnection of the transformer under fault conditions. Another
advantage is that the information about the pressure rise inside the transformer can be obtained well before the
bellows cover detaches either by checking the bellows position in the oil level indicator window or by monitoring
the pressure rise itself. The latter is actually the basis for an efficient and reliable monitoring of power voltage
transformers. The most common solution is an overpressure switch which can trip the monitoring or the
protection system when the oil pressure exceeds a certain predefined value, indicating that the transformer
needs to be inspected. This ensures an unparalleled reliability of open-core transformers and is more than
sufficient for all power voltage transformer monitoring needs, with very little or no additional cost.

http://www.ee.co.za/article/open-core-power-voltage-transformers-concept-properties-ap... 2016/11/10
Open-core power voltage transformers: Concept, properties, and application - EE Publish... Page 9 of 17

(http://www.ee.co.za/wp- (http://www.ee.co.za/wp-
content/uploads/2015/01/07-tt-otok-open-core- content/uploads/2015/01/07-tt-otok-open-core-
power-Fig.03.gif)Fig. 3: Inductive voltage power-Fig.04.gif)Fig. 4: Inductive voltage
transformer before the bellows. transformer after the bellows.

Inrush current decrease

Inrush current is present when any transformer is switched on. It can achieve an instantaneous value of ten or
more times higher than the rated current of the transformer [12]. The peak value of the current is defined by
equation 1.

(http://www.ee.co.za/wp-content/uploads/2015/01/07-tt-Otok-consulting-eqn-
01.gif) (1)

http://www.ee.co.za/article/open-core-power-voltage-transformers-concept-properties-ap... 2016/11/10
Open-core power voltage transformers: Concept, properties, and application - EE Publi... Page 10 of 17

where:

Al is the core cross section; A is the area enclosed by one turn of the winding; i0 is the mean length of the
magnetic path; B, Bs and Br are the rated flux density, saturation flux density and remanent flux density
respectively [13].

The magnitude of the inrush current is influenced by several factors, ranging from the moment of connection
and the angle of the voltage waveform to the remanent magnetism displayed in equation 1 by the variable Br.

Remanent magnetism is a consequence of the hysteresis loop and the inability of the magnetic core to
demagnetise instantly [14].

With closed-core transformers, the remanent flux density can range from 50 to 90% of the rated flux density
value, depending on the core material and core assembly [13]. According to equation 1, the remanent flux
density is superposed to the rated flux density, meaning that the core can be deeply saturated, thus resulting in
a high inrush current value.

The introduction of the air gap into the magnetic circuit can drastically decrease the remanent magnetism and
consequently the peak value of the inrush current [13,14]. Additionally, we can draw a parallel to the current
transformer cores with transient response requirements such as TPY or TPZ classes, which according to IEC
61869-2 require the remanent magnetism (i.e. remanence factor Kr) to be less than 10 % of the rated flux. If
the typical air gap values of such cores, which range from 4 – 12 mm are compared to typical equivalent air
gap values of open-core power voltage transformers, it can be concluded that the open-core practically
eliminates the remanence flux altogether.

Insusceptibility to overvoltage

Fig. 5 shows the equivalent diagram of the open-core transformer [16].

http://www.ee.co.za/article/open-core-power-voltage-transformers-concept-properties-ap... 2016/11/10
Open-core power voltage transformers: Concept, properties, and application - EE Publi... Page 11 of 17

(http://www.ee.co.za/wp-content/uploads/2015/01/07-tt-otok-open-core-power-Fig.05.gif)

Fig. 5. Equivalent diagram of the open-core power voltage transformer active part.

The main goal of a well-designed insulation system is an equalised distribution of dielectric stresses along all
areas of the insulation, both internal (oil impregnated paper insulation, between layers and sections of the
primary winding) and external (insulator – air boundary). As shown in Fig. 5, the transformer is actually a
complex LC network (resistance values, although present, do not influence the dielectric stress distribution of
the transformer), which means that the dielectric stress distribution is hugely dependent on the frequency of the
overvoltage applied to it [16]. The number of nodes in this network corresponds to the number of primary

http://www.ee.co.za/article/open-core-power-voltage-transformers-concept-properties-ap... 2016/11/10
Open-core power voltage transformers: Concept, properties, and application - EE Publi... Page 12 of 17

winding sections. Each section is directly connected to a capacitive screen in the main insulation. The
capacitance between two adjacent screens is represented by C1 to Cn capacitances in the equivalent diagram.

The self-capacitance of the section is small by comparison and can be disregarded [16]. Each screen has a
capacitance to ground designated by Co1 to Con. Each section is represented by its self-inductance (L1 to Ln)
and an array of mutual inductances towards all other sections. These two sets of parameters comprise the
inductance matrix which is calculated using FEM analysis, while the capacitances can be calculated
analytically, because of the cylindrical geometry of the insulation [16, 17]. Once all parameters have been
determined, they can be imported into an EMTP solver, which can then calculate the voltage distribution across
the primary winding for various operation scenarios, most notably a lightning impulse, a switching impulse and
sinusoidal overvoltages at different frequencies. Each of these parameters can be easily controlled by design:
The section inductance can be fine-tuned by changing the number of turns of each section, and capacitances
can be optimised by changing the geometry of capacitive screens in the main insulation. An example for the
calculation of lightning impulse voltage distribution for a 362 kV, 100 kVA power voltage transformer can be
seen in Fig. 6.

