Station Room 3 Y N
Any Fault alarms sustained on Station UPS charger “2A” or “2B” (Report to LCO and defect if any)
Any Fault alarms sustained on 220V Station Battery charger “A” or “B” (Report to LCO and defect if any)
Any Fault alarms sustained on 220V DC Station “A”, “B” or “C” (Report to LCO and defect if any)
Any Fault alarms sustained on the 50V Telecoms Battery charger (Report to LCO and defect if any)
380V Station Diesel Gen board breaker to Diesel Gen “A” racked in? (If not report to LCO)
380V Station Diesel Gen board breaker to Diesel Gen “B” racked in? (If not report to LCO)
380V Diesel Gen board Live from 380V Distribution board “A” or “B” A B
Are the Lights in the switchgear room all in working condition? (Defect if Not)
Housekeeping, fire extinguishers & diagrams in order. (Defect if Not)
Is the access gate closed and locked? (Defect any damage to gate & lock)
Station Room 2 Y N
Any Fault alarms sustained on any of 11kV Station board 2 breakers (Report to LCO and defect if any)
All breaker indication lamps still in working condition? (Replace if not)
All breakers IED screens still in working condition? (Report to LCO and defect if any)
Any Fault alarms sustained on Station UPS charger “1A” or “1B” (Report to LCO and defect if any)
Is 380V Station Crane board 1 Live? (Investigate & Report to LCO if not)
Is 380V Distribution board 1 Live (Investigate & Report to LCO if not)
Is 380V Distribution board 2 Live (Investigate & Report to LCO if not)
Is the 380V breakers (Dis. Brd. 1 & 2) to Station Diesel Gen board racked in and close? (If not report to LCO)
Are the Lights in the switchgear room all in working condition? (Defect if Not)
Is the gate to 11/0,4kV Distribution Trfr 1 & 2 closed and locked? (Defect any damage to gate & lock)
Is the gate to Station Crane Trfr closed and locked? (Defect any damage to gate & lock)
Is the switchgear room air conditioner in service and blowing out cool air (Defect if not)
Are both access doors closed and locked? (Defect any damage to doors & locks)
Housekeeping, fire extinguishers & diagrams in order. (Defect if Not)
When downloaded from the document management system, this document is uncontrolled and the responsibility rests with
the user to ensure it is in line with the authorised version on the system.
No part of this document may be reproduced without the expressed consent of the copyright holder, Eskom Holdings SOC
Ltd, Reg No 2002/015527/30.
Template Rev 5
240-43921804
MATLA POWER STATION Identifier
Document Rev 2
15738
Electrical Operating Desk Identifier
Plant Inspection Effective Date 21 August 2017
Review Date August 2020
Station Room 1 Y N
Any Fault alarms sustained on any of 11kV Station board 1 breakers (Report to LCO and defect if any)
Any Fault alarms sustained on 11kV Station board 1 & 2 MIB breakers (Report to LCO and defect if any)
All breaker indication lamps still in working condition? (Replace if not)
All breakers IED screens still in working condition? (Report to LCO and defect if any)
Are all indications lamps working on the Station Trfr. panel (Replace if not)
Any Fault alarms sustained on 24V Station Battery charger “A”, “B”, “C” or “D” (Report to LCO and defect if
any)
Any batteries found leaking? (Defect if any)
Any batteries found with low battery water levels? (Defect if any)
Is there any corrosive buildup (green or white) on any of the battery terminal? (Defect if any)
Is the switchgear room air conditioner in service and blowing out cool air (Defect if not)
Are the Lights in the switchgear room all in working condition? (Defect if Not)
Are both access doors closed and locked? (Defect any damage to doors & locks)
Housekeeping, fire extinguishers & diagrams in order. (Defect if Not)
Station Diesel Gens (Indicate Y for Yes & N for No) A B Switchgear
Any Fault alarms sustained on local control panels (Report to LCO and defect if any)
All breaker indication lamps still in working condition? (Replace if not)
Local breakers (Large MCB) closed? (If not follow up)
Water jacket heater Mcb “ON” (If tripped switch on once only, defect if it trips again)
Diesel Gen engine warm (If not defect water heater)
Diesel Gen radiator water level full. (Top up if not)
Any Oil leaks on the Diesel gen? (Defect if any)
Any batteries found leaking? (Defect if any)
Any batteries found with low battery water levels? (Defect if any)
Is there any corrosive buildup (green or white) on any of the battery terminal? (Defect if any)
Are the Lights in the room all in working condition? (Defect if Not)
Are all doors closed and locked. (Defect any damage to gates & locks)
When downloaded from the document management system, this document is uncontrolled and the responsibility rests with
the user to ensure it is in line with the authorised version on the system.
No part of this document may be reproduced without the expressed consent of the copyright holder, Eskom Holdings SOC
Ltd, Reg No 2002/015527/30.
Template Rev 5
240-43921804
MATLA POWER STATION Identifier
Document Rev 2
15738
Electrical Operating Desk Identifier
Plant Inspection Effective Date 21 August 2017
Review Date August 2020
WTP South 11/3,3kV Service & 11/0,4kV WTP Transformers 380V 380V 380V 380V 3,3kV 3,3kV
(Indicate Y for Yes & N for No) 1A 1B 1C 1D 1 2
Any water buildup in the Trfr bund area (Defect if any)
Any oil leaks evident on and around the Trfr. (Defect if any)
Trfr oil level Normal (Defect if below 0,3 (30%))
Trfr Oil temperatures normal. (Report High Temperatures to LCO)
Trfr Winding temperatures normal (Report High Temperatures to LCO)
Oil sampling valves locked. (Defect if no locking mechanism & replace broken
locks)
Housekeeping in order around the Trfr. (Defect if Not)
When downloaded from the document management system, this document is uncontrolled and the responsibility rests with
the user to ensure it is in line with the authorised version on the system.
No part of this document may be reproduced without the expressed consent of the copyright holder, Eskom Holdings SOC
Ltd, Reg No 2002/015527/30.
Template Rev 5
240-43921804
MATLA POWER STATION Identifier
Document Rev 2
15738
Electrical Operating Desk Identifier
Plant Inspection Effective Date 21 August 2017
Review Date August 2020
Assistant shift
Supervisor:
Name: Signature: Date: Time:
Local Control
Officer:
Name: Signature: Date: Time:
When downloaded from the document management system, this document is uncontrolled and the responsibility rests with
the user to ensure it is in line with the authorised version on the system.
No part of this document may be reproduced without the expressed consent of the copyright holder, Eskom Holdings SOC
Ltd, Reg No 2002/015527/30.
Template Rev 5
240-43921804
MATLA POWER STATION Identifier
Document Rev 2
15738
Electrical Operating Desk Identifier
Plant Inspection Effective Date 21 August 2017
Review Date August 2020
380V
11kV 11kV 11kV 3,3kV 3,3kV 3,3kV 3,3kV 380V 380V 380V
Unit 1 MV Switchgear room (Indicate Y for Yes & N for No)
Lighting
Essen.
A B C A B C D C D Lighting
Each board Live from normal supply? (If not investigate and report)
Any relays operated on any of the breakers (Report to LCO and Ptm)
Any Fault alarms sustained on alarm panel (Conlog) (Follow up and report to LCO)
All breaker indication lamps still in working condition? (Replace if not)
Normal supply breakers to relative boards closed? E.g. Supply to N closed from C
(If not investigate)
Remote blocks in position and without defect on all supply & incoming breakers
Bus Zone Protection panel Test blocks in position and without defect (If not
Report & Defect)
All breaker panels and doors closed and without defect (If not Report & defect)
Are the Lights in the switchgear room all in working condition? (Defect if Not)
Loop Supply breaker Closed? (If not follow up) Yes No Description if no:
Are both access doors closed and locked? (Defect any damage to doors & locks) Yes No Description if no:
Housekeeping, fire extinguishers & diagrams in order. (Defect if Not) Yes No Description if no:
When downloaded from the document management system, this document is uncontrolled and the responsibility rests with the user to ensure it is in line with the authorised
version on the system.
No part of this document may be reproduced without the expressed consent of the copyright holder, Eskom Holdings SOC Ltd, Reg No 2002/015527/30.
Template Rev 5
240-43921804
MATLA POWER STATION Identifier
Document Rev 2
15738
Electrical Operating Desk Identifier
Plant Inspection Effective Date 21 August 2017
Review Date August 2020
Unit 2 Service & Dry Transformer bay (Indicate Y for Yes & N for No) A B C D SO3 Precip A Precip B Lighting
Any water buildup underneath the Trfr (Report to LCO & Unit SS)
Any oil leaks evident on and around the Trfr. (Defect if any)
Trfr oil level Normal (Defect if below 0,3 (30%))
Trfr Oil temperatures normal. (Report High Temperatures to LCO)
Trfr Winding temperatures normal, use thermal gun on dry Trfr’s. (Report High Temperatures to LCO)
Trfr Fan in working condition. (Defect if Not)
Trfr Fan control cubicle indication lights working? (Replace blown bulbs)
Lights in the Trfr area in working condition. (Defect if Not (Outage defect for dry Trfr.))
Any water or steam leaks evident into the Trfr area. (Report leaks to LCO & SM A.S.A.P.)
Excessive dust build-up on the Dry Trfr? (Outage Defect if Not)
Housekeeping in order around the Trfr. (Defect if Not)
Trfr gate closed and locked. (Replace any broken locks A.S.A.P.)
11kV 11kV 11kV A B Loop 3,3kV 3,3kV 3,3kV 3,3kV 400V 400V 400V
Unit 2 MV Switchgear room (Indicate Y for Yes & N for No)
MIB MIB MIB Lighting
A B C A B C D C D
Each board Live from normal supply? (If not investigate and report)
Any Fault alarms sustained on any of breakers (Report to LCO and defect if any)
All breaker indication lamps still in working condition? (Replace if not)
All breakers IED screens still in working condition? (Report to LCO and defect if any)
Normal supply breakers to relative boards closed? E.g. Supply to N closed from C (If
not investigate)
Remote blocks in position and without defect on all supply & incoming breakers
Bus Zone Protection panel Test blocks in position and without defect (If not Report &
Defect)
All breaker panels and doors closed and without defect (If not Report & defect)
Are the Lights in the switchgear room all in working condition? (Defect if Not)
Loop Supply breaker Closed? (If not follow up) Yes No Description if no:
Are both access doors closed and locked? (Defect any damage to doors & locks) Yes No Description if no:
Housekeeping, fire extinguishers & diagrams in order. (Defect if Not) Yes No Description if no:
When downloaded from the document management system, this document is uncontrolled and the responsibility rests with the user to ensure it is in line with the authorised
version on the system.
No part of this document may be reproduced without the expressed consent of the copyright holder, Eskom Holdings SOC Ltd, Reg No 2002/015527/30.
Template Rev 5
240-43921804
MATLA POWER STATION Identifier
Document Rev 2
15738
Electrical Operating Desk Identifier
Plant Inspection Effective Date 21 August 2017
Review Date August 2020
Unit 3 Service & Dry Transformer bay (Indicate Y for Yes & N for No) A B C D SO3 Precip A Precip B Lighting
Any water buildup underneath the Trfr (Report to LCO & Unit SS)
Any oil leaks evident on and around the Trfr. (Defect if any)
Trfr oil level Normal (Defect if below 0,3 (30%))
Trfr Oil temperatures normal. (Report High Temperatures to LCO)
Trfr Winding temperatures normal, use thermal gun on dry Trfr’s. (Report High Temperatures to LCO)
Trfr Fan in working condition. (Defect if Not)
Trfr Fan control cubicle indication lights working? (Replace blown bulbs)
Lights in the Trfr area in working condition. (Defect if Not (Outage defect for dry Trfr.))
Any water or steam leaks evident into the Trfr area. (Report leaks to LCO & SM A.S.A.P.)
Excessive dust build-up on the Dry Trfr? (Outage Defect if Not)
Housekeeping in order around the Trfr. (Defect if Not)
Trfr gate closed and locked. (Replace any broken locks A.S.A.P.)
11kV 11kV 11kV A B Loop 3,3kV 3,3kV 3,3kV 3,3kV 400V 400V 400V
Unit 3 MV Switchgear room (Indicate Y for Yes & N for No)
MIB MIB MIB Lighting
A B C A B C D C D
Each board Live from normal supply? (If not investigate and report)
Any Fault alarms sustained on any of breakers (Report to LCO and defect if any)
All breaker indication lamps still in working condition? (Replace if not)
All breakers IED screens still in working condition? (Report to LCO and defect if any)
Normal supply breakers to relative boards closed? E.g. Supply to N closed from C (If
not investigate)
Remote blocks in position and without defect on all supply & incoming breakers
Bus Zone Protection panel Test blocks in position and without defect (If not Report &
Defect)
All breaker panels and doors closed and without defect (If not Report & defect)
Are the Lights in the switchgear room all in working condition? (Defect if Not)
Loop Supply breaker Closed? (If not follow up) Yes No Description if no:
Are both access doors closed and locked? (Defect any damage to doors & locks) Yes No Description if no:
Housekeeping, fire extinguishers & diagrams in order. (Defect if Not) Yes No Description if no:
When downloaded from the document management system, this document is uncontrolled and the responsibility rests with the user to ensure it is in line with the authorised
version on the system.
No part of this document may be reproduced without the expressed consent of the copyright holder, Eskom Holdings SOC Ltd, Reg No 2002/015527/30.
Template Rev 5
240-43921804
MATLA POWER STATION Identifier
Document Rev 2
15738
Electrical Operating Desk Identifier
Plant Inspection Effective Date 21 August 2017
Review Date August 2020
When downloaded from the document management system, this document is uncontrolled and the responsibility rests with
the user to ensure it is in line with the authorised version on the system.
No part of this document may be reproduced without the expressed consent of the copyright holder, Eskom Holdings SOC
Ltd, Reg No 2002/015527/30.
Template Rev 5
240-43921804
MATLA POWER STATION Identifier
Document Rev 2
15738
Electrical Operating Desk Identifier
Plant Inspection Effective Date 21 August 2017
Review Date August 2020
380V 400kV Yard boards & transformers. (Indicate Y for Yes & N for No) A B
380V 400kV yard boards Live from normal supply and the bus section open? (If not follow up)
Are there any panels open on any of the boards? (defect if any)
380V 400kV Yard Trfr oil level, Silica Gel & Oil breather level Normal (Defect if below 0,3 (30%), pink & low oil)
Any oil leaks evident on and/or around the 380V 400kV Yard Trfr. (Defect if any)
Are the Lights in the relay house all in working condition? (Defect if Not)
Housekeeping, fire extinguishers & diagrams in order. (Defect if Not)
400kV & 275kV HV yard gates closed and locked. (Report any damaged locks to TOC and apply a temp. lock)
Is the access door to the 400kV & 275kV relay house closed and locked? (Report any damaged locks to TOC
and apply a temp. lock)
When downloaded from the document management system, this document is uncontrolled and the responsibility rests with
the user to ensure it is in line with the authorised version on the system.
No part of this document may be reproduced without the expressed consent of the copyright holder, Eskom Holdings SOC
Ltd, Reg No 2002/015527/30.
Template Rev 5
240-43921804
MATLA POWER STATION Identifier
Document Rev 2
15738
Electrical Operating Desk Identifier
Plant Inspection Effective Date 21 August 2017
Review Date August 2020
Assistant shift
Supervisor:
Name: Signature: Date: Time:
Local Control
Officer:
Name: Signature: Date: Time:
When downloaded from the document management system, this document is uncontrolled and the responsibility rests with
the user to ensure it is in line with the authorised version on the system.
No part of this document may be reproduced without the expressed consent of the copyright holder, Eskom Holdings SOC
Ltd, Reg No 2002/015527/30.
Template Rev 5
240-43921804
MATLA POWER STATION Identifier
Document Rev 2
15738
Electrical Operating Desk Identifier
Plant Inspection Effective Date 21 August 2017
Review Date August 2020
Unit 1 to 3 Unit 4 to 6
Unit 1 to 6 Gen 20kV breaker and air system Unit 1 Unit 2 Unit 3 Unit 4 Unit 5 Unit 6
Compressors Compressors
(Indicate Y for Yes & N for No for the compressors)
Y N Y N Y N Y N Y N Y N A B A B
Any alarms sustained on the alarm panels (Conlogs) (follow up if any)
Any oil leaks around the compressors? (Defect if any)
Compressor oil levels above the minimum required level mark? Defect if not)
Which compressor is running (Mark A or B) if both follow up why (leaks?)
Check that no motor protections operated on S/by compressor & mark S/by
Any air leaks detected on the running compressor PRV (Defect if any)
Compressor catch pod oil & water drained (Indicate Y or N)
Any air leaks on any of the valves at 9,5meter level (defect if any)
Any air leaks detected from the receivers down to the breaker (Defect if any)
Water drained from the 20MPa & 15MPa air receivers.
Any water leaks detected on the demin tank (Defect if any)
Demin cooling water tank above 80% (Top up if not)
20kV Breaker earth switch motors locked in off position on all three phases?
Indicate A or B for running 20kV breaker vent fan.
Indicate A or B for running 20kV breaker cooling water pump.
Any water leaks on “A” 20kV breaker cooling water pump (Defect if any).
Any water leaks on “B” 20kV breaker cooling water pump (Defect if any).
Any water leaks on the cooling system (Demin or CW) defect if any.
Any air leaks below the 20kV breaker? (Defect if any)
Any air leaks inside the 20kV breaker cubicle? (Defect if any)
20kV Breaker switched to remote and cubicle locked?
Record the 20kV breaker low pressure (3 MPa gauge) MPa MPa MPa MPa MPa MPa
Record the 20kV breaker high pressure (15 MPa gauge) MPa MPa MPa MPa MPa MPa
When downloaded from the document management system, this document is uncontrolled and the responsibility rests with the user to ensure it is in line with the authorised
version on the system.
No part of this document may be reproduced without the expressed consent of the copyright holder, Eskom Holdings SOC Ltd, Reg No 2002/015527/30.
Template Rev 5
240-43921804
MATLA POWER STATION Identifier
Document Rev 2
15738
Electrical Operating Desk Identifier
Plant Inspection Effective Date 21 August 2017
Review Date August 2020
11kV 11kV 11kV A B Loop 3,3kV 3,3kV 3,3kV 3,3kV 400V 400V 400V
Unit 6 MV Switchgear room (Indicate Y for Yes & N for No)
MIB MIB MIB Lighting
A B C A B C D C D
Each board Live from normal supply? (If not investigate and report)
Any Fault alarms sustained on any of breakers (Report to LCO and defect if any)
All breaker indication lamps still in working condition? (Replace if not)
All breakers IED screens still in working condition? (Report to LCO and defect if any)
Normal supply breakers to relative boards closed? E.g. Supply to N closed from C (If
not investigate)
Remote blocks in position and without defect on all supply & incoming breakers
Bus Zone Protection panel Test blocks in position and without defect (If not Report &
Defect)
All breaker panels and doors closed and without defect (If not Report & defect)
Are the Lights in the switchgear room all in working condition? (Defect if Not)
Loop Supply breaker Closed? (If not follow up) Yes No Description if no:
Are both access doors closed and locked? (Defect any damage to doors & locks) Yes No Description if no:
Housekeeping, fire extinguishers & diagrams in order. (Defect if Not) Yes No Description if no:
D. D. N P SO3
Unit 6 LV Switchgear room & 400V boards (Indicate Y for Yes & N for No) A B
Gen A Gen B
Each 400V board Live from its normal supply? (If not investigate and report to LCO ASAP)
All 400V breaker keys switched on i.e. s/by (If not investigate and rectify)
All breaker indication lamps still in working condition? (Replace if not)
Normal supply breakers to relative boards closed? E.g. Supply to D.Gen A closed from A (If
not investigate)
Transfer switched on all relevant board (If not follow up)
All breaker panels and doors closed and without defect (If not Report & defect)
Are the Lights in the switchgear room all in working condition? (Defect if Not)
Are both access doors closed and locked? (Defect any damage to doors & locks) Yes No
Housekeeping, fire extinguishers & diagrams in order. (Defect if Not) Yes No
When downloaded from the document management system, this document is uncontrolled and the responsibility rests with the user to ensure it is in line with the authorised
version on the system.