(http://www.ee.co.za/wp-content/uploads/2015/01/07-tt-otok-open-core-power-Fig.061.gif)

Fig. 6. Lightning impulse voltage distribution for 362 kV power voltage transformer.

As can be seen from Fig. 6, the voltage distribution is practically linear during the entire duration of the voltage
impulse.

This ability to withstand overvoltages of various types (waveform, amplitude, frequency) has been confirmed by
a range of tests and positive service experience of the open-core inductive voltage transformers [16]. The
feature that separates power voltage transformers from inductive voltage transformers is their behavior under
sinusoidal voltages at different frequencies. This is because the power voltage transformers have a lower

http://www.ee.co.za/article/open-core-power-voltage-transformers-concept-properties-ap... 2016/11/10
Open-core power voltage transformers: Concept, properties, and application - EE Publi... Page 13 of 17

primary winding inductance (due to a smaller number of turns) than their instrument transformer counterparts,
which results in a very stable voltage distribution over a typical range of lower frequencies. While the voltage
distribution for instrument transformers is fine tuned for both the rated frequency and the test frequency of the
power-frequency withstand voltage test (usually 100 to 150 Hz), experience has shown that for power voltage
transformers it is enough to adjust the distribution only for the rated frequency, and a wide range of other
frequencies will exhibit the same distribution.

This fact is illustrated in Figs. 7 and 8, which show calculated and measured voltage distributions for a 145 kV
50 kVA power voltage transformer unit. This behaviour is inherent to all transformers of this type.

(http://www.ee.co.za/wp-content/uploads/2015/01/07-tt-otok-open-core-power-Fig.071.gif)

Fig. 7: Voltage distribution for 145 kV. Power is expressed in p.u.

http://www.ee.co.za/article/open-core-power-voltage-transformers-concept-properties-ap... 2016/11/10
Open-core power voltage transformers: Concept, properties, and application - EE Publi... Page 14 of 17

(http://www.ee.co.za/wp-content/uploads/2015/01/07-tt-otok-open-core-power-Fig.081.gif)

Fig. 8: Percentage deviation from ideal voltage distribution.

Figs. 7 and 8 show that voltage distribution is highly linear in all cases. Furthermore, a strict control of dielectric
stress in the entire active part also controls the stress distribution on the insulator surface. These two combined
cause the transformers to be able to achieve the insulation requirements for the highest voltage levels.

Additionally, the transformers are partial-discharge (PD) free (PD less than 10%) even at power frequency
withstand voltage. This fact greatly enhances the lifetime of the transformer and reduces breakdowns due to
insulation ageing influenced by PD [18].

Application

The most common application of these transformers is for the “in-house” supply of various substations,
meaning the supply of power for auxiliary equipment, such as protection and monitoring systems.

In this configuration, the power voltage transformer substitutes a distributive transformer or diesel generator.
This solution is very convenient in remote substations which have no access to the distribution system, which is
common in countries which have large territories with low population density, such as the USA, Canada and
Australia. An example of such transformers for this application is shown in Fig. 9.

http://www.ee.co.za/article/open-core-power-voltage-transformers-concept-properties-ap... 2016/11/10
Open-core power voltage transformers: Concept, properties, and application - EE Publi... Page 15 of 17

(http://www.ee.co.za/wp-content/uploads/2015/01/07-tt-otok-open-core-power-Fig.091.gif)

Fig. 9. 362 kV transformers for auxiliary supply of a substation in Estonia

The other conventional, albeit less common, application is for the power supply of remote communication
towers or antennae, mines, pump stations, etc. In this case, by building a lightweight station it is possible to
ensure an economical, robust and reliable power supply. Due to their modest weight and ease of transport,
these transformers can be used for a temporary supply of local demand while the substation is being built, or
as an emergency supply after faults or environmental disasters.

The idea is to use the power voltage transformer as a primary unit in a substation to provide electrical energy to
remote communities and users. This way it is possible to reach numerous rural communities or mountainous
areas where the construction of the distribution grid is economically unviable, or even technically impossible,
thus providing stable electrical energy to those who do not have it.

A substation based on a power voltage transformer as the main transformer can be very compact and
straightforward, resulting in savings in both the primary and secondary equipment, protection and monitoring
alike. HV switchgear (which would most probably exceed the transformer itself in sheer cost) can be replaced
by a HV fuse, no extensive monitoring is necessary and maintenance is basically limited to periodic visual
checks and routine site measurements, just as with instrument transformers. Some confirmation of this has
already been reported, as cost-benefit analyses of pilot projects have shown that this type of substation can
cost approximately one-third of a regular substation [20].

Conclusion

http://www.ee.co.za/article/open-core-power-voltage-transformers-concept-properties-ap... 2016/11/10
Open-core power voltage transformers: Concept, properties, and application - EE Publi... Page 16 of 17

The open-core power voltage transformer is an ideal solution for an auxiliary supply of substations or remote
consumers, both communities and industry. The advantages these transformers offer support the
“maintenance free” philosophy, but also, due to their explosion safety, ferroresonance immunity and other
traits, can truly be labelled as “install-and-forget” units which are proven to operate reliably in all conditions,
which is the premise of the entire concept. Furthermore, precisely because of these advantages, substation
design can also be simplified and made more financially attractive. Therein lies the potential for a more
widespread use of power voltage transformers as primary units for power supply and distribution to remote
areas in the vicinity of overhead power lines.

References

[1] IEC 61869-1:2009: “Instrument Transformers – Part 1: General Requirements”, 2009.


[2] IEC 61869-3: “Instrument Transformers – Part 3: Additional requirements for voltage transformers”, 2011.
[3] IEEE C57.13: “IEEE Standard requirements for instrument transformers”, IEEE engineering society, 2008.
[4] M Poljak, B Bojanić, T Hafner, J Tomašević: “A new Concept of Combined Transformers”, European
Transactions on Electrical Power, Vol. 6, pp. 2563-259, August 1996.
[5] M Poljak, B Bojanić: “Dilemma – Inductive or Capacitor Instrument Transformers”, Cigré Croatia, 2003.
[6] I Žiger, D Krajtner, Z Ubrekić, M Brkić: “Design of the open-core power voltage transformer”, International
Colloquium Transformer Research and Asset Management, Dubrovnik, Croatia, 2012.
[7] Ž Janić: “Improvement of Power Transformer Design in Order to Reduce Stray Losses”, Doctoral
dissertation, Faculty of Electrical Engineering and Computing, Zagreb, 2008.
[8] D Krajtner: “Influence of the Inductive Transformer Construction on Ferroresonance Appearance in High
voltage Networks”, Cigré Croatia, 2005.
[9] V Bego: “Instrument Transformers” (In Croatian), 1977.
[10] IEC/TR 61869-102 Ed.1.0: “Instrument Transformers – Ferroresonance oscillations in substations
associated with inductive voltage transformers” – Draft approved for publication, January, 2013.
[11] TIP – SF6 Station Service Voltage Transformer: Cost-effective solution for insulated applications, ABB
product catalogue, 2013.
[12] S Kahrobaee, MC Algrain, S. Asgarpoor: “Investigation and Mitigation of Transformer Inrush Current
During Black Start of an Independant Power Producer Plant”, Energy and power Engineering, Vol. 5, 2013.
[13] SV Kulkarni, SA Khaparde: “Transformer engineering – Design and Practice”, Marcel Dekker, New York,
2004.
[14] WT McLyman: “Transformer and Inductor Design Handbook”, Marcel Dekker, New York, 2004.
[15] IEC 61869-2: “Instrument transformers – Part 2: Current transformers”, 2010.
[16] M Poljak: “Insulation System of Combined Instrument Transformers”, Doctoral dissertation, Faculty of
Electrical Engineering and Computing, Zagreb, 2006.
[17] D Filipović-Grčić: “Optimisation of condenser type insulation system made of oil impregnated paper”,
Doctoral dissertation, Faculty of Electrical Engineering and Computing, Zagreb, 2010.
[18] M Poljak, B Bojanić: “How to prevent instrument transformer explosions”, Cigré Croatia, 2007.
[19] F Birol: “Energy for all: financing access for the poor”, Energy for All Conference, Oslo, Norway, October
2011.
[20] OR Calvo, RG Ibarra, A Solano, E Acosta: “Rural Electrification in Chihuahua, Mexico at one third of the
cost vs a conventional substation”, World Energy Congress, Montreal, Canada, September 2010.

Contact Stanislav Kolenic,Otok Consulting, Tel 011 807-0993, stanko@telkomsa.net


(mailto:stanko@telkomsa.net)

http://www.ee.co.za/article/open-core-power-voltage-transformers-concept-properties-ap... 2016/11/10
Open-core power voltage transformers: Concept, properties, and application - EE Publi... Page 17 of 17

Related Tags
Energize T+D Technical (http://www.ee.co.za/tag/energize-td-technical)Otok Consulting
(http://www.ee.co.za/tag/otok-consulting)
240
48

(http://www.ee.co.za/subscriptions/apple- (https://www.facebook.com/eepublishers) (http://www.linkedin.com/company/ee-


ios-e-zines) publishers)

1. 1
2. 2

Previous (#)
Next (#)

http://www.ee.co.za/article/open-core-power-voltage-transformers-concept-properties-ap... 2016/11/10

You might also like