No part of this document may be reproduced without the expressed consent of the copyright holder, Eskom Holdings SOC Ltd, Reg No 2002/015527/30.
Template Rev 5
240-43921804
MATLA POWER STATION Identifier
Document Rev 2
15738
Electrical Operating Desk Identifier
Plant Inspection Effective Date 21 August 2017
Review Date August 2020
Unit 6 Service & Dry Transformer bay (Indicate Y for Yes & N for No) A B C D SO3 Precip A Precip B Lighting
Any water buildup underneath the Trfr (Report to LCO & Unit SS)
Any oil leaks evident on and around the Trfr. (Defect if any)
Trfr oil level Normal (Defect if below 0,3 (30%))
Trfr Oil temperatures normal. (Report High Temperatures to LCO)
Trfr Winding temperatures normal, use thermal gun on dry Trfr’s. (Report High Temperatures to LCO)
Trfr Fan in working condition. (Defect if Not)
Trfr Fan control cubicle indication lights working? (Replace blown bulbs)
Lights in the Trfr area in working condition. (Defect if Not (Outage defect for dry Trfr.))
Any water or steam leaks evident into the Trfr area. (Report leaks to LCO & SM A.S.A.P.)
Excessive dust build-up on the Dry Trfr? (Outage Defect if Not)
Housekeeping in order around the Trfr. (Defect if Not)
Trfr gate closed and locked. (Replace any broken locks A.S.A.P.)
When downloaded from the document management system, this document is uncontrolled and the responsibility rests with the user to ensure it is in line with the authorised
version on the system.
No part of this document may be reproduced without the expressed consent of the copyright holder, Eskom Holdings SOC Ltd, Reg No 2002/015527/30.
Template Rev 5
240-43921804
MATLA POWER STATION Identifier
Document Rev 2
15738
Electrical Operating Desk Identifier
Plant Inspection Effective Date 21 August 2017
Review Date August 2020
11kV 11kV 11kV A B Loop 3,3kV 3,3kV 3,3kV 3,3kV 400V 400V 400V
Unit 5 MV Switchgear room (Indicate Y for Yes & N for No)
MIB MIB MIB Lighting
A B C A B C D C D
Each board Live from normal supply? (If not investigate and report)
Any Fault alarms sustained on any of breakers (Report to LCO and defect if any)
All breaker indication lamps still in working condition? (Replace if not)
All breakers IED screens still in working condition? (Report to LCO and defect if any)
Normal supply breakers to relative boards closed? E.g. Supply to N closed from C (If
not investigate)
Remote blocks in position and without defect on all supply & incoming breakers
Bus Zone Protection panel Test blocks in position and without defect (If not Report &
Defect)
All breaker panels and doors closed and without defect (If not Report & defect)
Are the Lights in the switchgear room all in working condition? (Defect if Not)
Loop Supply breaker Closed? (If not follow up) Yes No Description if no:
Are both access doors closed and locked? (Defect any damage to doors & locks) Yes No Description if no:
Housekeeping, fire extinguishers & diagrams in order. (Defect if Not) Yes No Description if no:
D. D. N P SO3
Unit 5 LV Switchgear room & 400V boards (Indicate Y for Yes & N for No) A B
Gen A Gen B
Each 400V board Live from its normal supply? (If not investigate and report to LCO ASAP)
All 400V breaker keys switched on i.e. s/by (If not investigate and rectify)
All breaker indication lamps still in working condition? (Replace if not)
Normal supply breakers to relative boards closed? E.g. Supply to D.Gen A closed from A (If
not investigate)
Transfer switched on all relevant board (If not follow up)
All breaker panels and doors closed and without defect (If not Report & defect)
Are the Lights in the switchgear room all in working condition? (Defect if Not)
Are both access doors closed and locked? (Defect any damage to doors & locks) Yes No
Housekeeping, fire extinguishers & diagrams in order. (Defect if Not) Yes No
When downloaded from the document management system, this document is uncontrolled and the responsibility rests with the user to ensure it is in line with the authorised
version on the system.
No part of this document may be reproduced without the expressed consent of the copyright holder, Eskom Holdings SOC Ltd, Reg No 2002/015527/30.
Template Rev 5
240-43921804
MATLA POWER STATION Identifier
Document Rev 2
15738
Electrical Operating Desk Identifier
Plant Inspection Effective Date 21 August 2017
Review Date August 2020
Unit 5 Service & Dry Transformer bay (Indicate Y for Yes & N for No) A B C D SO3 Precip A Precip B Lighting
Any water buildup underneath the Trfr (Report to LCO & Unit SS)
Any oil leaks evident on and around the Trfr. (Defect if any)
Trfr oil level Normal (Defect if below 0,3 (30%))
Trfr Oil temperatures normal. (Report High Temperatures to LCO)
Trfr Winding temperatures normal, use thermal gun on dry Trfr’s. (Report High Temperatures to LCO)
Trfr Fan in working condition. (Defect if Not)
Trfr Fan control cubicle indication lights working? (Replace blown bulbs)
Lights in the Trfr area in working condition. (Defect if Not (Outage defect for dry Trfr.))
Any water or steam leaks evident into the Trfr area. (Report leaks to LCO & SM A.S.A.P.)
Excessive dust build-up on the Dry Trfr? (Outage Defect if Not)
Housekeeping in order around the Trfr. (Defect if Not)
Trfr gate closed and locked. (Replace any broken locks A.S.A.P.)
When downloaded from the document management system, this document is uncontrolled and the responsibility rests with the user to ensure it is in line with the authorised
version on the system.
No part of this document may be reproduced without the expressed consent of the copyright holder, Eskom Holdings SOC Ltd, Reg No 2002/015527/30.
Template Rev 5
240-43921804
MATLA POWER STATION Identifier
Document Rev 2
15738
Electrical Operating Desk Identifier
Plant Inspection Effective Date 21 August 2017
Review Date August 2020
11kV 11kV 11kV A B Loop 3,3kV 3,3kV 3,3kV 3,3kV 400V 400V 400V
Unit 4 MV Switchgear room (Indicate Y for Yes & N for No)
MIB MIB MIB Lighting
A B C A B C D C D
Each board Live from normal supply? (If not investigate and report)
Any Fault alarms sustained on any of breakers (Report to LCO and defect if any)
All breaker indication lamps still in working condition? (Replace if not)
All breakers IED screens still in working condition? (Report to LCO and defect if any)
Normal supply breakers to relative boards closed? E.g. Supply to N closed from C (If
not investigate)
Remote blocks in position and without defect on all supply & incoming breakers
Bus Zone Protection panel Test blocks in position and without defect (If not Report &
Defect)
All breaker panels and doors closed and without defect (If not Report & defect)
Are the Lights in the switchgear room all in working condition? (Defect if Not)
Loop Supply breaker Closed? (If not follow up) Yes No Description if no:
Are both access doors closed and locked? (Defect any damage to doors & locks) Yes No Description if no:
Housekeeping, fire extinguishers & diagrams in order. (Defect if Not) Yes No Description if no:
D. D. N P SO3
Unit 4 LV Switchgear room & 400V boards (Indicate Y for Yes & N for No) A B
Gen A Gen B
Each 400V board Live from its normal supply? (If not investigate and report to LCO ASAP)
All 400V breaker keys switched on i.e. s/by (If not investigate and rectify)
All breaker indication lamps still in working condition? (Replace if not)
Normal supply breakers to relative boards closed? E.g. Supply to D.Gen A closed from A (If
not investigate)
Transfer switched on all relevant board (If not follow up)
All breaker panels and doors closed and without defect (If not Report & defect)
Are the Lights in the switchgear room all in working condition? (Defect if Not)
Are both access doors closed and locked? (Defect any damage to doors & locks) Yes No
Housekeeping, fire extinguishers & diagrams in order. (Defect if Not) Yes No
When downloaded from the document management system, this document is uncontrolled and the responsibility rests with the user to ensure it is in line with the authorised
version on the system.
No part of this document may be reproduced without the expressed consent of the copyright holder, Eskom Holdings SOC Ltd, Reg No 2002/015527/30.
Template Rev 5
240-43921804
MATLA POWER STATION Identifier
Document Rev 2
15738
Electrical Operating Desk Identifier
Plant Inspection Effective Date 21 August 2017
Review Date August 2020
Unit 4 Service & Dry Transformer bay (Indicate Y for Yes & N for No) A B C D SO3 Precip A Precip B Lighting
Any water buildup underneath the Trfr (Report to LCO & Unit SS)
Any oil leaks evident on and around the Trfr. (Defect if any)
Trfr oil level Normal (Defect if below 0,3 (30%))
Trfr Oil temperatures normal. (Report High Temperatures to LCO)
Trfr Winding temperatures normal, use thermal gun on dry Trfr’s. (Report High Temperatures to LCO)
Trfr Fan in working condition. (Defect if Not)
Trfr Fan control cubicle indication lights working? (Replace blown bulbs)
Lights in the Trfr area in working condition. (Defect if Not (Outage defect for dry Trfr.))
Any water or steam leaks evident into the Trfr area. (Report leaks to LCO & SM A.S.A.P.)
Excessive dust build-up on the Dry Trfr? (Outage Defect if Not)
Housekeeping in order around the Trfr. (Defect if Not)
Trfr gate closed and locked. (Replace any broken locks A.S.A.P.)
When downloaded from the document management system, this document is uncontrolled and the responsibility rests with the user to ensure it is in line with the authorised
version on the system.
No part of this document may be reproduced without the expressed consent of the copyright holder, Eskom Holdings SOC Ltd, Reg No 2002/015527/30.
Template Rev 5
240-43921804
MATLA POWER STATION Identifier
Document Rev 2
15738
Electrical Operating Desk Identifier
Plant Inspection Effective Date 21 August 2017
Review Date August 2020
Assistant shift
Supervisor:
Name: Signature: Date: Time:
Local Control
Officer:
Name: Signature: Date: Time:
When downloaded from the document management system, this document is uncontrolled and the responsibility rests with
the user to ensure it is in line with the authorised version on the system.
No part of this document may be reproduced without the expressed consent of the copyright holder, Eskom Holdings SOC
Ltd, Reg No 2002/015527/30.
Template Rev 5
240-43921804
MATLA POWER STATION Identifier
Document Rev 2
15738
Electrical Operating Desk Identifier
Plant Inspection Effective Date 21 August 2017
Review Date August 2020
380V
11kV 11kV 11kV 3,3kV 3,3kV 3,3kV 3,3kV 380V 380V 380V
Unit 1 MV Switchgear room (Indicate Y for Yes & N for No)
Lighting
Essen.
A B C A B C D C D Lighting
Each board Live from normal supply? (If not investigate and report)
Any relays operated on any of the breakers (Report to LCO and Ptm)
Any Fault alarms sustained on alarm panel (Conlog) (Follow up and report to LCO)
All breaker indication lamps still in working condition? (Replace if not)
Normal supply breakers to relative boards closed? E.g. Supply to N closed from C
(If not investigate)
Remote blocks in position and without defect on all supply & incoming breakers
Bus Zone Protection panel Test blocks in position and without defect (If not
Report & Defect)
All breaker panels and doors closed and without defect (If not Report & defect)
Are the Lights in the switchgear room all in working condition? (Defect if Not)
Loop Supply breaker Closed? (If not follow up) Yes No Description if no:
Are both access doors closed and locked? (Defect any damage to doors & locks) Yes No Description if no:
Housekeeping, fire extinguishers & diagrams in order. (Defect if Not) Yes No Description if no:
When downloaded from the document management system, this document is uncontrolled and the responsibility rests with the user to ensure it is in line with the authorised
version on the system.
No part of this document may be reproduced without the expressed consent of the copyright holder, Eskom Holdings SOC Ltd, Reg No 2002/015527/30.
Template Rev 5
240-43921804
MATLA POWER STATION Identifier
Document Rev 2
15738
Electrical Operating Desk Identifier
Plant Inspection Effective Date 21 August 2017
Review Date August 2020
Unit 2 Service & Dry Transformer bay (Indicate Y for Yes & N for No) A B C D SO3 Precip A Precip B Lighting
Any water buildup underneath the Trfr (Report to LCO & Unit SS)
Any oil leaks evident on and around the Trfr. (Defect if any)
Trfr oil level Normal (Defect if below 0,3 (30%))
Trfr Oil temperatures normal. (Report High Temperatures to LCO)
Trfr Winding temperatures normal, use thermal gun on dry Trfr’s. (Report High Temperatures to LCO)
Trfr Fan in working condition. (Defect if Not)
Trfr Fan control cubicle indication lights working? (Replace blown bulbs)
Lights in the Trfr area in working condition. (Defect if Not (Outage defect for dry Trfr.))
Any water or steam leaks evident into the Trfr area. (Report leaks to LCO & SM A.S.A.P.)
Excessive dust build-up on the Dry Trfr? (Outage Defect if Not)
Housekeeping in order around the Trfr. (Defect if Not)
Trfr gate closed and locked. (Replace any broken locks A.S.A.P.)
11kV 11kV 11kV A B Loop 3,3kV 3,3kV 3,3kV 3,3kV 400V 400V 400V
Unit 2 MV Switchgear room (Indicate Y for Yes & N for No)
MIB MIB MIB Lighting
A B C A B C D C D
Each board Live from normal supply? (If not investigate and report)
Any Fault alarms sustained on any of breakers (Report to LCO and defect if any)
All breaker indication lamps still in working condition? (Replace if not)
All breakers IED screens still in working condition? (Report to LCO and defect if any)
Normal supply breakers to relative boards closed? E.g. Supply to N closed from C (If
not investigate)
Remote blocks in position and without defect on all supply & incoming breakers
Bus Zone Protection panel Test blocks in position and without defect (If not Report &
Defect)
All breaker panels and doors closed and without defect (If not Report & defect)
Are the Lights in the switchgear room all in working condition? (Defect if Not)
Loop Supply breaker Closed? (If not follow up) Yes No Description if no:
Are both access doors closed and locked? (Defect any damage to doors & locks) Yes No Description if no:
Housekeeping, fire extinguishers & diagrams in order. (Defect if Not) Yes No Description if no:
When downloaded from the document management system, this document is uncontrolled and the responsibility rests with the user to ensure it is in line with the authorised
version on the system.
No part of this document may be reproduced without the expressed consent of the copyright holder, Eskom Holdings SOC Ltd, Reg No 2002/015527/30.
Template Rev 5
240-43921804
MATLA POWER STATION Identifier
Document Rev 2
15738
Electrical Operating Desk Identifier
Plant Inspection Effective Date 21 August 2017
Review Date August 2020
Unit 3 Service & Dry Transformer bay (Indicate Y for Yes & N for No) A B C D SO3 Precip A Precip B Lighting
Any water buildup underneath the Trfr (Report to LCO & Unit SS)
Any oil leaks evident on and around the Trfr. (Defect if any)
Trfr oil level Normal (Defect if below 0,3 (30%))
Trfr Oil temperatures normal. (Report High Temperatures to LCO)
Trfr Winding temperatures normal, use thermal gun on dry Trfr’s. (Report High Temperatures to LCO)
Trfr Fan in working condition. (Defect if Not)
Trfr Fan control cubicle indication lights working? (Replace blown bulbs)
Lights in the Trfr area in working condition. (Defect if Not (Outage defect for dry Trfr.))
Any water or steam leaks evident into the Trfr area. (Report leaks to LCO & SM A.S.A.P.)
Excessive dust build-up on the Dry Trfr? (Outage Defect if Not)
Housekeeping in order around the Trfr. (Defect if Not)
Trfr gate closed and locked. (Replace any broken locks A.S.A.P.)
11kV 11kV 11kV A B Loop 3,3kV 3,3kV 3,3kV 3,3kV 400V 400V 400V
Unit 3 MV Switchgear room (Indicate Y for Yes & N for No)
MIB MIB MIB Lighting
A B C A B C D C D
Each board Live from normal supply? (If not investigate and report)
Any Fault alarms sustained on any of breakers (Report to LCO and defect if any)
All breaker indication lamps still in working condition? (Replace if not)
All breakers IED screens still in working condition? (Report to LCO and defect if any)
Normal supply breakers to relative boards closed? E.g. Supply to N closed from C (If
not investigate)
Remote blocks in position and without defect on all supply & incoming breakers
Bus Zone Protection panel Test blocks in position and without defect (If not Report &
Defect)
All breaker panels and doors closed and without defect (If not Report & defect)
Are the Lights in the switchgear room all in working condition? (Defect if Not)
Loop Supply breaker Closed? (If not follow up) Yes No Description if no:
Are both access doors closed and locked? (Defect any damage to doors & locks) Yes No Description if no:
Housekeeping, fire extinguishers & diagrams in order. (Defect if Not) Yes No Description if no:
When downloaded from the document management system, this document is uncontrolled and the responsibility rests with the user to ensure it is in line with the authorised
version on the system.
No part of this document may be reproduced without the expressed consent of the copyright holder, Eskom Holdings SOC Ltd, Reg No 2002/015527/30.
Template Rev 5
240-43921804
MATLA POWER STATION Identifier
Document Rev 2
15738
Electrical Operating Desk Identifier
Plant Inspection Effective Date 21 August 2017
Review Date August 2020
Assistant shift
Supervisor:
Name: Signature: Date: Time:
Local Control
Officer:
Name: Signature: Date: Time:
When downloaded from the document management system, this document is uncontrolled and the responsibility
rests with the user to ensure it is in line with the authorised version on the system.
No part of this document may be reproduced without the expressed consent of the copyright holder, Eskom
Holdings SOC Ltd, Reg No 2002/015527/30.
Template Rev 5
240-43921804
MATLA POWER STATION Identifier
Document Rev 2
15738
Electrical Operating Desk Identifier
Plant Inspection Effective Date 21 August 2017
Review Date August 2020
11kV 11kV 11kV A B Loop 3,3kV 3,3kV 3,3kV 3,3kV 400V 400V 400V
Unit 4 MV Switchgear room (Indicate Y for Yes & N for No)
MIB MIB MIB Lighting
A B C A B C D C D
Each board Live from normal supply? (If not investigate and report)
Any Fault alarms sustained on any of breakers (Report to LCO and defect if any)
All breaker indication lamps still in working condition? (Replace if not)
All breakers IED screens still in working condition? (Report to LCO and defect if any)
Normal supply breakers to relative boards closed? E.g. Supply to N closed from C (If
not investigate)
Remote blocks in position and without defect on all supply & incoming breakers
Bus Zone Protection panel Test blocks in position and without defect (If not Report &
Defect)
All breaker panels and doors closed and without defect (If not Report & defect)
Are the Lights in the switchgear room all in working condition? (Defect if Not)
Loop Supply breaker Closed? (If not follow up) Yes No Description if no:
Are both access doors closed and locked? (Defect any damage to doors & locks) Yes No Description if no:
Housekeeping, fire extinguishers & diagrams in order. (Defect if Not) Yes No Description if no:
When downloaded from the document management system, this document is uncontrolled and the responsibility rests with the user to ensure it is in line with the authorised
version on the system.
No part of this document may be reproduced without the expressed consent of the copyright holder, Eskom Holdings SOC Ltd, Reg No 2002/015527/30.
Template Rev 5
240-43921804
MATLA POWER STATION Identifier
Document Rev 2
15738
Electrical Operating Desk Identifier
Plant Inspection Effective Date 21 August 2017
Review Date August 2020
Unit 5 Service & Dry Transformer bay (Indicate Y for Yes & N for No) A B C D SO3 Precip A Precip B Lighting
Any water buildup underneath the Trfr (Report to LCO & Unit SS)
Any oil leaks evident on and around the Trfr. (Defect if any)
Trfr oil level Normal (Defect if below 0,3 (30%))
Trfr Oil temperatures normal. (Report High Temperatures to LCO)
Trfr Winding temperatures normal, use thermal gun on dry Trfr’s. (Report High Temperatures to LCO)
Trfr Fan in working condition. (Defect if Not)
Trfr Fan control cubicle indication lights working? (Replace blown bulbs)
Lights in the Trfr area in working condition. (Defect if Not (Outage defect for dry Trfr.))
Any water or steam leaks evident into the Trfr area. (Report leaks to LCO & SM A.S.A.P.)
Excessive dust build-up on the Dry Trfr? (Outage Defect if Not)
Housekeeping in order around the Trfr. (Defect if Not)
Trfr gate closed and locked. (Replace any broken locks A.S.A.P.)
Unit 5 MV Switchgear room (Indicate Y for Yes & 11kV 11kV 11kV A B Loop 3,3kV 3,3kV 3,3kV 3,3kV 400V 400V 400V
N for No) A B C MIB MIB MIB A B C D C D Lighting
Each board Live from normal supply? (If not investigate and report)
Any Fault alarms sustained on any of breakers (Report to LCO and defect if any)
All breaker indication lamps still in working condition? (Replace if not)
All breakers IED screens still in working condition? (Report to LCO and defect if any)
Normal supply breakers to relative boards closed? E.g. Supply to N closed from C (If
not investigate)
Remote blocks in position and without defect on all supply & incoming breakers
Bus Zone Protection panel Test blocks in position and without defect (If not Report &
Defect)
All breaker panels and doors closed and without defect (If not Report & defect)
Are the Lights in the switchgear room all in working condition? (Defect if Not)
Loop Supply breaker Closed? (If not follow up) Yes No Description if no:
Are both access doors closed and locked? (Defect any damage to doors & locks) Yes No Description if no:
Housekeeping, fire extinguishers & diagrams in order. (Defect if Not) Yes No Description if no:
When downloaded from the document management system, this document is uncontrolled and the responsibility rests with the user to ensure it is in line with the authorised
version on the system.
No part of this document may be reproduced without the expressed consent of the copyright holder, Eskom Holdings SOC Ltd, Reg No 2002/015527/30.
Template Rev 5
240-43921804
MATLA POWER STATION Identifier
Document Rev 2
15738
Electrical Operating Desk Identifier
Plant Inspection Effective Date 21 August 2017
Review Date August 2020
Unit 6 Service & Dry Transformer bay (Indicate Y for Yes & N for No) A B C D SO3 Precip A Precip B Lighting
Any water buildup underneath the Trfr (Report to LCO & Unit SS)
Any oil leaks evident on and around the Trfr. (Defect if any)
Trfr oil level Normal (Defect if below 0,3 (30%))
Trfr Oil temperatures normal. (Report High Temperatures to LCO)
Trfr Winding temperatures normal, use thermal gun on dry Trfr’s. (Report High Temperatures to LCO)
Trfr Fan in working condition. (Defect if Not)
Trfr Fan control cubicle indication lights working? (Replace blown bulbs)
Lights in the Trfr area in working condition. (Defect if Not (Outage defect for dry Trfr.))
Any water or steam leaks evident into the Trfr area. (Report leaks to LCO & SM A.S.A.P.)
Excessive dust build-up on the Dry Trfr? (Outage Defect if Not)
Housekeeping in order around the Trfr. (Defect if Not)
Trfr gate closed and locked. (Replace any broken locks A.S.A.P.)
11kV 11kV 11kV A B Loop 3,3kV 3,3kV 3,3kV 3,3kV 400V 400V 400V
Unit 6 MV Switchgear room (Indicate Y for Yes & N for No)
MIB MIB MIB Lighting
A B C A B C D C D
Each board Live from normal supply? (If not investigate and report)
Any Fault alarms sustained on any of breakers (Report to LCO and defect if any)
All breaker indication lamps still in working condition? (Replace if not)
All breakers IED screens still in working condition? (Report to LCO and defect if any)
Normal supply breakers to relative boards closed? E.g. Supply to N closed from C (If
not investigate)
Remote blocks in position and without defect on all supply & incoming breakers
Bus Zone Protection panel Test blocks in position and without defect (If not Report &
Defect)
All breaker panels and doors closed and without defect (If not Report & defect)
Are the Lights in the switchgear room all in working condition? (Defect if Not)
Loop Supply breaker Closed? (If not follow up) Yes No Description if no:
Are both access doors closed and locked? (Defect any damage to doors & locks) Yes No Description if no:
Housekeeping, fire extinguishers & diagrams in order. (Defect if Not) Yes No Description if no:
When downloaded from the document management system, this document is uncontrolled and the responsibility rests with the user to ensure it is in line with the authorised
version on the system.
No part of this document may be reproduced without the expressed consent of the copyright holder, Eskom Holdings SOC Ltd, Reg No 2002/015527/30.
Template Rev 5
240-43921804
MATLA POWER STATION Identifier
Document Rev 2
15738
Electrical Operating Desk Identifier
Plant Inspection Effective Date 21 August 2017
Review Date August 2020
Ash plant boards & transformers. (Indicate Y for Yes & N for No) A B
11kV Ash plant board live from normal supply and the bus section breaker open? (If not follow up)
3,3kV Ash plant board live from normal supply and the bus section breaker open? (If not follow up)
380V Ash plant board live from normal supply and the bus section breaker open? (If not follow up)
All breaker panels and doors closed and without defect (If not Report & defect)
Remote blocks in position and without defect on all supply & incoming breakers
Bus Zone Protection panel Test blocks in position and without defect (If not Report & Defect)
Any Fault alarms sustained on alarm panel (Conlog) (Follow up and report to LCO)
Are the Lights in the Sub Station all in working condition? (Defect if Not)
Housekeeping, fire extinguishers & diagrams in order. (Defect if Not)
Are both access doors closed and locked? (Defect any damage to doors & locks).
3,3kV Ash Plant Trfr oil level, Silica Gel & Oil breather level Normal (Defect if below 0,3 (30%), pink & low oil)
380V Ash Plant Trfr oil level, Silica Gel & Oil breather level Normal (Defect if below 0,3 (30%), pink & low oil)
All Trfr gates closed and locked. (Replace any broken locks A.S.A.P.)
When downloaded from the document management system, this document is uncontrolled and the responsibility
rests with the user to ensure it is in line with the authorised version on the system.
No part of this document may be reproduced without the expressed consent of the copyright holder, Eskom Holdings
SOC Ltd, Reg No 2002/015527/30.
Template Rev 5
240-43921804
MATLA POWER STATION Identifier
Document Rev 2
15738
Electrical Operating Desk Identifier
Plant Inspection Effective Date 21 August 2017
Review Date August 2020
WTP North 11/0,4kV Transformers (Indicate Y for Yes & N for No) A B
Any water buildup in the Trfr bund area (Defect if any)
Any oil leaks evident on and/or around the Trfr. (Defect if any)
Trfr oil level Normal (Defect if below 0,3 (30%))
Trfr Oil temperatures normal. (Report High Temperatures to LCO)
Trfr Winding temperatures normal (Report High Temperatures to LCO)
Oil sampling valves locked. (Defect if no locking mechanism & replace broken locks)
Housekeeping in order around the Trfr. (Defect if Not)
Overland conveyor Sub Station 1 & transformers. (Indicate Y for Yes & N for No) A B
11kV Overland conveyor brd. live from normal supply and the bus section breaker open? (If not follow up)
3,3kV Overland conv. brd. 1 live from normal supply and the bus section breaker open? (If not follow up)
380V Overland conv. brd. 1 live from normal supply and the bus section breaker open? (If not follow up)
All breaker panels and doors closed and without defect (If not Report & defect)
Remote blocks in position and without defect on all supply & incoming breakers
Bus Zone Protection panel Test blocks in position and without defect (If not Report & Defect)
Any Fault alarms sustained on alarm panel (Conlog) (Follow up and report to LCO)
Are the Lights in the Sub Station all in working condition? (Defect if Not)
Housekeeping, fire extinguishers & diagrams in order. (Defect if Not)
Are both access doors closed and locked? (Defect any damage to doors & locks).
3,3kV Overland conv. Trfr 1 oil level, Silica Gel & Oil breather level Normal (Defect if below 0,3 (30%), pink & low oil)
380V Overland conv. Trfr 1 oil level, Silica Gel & Oil breather level Normal (Defect if below 0,3 (30%), pink & low oil)
Overland conveyor Sub Station 2 & transformers. (Indicate Y for Yes & N for No) A B
3,3kV Overland conv. brd. 2 live from normal supply and the bus section breaker open? (If not follow up)
380V Overland conv. brd. 2 live from normal supply and the bus section breaker open? (If not follow up)
All breaker panels and doors closed and without defect (If not Report & defect)
Remote blocks in position and without defect on all supply & incoming breakers
Any Fault alarms sustained on alarm panel (Conlog) (Follow up and report to LCO)
Are the Lights in the Sub Station all in working condition? (Defect if Not)
Housekeeping, fire extinguishers & diagrams in order. (Defect if Not)
Are both access doors closed and locked? (Defect any damage to doors & locks).
3,3kV Overland conv. Trfr 2 oil level, Silica Gel & Oil breather level Normal (Defect if below 0,3 (30%), pink & low oil)
380V Overland conv. Trfr 2 oil level, Silica Gel & Oil breather level Normal (Defect if below 0,3 (30%), pink & low oil)
Overland conveyor Sub Station 3 & transformers. (Indicate Y for Yes & N for No) A B
380V Overland conv. brd. 3 live from normal supply and the bus section breaker open? (If not follow up)
All breaker panels and doors closed and without defect (If not Report & defect)
Are the Lights in the Sub Station all in working condition? (Defect if Not)
Housekeeping, fire extinguishers & diagrams in order. (Defect if Not)
Are both access doors closed and locked? (Defect any damage to doors & locks).
380V Overland conv. Trfr 3 oil level, Silica Gel & Oil breather level Normal (Defect if below 0,3 (30%), pink & low oil)
When downloaded from the document management system, this document is uncontrolled and the responsibility
rests with the user to ensure it is in line with the authorised version on the system.
No part of this document may be reproduced without the expressed consent of the copyright holder, Eskom Holdings
SOC Ltd, Reg No 2002/015527/30.
Template Rev 5
240-43921804
MATLA POWER STATION Identifier
Document Rev 2
15738
Electrical Operating Desk Identifier
Plant Inspection Effective Date 21 August 2017
Review Date August 2020
Assistant shift
Supervisor:
Name: Signature: Date: Time:
Local Control
Officer:
Name: Signature: Date: Time:
When downloaded from the document management system, this document is uncontrolled and the responsibility
rests with the user to ensure it is in line with the authorised version on the system.
No part of this document may be reproduced without the expressed consent of the copyright holder, Eskom Holdings
SOC Ltd, Reg No 2002/015527/30.
Template Rev 5
240-43921804
MATLA POWER STATION Identifier
Document Rev 2
15738
Electrical Operating Desk Identifier
Plant Inspection Effective Date 21 August 2017
Review Date August 2020
Unit 1 to 3 Unit 4 to 6
Unit 1 to 6 Gen 20kV breaker and air system Unit 1 Unit 2 Unit 3 Unit 4 Unit 5 Unit 6
Compressors Compressors
(Indicate Y for Yes & N for No for the compressors)
Y N Y N Y N Y N Y N Y N A B A B
Any alarms sustained on the alarm panels (Conlogs) (follow up if any)
Any oil leaks around the compressors? (Defect if any)
Compressor oil levels above the minimum required level mark? Defect if not)
Which compressor is running (Mark A or B) if both follow up why (leaks?)
Check that no motor protections operated on S/by compressor & mark S/by
Any air leaks detected on the running compressor PRV (Defect if any)
Compressor catch pod oil & water drained (Indicate Y or N)
Any air leaks on any of the valves at 9,5meter level (defect if any)
Any air leaks detected from the receivers down to the breaker (Defect if any)
Water drained from the 20MPa & 15MPa air receivers.
Any water leaks detected on the demin tank (Defect if any)
Demin cooling water tank above 80% (Top up if not)
20kV Breaker earth switch motors locked in off position on all three phases?
Indicate A or B for running 20kV breaker vent fan.
Indicate A or B for running 20kV breaker cooling water pump.
Any water leaks on “A” 20kV breaker cooling water pump (Defect if any).
Any water leaks on “B” 20kV breaker cooling water pump (Defect if any).
Any water leaks on the cooling system (Demin or CW) defect if any.
Any air leaks below the 20kV breaker? (Defect if any)
Any air leaks inside the 20kV breaker cubicle? (Defect if any)
20kV Breaker switched to remote and cubicle locked?
Record the 20kV breaker low pressure (3 MPa gauge) MPa MPa MPa MPa MPa MPa
Record the 20kV breaker high pressure (15 MPa gauge) MPa MPa MPa MPa MPa MPa
When downloaded from the document management system, this document is uncontrolled and the responsibility rests with the user to ensure it is in line with the authorised
version on the system.
No part of this document may be reproduced without the expressed consent of the copyright holder, Eskom Holdings SOC Ltd, Reg No 2002/015527/30.
Template Rev 5
240-43921804
MATLA POWER STATION Identifier
Document Rev 2
15738
Electrical Operating Desk Identifier
Plant Inspection Effective Date 21 August 2017
Review Date August 2020
Precip Sub Station 6A & 6B (Indicate Y for Yes & N for No) A B
400V Precip board 6 live from normal supply? (If not follow up)
All breaker panels and doors closed and without defect (If not Report & defect)
Any Fault alarms sustained on the breaker IED (Follow up and report to LCO)
Are the Lights in the Sub Station all in working condition? (Defect if Not)
Are the air cons running inside the Sub Station? (Defect if Not)
Housekeeping, fire extinguishers & diagrams in order. (Defect if Not)
Are both access doors closed and locked? (Defect any damage to doors & locks).
Incline Sub Station 3A & 3B boards & Transformers (Indicate Y for Yes & N for No) A B
380V Incline board 3 live from normal supply & bus section open? (If not follow up)
All board panels and doors closed and without defect (If not Report & defect)
Are the Lights in the Sub Station all in working condition? (Defect if Not)
Are the air cons running inside the Sub Station? (Defect if Not)
Housekeeping, fire extinguishers & diagrams in order. (Defect if Not)
Are both access doors closed and locked? (Defect any damage to doors & locks).
380V Incline Trfr 3 oil level, Silica Gel & Oil breather level Normal (Defect if below 0,3 (30%), pink & low oil)
Any oil leaks evident on and/or around the 380V Incline Trfr 3. (Defect if any)
Any water or ash buildup in the Trfr bund area (Defect if any)
Precip Sub Station 5A & 5B (Indicate Y for Yes & N for No) A B
400V Precip board 5 live from normal supply? (If not follow up)
All breaker panels and doors closed and without defect (If not Report & defect)
Any Fault alarms sustained on the breaker IED (Follow up and report to LCO)
Are the Lights in the Sub Station all in working condition? (Defect if Not)
Are the air cons running inside the Sub Station? (Defect if Not)
Housekeeping, fire extinguishers & diagrams in order. (Defect if Not)
Are both access doors closed and locked? (Defect any damage to doors & locks).
Precip Sub Station 4A & 4B (Indicate Y for Yes & N for No) A B
380V Precip board 4 live from normal supply? (If not follow up)
All breaker panels and doors closed and without defect (If not Report & defect)
Are the Lights in the Sub Station all in working condition? (Defect if Not)
Are the air cons running inside the Sub Station? (Defect if Not)
Housekeeping, fire extinguishers & diagrams in order. (Defect if Not)
Are both access doors closed and locked? (Defect any damage to doors & locks).
Incline Sub Station 2A & 2B boards & Transformers (Indicate Y for Yes & N for No) A B
380V Incline board 2 live from normal supply & bus section open? (If not follow up)
All board panels and doors closed and without defect (If not Report & defect)
Are the Lights in the Sub Station all in working condition? (Defect if Not)
Are the air cons running inside the Sub Station? (Defect if Not)
Housekeeping, fire extinguishers & diagrams in order. (Defect if Not)
Are both access doors closed and locked? (Defect any damage to doors & locks).
380V Incline Trfr 2 oil level, Silica Gel & Oil breather level Normal (Defect if below 0,3 (30%), pink & low oil)
Any oil leaks evident on and/or around the 380V Incline Trfr 2. (Defect if any)
Any water or ash buildup in the Trfr bund area (Defect if any)
When downloaded from the document management system, this document is uncontrolled and the responsibility
rests with the user to ensure it is in line with the authorised version on the system.
No part of this document may be reproduced without the expressed consent of the copyright holder, Eskom Holdings
SOC Ltd, Reg No 2002/015527/30.
Template Rev 5
240-43921804
MATLA POWER STATION Identifier
Document Rev 2
15738
Electrical Operating Desk Identifier
Plant Inspection Effective Date 21 August 2017
Review Date August 2020
Precip Sub Station 3A & 3B (Indicate Y for Yes & N for No) A B
400V Precip board 3 live from normal supply? (If not follow up)
All breaker panels and doors closed and without defect (If not Report & defect)
Any Fault alarms sustained on the breaker IED (Follow up and report to LCO)
Are the Lights in the Sub Station all in working condition? (Defect if Not)
Are the air cons running inside the Sub Station? (Defect if Not)
Housekeeping, fire extinguishers & diagrams in order. (Defect if Not)
Are both access doors closed and locked? (Defect any damage to doors & locks).
Precip Sub Station 2A & 2B (Indicate Y for Yes & N for No) A B
400V Precip board 2 live from normal supply? (If not follow up)
All breaker panels and doors closed and without defect (If not Report & defect)
Any Fault alarms sustained on the breaker IED (Follow up and report to LCO)
Are the Lights in the Sub Station all in working condition? (Defect if Not)
Are the air cons running inside the Sub Station? (Defect if Not)
Housekeeping, fire extinguishers & diagrams in order. (Defect if Not)
Are both access doors closed and locked? (Defect any damage to doors & locks).
Incline Sub Station 1A & 1B boards & Transformers (Indicate Y for Yes & N for No) A B
400V Incline board 1 live from normal supply & bus section breaker open? (If not follow up)
All board panels and doors closed and without defect (If not Report & defect)
Are the Lights in the Sub Station all in working condition? (Defect if Not)
Are the air cons running inside the Sub Station? (Defect if Not)
Housekeeping, fire extinguishers & diagrams in order. (Defect if Not)
Are both access doors closed and locked? (Defect any damage to doors & locks).
400V Incline Trfr 1 oil level, Silica Gel & Oil breather level Normal (Defect if below 0,3 (30%), pink & low oil)
Any oil leaks evident on and/or around the 400V Incline Trfr 1. (Defect if any)
Any water or ash buildup in the Trfr bund area (Defect if any)
Precip Sub Station 1A & 1B (Indicate Y for Yes & N for No) A B
380V Precip board 1 live from normal supply? (If not follow up)
All breaker panels and doors closed and without defect (If not Report & defect)
Are the Lights in the Sub Station all in working condition? (Defect if Not)
Are the air cons running inside the Sub Station? (Defect if Not)
Housekeeping, fire extinguishers & diagrams in order. (Defect if Not)
Are both access doors closed and locked? (Defect any damage to doors & locks).
Notes:
______________________________________________________________________________
______________________________________________________________________________
______________________________________________________________________________
______________________________________________________________________________
When downloaded from the document management system, this document is uncontrolled and the responsibility
rests with the user to ensure it is in line with the authorised version on the system.
No part of this document may be reproduced without the expressed consent of the copyright holder, Eskom Holdings
SOC Ltd, Reg No 2002/015527/30.
Template Rev 5
240-43921804
MATLA POWER STATION Identifier
Document Rev 2
15738
Electrical Operating Desk Identifier
Plant Inspection Effective Date 21 August 2017
Review Date August 2020
When downloaded from the document management system, this document is uncontrolled and the responsibility
rests with the user to ensure it is in line with the authorised version on the system.
No part of this document may be reproduced without the expressed consent of the copyright holder, Eskom Holdings
SOC Ltd, Reg No 2002/015527/30.
Template Rev 5
240-43921804
MATLA POWER STATION Identifier
Document Rev 2
15738
Electrical Operating Desk Identifier
Plant Inspection Effective Date 21 August 2017
Review Date August 2020
Assistant shift
Supervisor:
Name: Signature: Date: Time:
Local Control
Officer:
Name: Signature: Date: Time:
When downloaded from the document management system, this document is uncontrolled and the responsibility
rests with the user to ensure it is in line with the authorised version on the system.
No part of this document may be reproduced without the expressed consent of the copyright holder, Eskom Holdings
SOC Ltd, Reg No 2002/015527/30.
Template Rev 5
240-43921804
MATLA POWER STATION Identifier
Document Rev 2
15738
Electrical Operating Desk Identifier
Plant Inspection Effective Date 21 August 2017
Review Date August 2020
11kV 11kV 11kV A B Loop 3,3kV 3,3kV 3,3kV 3,3kV 400V 400V 400V
Unit 4 MV Switchgear room (Indicate Y for Yes & N for No)
MIB MIB MIB Lighting
A B C A B C D C D
Each board Live from normal supply? (If not investigate and report)
Any Fault alarms sustained on any of breakers (Report to LCO and defect if any)
All breaker indication lamps still in working condition? (Replace if not)
All breakers IED screens still in working condition? (Report to LCO and defect if any)
Normal supply breakers to relative boards closed? E.g. Supply to N closed from C (If
not investigate)
Remote blocks in position and without defect on all supply & incoming breakers
Bus Zone Protection panel Test blocks in position and without defect (If not Report &
Defect)
All breaker panels and doors closed and without defect (If not Report & defect)
Are the Lights in the switchgear room all in working condition? (Defect if Not)
Loop Supply breaker Closed? (If not follow up) Yes No Description if no:
Are both access doors closed and locked? (Defect any damage to doors & locks) Yes No Description if no:
Housekeeping, fire extinguishers & diagrams in order. (Defect if Not) Yes No Description if no:
When downloaded from the document management system, this document is uncontrolled and the responsibility rests with the user to ensure it is in line with the authorised
version on the system.
No part of this document may be reproduced without the expressed consent of the copyright holder, Eskom Holdings SOC Ltd, Reg No 2002/015527/30.
Template Rev 5
240-43921804
MATLA POWER STATION Identifier
Document Rev 2
15738
Electrical Operating Desk Identifier
Plant Inspection Effective Date 21 August 2017
Review Date August 2020
Unit 5 Service & Dry Transformer bay (Indicate Y for Yes & N for No) A B C D SO3 Precip A Precip B Lighting
Any water buildup underneath the Trfr (Report to LCO & Unit SS)
Any oil leaks evident on and around the Trfr. (Defect if any)
Trfr oil level Normal (Defect if below 0,3 (30%))
Trfr Oil temperatures normal. (Report High Temperatures to LCO)
Trfr Winding temperatures normal, use thermal gun on dry Trfr’s. (Report High Temperatures to LCO)
Trfr Fan in working condition. (Defect if Not)
Trfr Fan control cubicle indication lights working? (Replace blown bulbs)
Lights in the Trfr area in working condition. (Defect if Not (Outage defect for dry Trfr.))
Any water or steam leaks evident into the Trfr area. (Report leaks to LCO & SM A.S.A.P.)
Excessive dust build-up on the Dry Trfr? (Outage Defect if Not)
Housekeeping in order around the Trfr. (Defect if Not)
Trfr gate closed and locked. (Replace any broken locks A.S.A.P.)
Unit 5 MV Switchgear room (Indicate Y for Yes & 11kV 11kV 11kV A B Loop 3,3kV 3,3kV 3,3kV 3,3kV 400V 400V 400V
N for No) A B C MIB MIB MIB A B C D C D Lighting
Each board Live from normal supply? (If not investigate and report)
Any Fault alarms sustained on any of breakers (Report to LCO and defect if any)
All breaker indication lamps still in working condition? (Replace if not)
All breakers IED screens still in working condition? (Report to LCO and defect if any)
Normal supply breakers to relative boards closed? E.g. Supply to N closed from C (If
not investigate)
Remote blocks in position and without defect on all supply & incoming breakers
Bus Zone Protection panel Test blocks in position and without defect (If not Report &
Defect)
All breaker panels and doors closed and without defect (If not Report & defect)
Are the Lights in the switchgear room all in working condition? (Defect if Not)
Loop Supply breaker Closed? (If not follow up) Yes No Description if no:
Are both access doors closed and locked? (Defect any damage to doors & locks) Yes No Description if no:
Housekeeping, fire extinguishers & diagrams in order. (Defect if Not) Yes No Description if no:
When downloaded from the document management system, this document is uncontrolled and the responsibility rests with the user to ensure it is in line with the authorised
version on the system.
No part of this document may be reproduced without the expressed consent of the copyright holder, Eskom Holdings SOC Ltd, Reg No 2002/015527/30.
Template Rev 5
240-43921804
MATLA POWER STATION Identifier
Document Rev 2
15738
Electrical Operating Desk Identifier
Plant Inspection Effective Date 21 August 2017
Review Date August 2020
Unit 6 Service & Dry Transformer bay (Indicate Y for Yes & N for No) A B C D SO3 Precip A Precip B Lighting
Any water buildup underneath the Trfr (Report to LCO & Unit SS)
Any oil leaks evident on and around the Trfr. (Defect if any)
Trfr oil level Normal (Defect if below 0,3 (30%))
Trfr Oil temperatures normal. (Report High Temperatures to LCO)
Trfr Winding temperatures normal, use thermal gun on dry Trfr’s. (Report High Temperatures to LCO)
Trfr Fan in working condition. (Defect if Not)
Trfr Fan control cubicle indication lights working? (Replace blown bulbs)
Lights in the Trfr area in working condition. (Defect if Not (Outage defect for dry Trfr.))
Any water or steam leaks evident into the Trfr area. (Report leaks to LCO & SM A.S.A.P.)
Excessive dust build-up on the Dry Trfr? (Outage Defect if Not)
Housekeeping in order around the Trfr. (Defect if Not)
Trfr gate closed and locked. (Replace any broken locks A.S.A.P.)
11kV 11kV 11kV A B Loop 3,3kV 3,3kV 3,3kV 3,3kV 400V 400V 400V
Unit 6 MV Switchgear room (Indicate Y for Yes & N for No)
MIB MIB MIB Lighting
A B C A B C D C D
Each board Live from normal supply? (If not investigate and report)
Any Fault alarms sustained on any of breakers (Report to LCO and defect if any)
All breaker indication lamps still in working condition? (Replace if not)
All breakers IED screens still in working condition? (Report to LCO and defect if any)
Normal supply breakers to relative boards closed? E.g. Supply to N closed from C (If
not investigate)
Remote blocks in position and without defect on all supply & incoming breakers
Bus Zone Protection panel Test blocks in position and without defect (If not Report &
Defect)
All breaker panels and doors closed and without defect (If not Report & defect)
Are the Lights in the switchgear room all in working condition? (Defect if Not)
Loop Supply breaker Closed? (If not follow up) Yes No Description if no:
Are both access doors closed and locked? (Defect any damage to doors & locks) Yes No Description if no:
Housekeeping, fire extinguishers & diagrams in order. (Defect if Not) Yes No Description if no:
When downloaded from the document management system, this document is uncontrolled and the responsibility rests with the user to ensure it is in line with the authorised
version on the system.
No part of this document may be reproduced without the expressed consent of the copyright holder, Eskom Holdings SOC Ltd, Reg No 2002/015527/30.
Template Rev 5
240-43921804
MATLA POWER STATION Identifier
Document Rev 2
15738
Electrical Operating Desk Identifier
Plant Inspection Effective Date 21 August 2017
Review Date August 2020
Assistant shift
Supervisor:
Name: Signature: Date: Time:
Local Control
Officer:
Name: Signature: Date: Time:
When downloaded from the document management system, this document is uncontrolled and the responsibility
rests with the user to ensure it is in line with the authorised version on the system.
No part of this document may be reproduced without the expressed consent of the copyright holder, Eskom
Holdings SOC Ltd, Reg No 2002/015527/30.
Template Rev 5
240-43921804
MATLA POWER STATION Identifier
Document Rev 2
15738
Electrical Operating Desk Identifier
Plant Inspection Effective Date 21 August 2017
Review Date August 2020
Coal Staith Sub Station 2 & transformers. (Indicate Y for Yes & N for No) A B
3,3kV Coal Staith board 2 live from normal supply and the bus section breaker open? (If not follow up)
380V Coal Staith board 2 live from normal supply and the bus section breaker open? (If not follow up)
All breaker panels and doors closed and without defect (If not Report & defect)
Remote blocks in position and without defect on all supply & incoming breakers
Any Fault alarms sustained on alarm panel (Conlog) (Follow up and report to LCO)
Are the Lights in the Sub Station all in working condition? (Defect if Not)
Housekeeping, fire extinguishers & diagrams in order. (Defect if Not)
Are both access doors closed and locked? (Defect any damage to doors & locks).
3,3kV Coal Staith Trfr 2 oil level, Silica Gel & Oil breather level Normal (Defect if below 0,3 (30%), pink & low oil)
380V Coal Staith Trfr 2 oil level, Silica Gel & Oil breather level Normal (Defect if below 0,3 (30%), pink & low oil)
Coal Staith Sub Station 1 & transformers. (Indicate Y for Yes & N for No) A B
3,3kV Coal Staith board 1 live from normal supply and the bus section breaker open? (If not follow up)
380V Coal Staith board 1 live from normal supply and the bus section breaker open? (If not follow up)
All breaker panels and doors closed and without defect (If not Report & defect)
Remote blocks in position and without defect on all supply & incoming breakers
Any Fault alarms sustained on alarm panel (Conlog) (Follow up and report to LCO)
Are the Lights in the Sub Station all in working condition? (Defect if Not)
Housekeeping, fire extinguishers & diagrams in order. (Defect if Not)
Are both access doors closed and locked? (Defect any damage to doors & locks).
3,3kV Coal Staith Trfr 1 oil level, Silica Gel & Oil breather level Normal (Defect if below 0,3 (30%), pink & low oil)
380V Coal Staith Trfr 1 oil level, Silica Gel & Oil breather level Normal (Defect if below 0,3 (30%), pink & low oil)
When downloaded from the document management system, this document is uncontrolled and the responsibility rests with
the user to ensure it is in line with the authorised version on the system.
No part of this document may be reproduced without the expressed consent of the copyright holder, Eskom Holdings SOC
Ltd, Reg No 2002/015527/30.
Template Rev 5
240-43921804
MATLA POWER STATION Identifier
Document Rev 2
15738
Electrical Operating Desk Identifier
Plant Inspection Effective Date 21 August 2017
Review Date August 2020
When downloaded from the document management system, this document is uncontrolled and the responsibility rests with the user to ensure it is in line with the authorised
version on the system.
No part of this document may be reproduced without the expressed consent of the copyright holder, Eskom Holdings SOC Ltd, Reg No 2002/015527/30.
Template Rev 5
240-43921804
MATLA POWER STATION Identifier
Document Rev 2
15738
Electrical Operating Desk Identifier
Plant Inspection Effective Date 21 August 2017
Review Date August 2020
Assistant shift
Supervisor:
Name: Signature: Date: Time:
Local Control
Officer:
Name: Signature: Date: Time:
When downloaded from the document management system, this document is uncontrolled and the responsibility
rests with the user to ensure it is in line with the authorised version on the system.
No part of this document may be reproduced without the expressed consent of the copyright holder, Eskom Holdings
SOC Ltd, Reg No 2002/015527/30.
Template Rev 5
240-43921804
MATLA POWER STATION Identifier
Document Rev 2
15738
Electrical Operating Desk Identifier
Plant Inspection Effective Date 21 August 2017
Review Date August 2020
Unit 1 to 3 Unit 4 to 6
Unit 1 to 6 Gen 20kV breaker and air system Unit 1 Unit 2 Unit 3 Unit 4 Unit 5 Unit 6
Compressors Compressors
(Indicate Y for Yes & N for No for the compressors)
Y N Y N Y N Y N Y N Y N A B A B
Any alarms sustained on the alarm panels (Conlogs) (follow up if any)
Any oil leaks around the compressors? (Defect if any)
Compressor oil levels above the minimum required level mark? Defect if not)
Which compressor is running (Mark A or B) if both follow up why (leaks?)
Check that no motor protections operated on S/by compressor & mark S/by
Any air leaks detected on the running compressor PRV (Defect if any)
Compressor catch pod oil & water drained (Indicate Y or N)
Any air leaks on any of the valves at 9,5meter level (defect if any)
Any air leaks detected from the receivers down to the breaker (Defect if any)
Water drained from the 20MPa & 15MPa air receivers.
Any water leaks detected on the demin tank (Defect if any)
Demin cooling water tank above 80% (Top up if not)
20kV Breaker earth switch motors locked in off position on all three phases?
Indicate A or B for running 20kV breaker vent fan.
Indicate A or B for running 20kV breaker cooling water pump.
Any water leaks on “A” 20kV breaker cooling water pump (Defect if any).
Any water leaks on “B” 20kV breaker cooling water pump (Defect if any).
Any water leaks on the cooling system (Demin or CW) defect if any.
Any air leaks below the 20kV breaker? (Defect if any)
Any air leaks inside the 20kV breaker cubicle? (Defect if any)
20kV Breaker switched to remote and cubicle locked?
Record the 20kV breaker low pressure (3 MPa gauge) MPa MPa MPa MPa MPa MPa
Record the 20kV breaker high pressure (15 MPa gauge) MPa MPa MPa MPa MPa MPa
When downloaded from the document management system, this document is uncontrolled and the responsibility rests with the user to ensure it is in line with the authorised
version on the system.
No part of this document may be reproduced without the expressed consent of the copyright holder, Eskom Holdings SOC Ltd, Reg No 2002/015527/30.
Template Rev 5
240-43921804
MATLA POWER STATION Identifier
Document Rev 2
15738
Electrical Operating Desk Identifier
Plant Inspection Effective Date 21 August 2017
Review Date August 2020
11kV 11kV 11kV A B Loop 3,3kV 3,3kV 3,3kV 3,3kV 400V 400V 400V
Unit 3 MV Switchgear room (Indicate Y for Yes & N for No)
MIB MIB MIB Lighting
A B C A B C D C D
Each board Live from normal supply? (If not investigate and report)
Any Fault alarms sustained on any of breakers (Report to LCO and defect if any)
All breaker indication lamps still in working condition? (Replace if not)
All breakers IED screens still in working condition? (Report to LCO and defect if any)
Normal supply breakers to relative boards closed? E.g. Supply to N closed from C (If
not investigate)
Remote blocks in position and without defect on all supply & incoming breakers
Bus Zone Protection panel Test blocks in position and without defect (If not Report &
Defect)
All breaker panels and doors closed and without defect (If not Report & defect)
Are the Lights in the switchgear room all in working condition? (Defect if Not)
Loop Supply breaker Closed? (If not follow up) Yes No Description if no:
Are both access doors closed and locked? (Defect any damage to doors & locks) Yes No Description if no:
Housekeeping, fire extinguishers & diagrams in order. (Defect if Not) Yes No Description if no:
D. D. N P SO3
Unit 3 LV Switchgear room & 400V boards (Indicate Y for Yes & N for No) A B
Gen A Gen B
Each 400V board Live from its normal supply? (If not investigate and report to LCO ASAP)
All 400V breaker keys switched on i.e. s/by (If not investigate and rectify)
All breaker indication lamps still in working condition? (Replace if not)
Normal supply breakers to relative boards closed? E.g. Supply to D.Gen A closed from A (If
not investigate)
Transfer switched on all relevant board (If not follow up)
All breaker panels and doors closed and without defect (If not Report & defect)
Are the Lights in the switchgear room all in working condition? (Defect if Not)
Are both access doors closed and locked? (Defect any damage to doors & locks) Yes No
Housekeeping, fire extinguishers & diagrams in order. (Defect if Not) Yes No
When downloaded from the document management system, this document is uncontrolled and the responsibility rests with the user to ensure it is in line with the authorised
version on the system.
No part of this document may be reproduced without the expressed consent of the copyright holder, Eskom Holdings SOC Ltd, Reg No 2002/015527/30.
Template Rev 5
240-43921804
MATLA POWER STATION Identifier
Document Rev 2
15738
Electrical Operating Desk Identifier
Plant Inspection Effective Date 21 August 2017
Review Date August 2020
Unit 3 Service & Dry Transformer bay (Indicate Y for Yes & N for No) A B C D SO3 Precip A Precip B Lighting
Any water buildup underneath the Trfr (Report to LCO & Unit SS)
Any oil leaks evident on and around the Trfr. (Defect if any)
Trfr oil level Normal (Defect if below 0,3 (30%))
Trfr Oil temperatures normal. (Report High Temperatures to LCO)
Trfr Winding temperatures normal, use thermal gun on dry Trfr’s. (Report High Temperatures to LCO)
Trfr Fan in working condition. (Defect if Not)
Trfr Fan control cubicle indication lights working? (Replace blown bulbs)
Lights in the Trfr area in working condition. (Defect if Not (Outage defect for dry Trfr.))
Any water or steam leaks evident into the Trfr area. (Report leaks to LCO & SM A.S.A.P.)
Excessive dust build-up on the Dry Trfr? (Outage Defect if Not)
Housekeeping in order around the Trfr. (Defect if Not)
Trfr gate closed and locked. (Replace any broken locks A.S.A.P.)
When downloaded from the document management system, this document is uncontrolled and the responsibility rests with the user to ensure it is in line with the authorised
version on the system.
No part of this document may be reproduced without the expressed consent of the copyright holder, Eskom Holdings SOC Ltd, Reg No 2002/015527/30.
Template Rev 5
240-43921804
MATLA POWER STATION Identifier
Document Rev 2
15738
Electrical Operating Desk Identifier
Plant Inspection Effective Date 21 August 2017
Review Date August 2020
11kV 11kV 11kV A B Loop 3,3kV 3,3kV 3,3kV 3,3kV 400V 400V 400V
Unit 2 MV Switchgear room (Indicate Y for Yes & N for No)
MIB MIB MIB Lighting
A B C A B C D C D
Each board Live from normal supply? (If not investigate and report)
Any Fault alarms sustained on any of breakers (Report to LCO and defect if any)
All breaker indication lamps still in working condition? (Replace if not)
All breakers IED screens still in working condition? (Report to LCO and defect if any)
Normal supply breakers to relative boards closed? E.g. Supply to N closed from C (If
not investigate)
Remote blocks in position and without defect on all supply & incoming breakers
Bus Zone Protection panel Test blocks in position and without defect (If not Report &
Defect)
All breaker panels and doors closed and without defect (If not Report & defect)
Are the Lights in the switchgear room all in working condition? (Defect if Not)
Loop Supply breaker Closed? (If not follow up) Yes No Description if no:
Are both access doors closed and locked? (Defect any damage to doors & locks) Yes No Description if no:
Housekeeping, fire extinguishers & diagrams in order. (Defect if Not) Yes No Description if no:
D. D. N P SO3
Unit 2 LV Switchgear room & 400V boards (Indicate Y for Yes & N for No) A B
Gen A Gen B
Each 400V board Live from its normal supply? (If not investigate and report to LCO ASAP)
All 400V breaker keys switched on i.e. s/by (If not investigate and rectify)
All breaker indication lamps still in working condition? (Replace if not)
Normal supply breakers to relative boards closed? E.g. Supply to D.Gen A closed from A (If
not investigate)
Transfer switched on all relevant board (If not follow up)
All breaker panels and doors closed and without defect (If not Report & defect)
Are the Lights in the switchgear room all in working condition? (Defect if Not)
Are both access doors closed and locked? (Defect any damage to doors & locks) Yes No
Housekeeping, fire extinguishers & diagrams in order. (Defect if Not) Yes No
When downloaded from the document management system, this document is uncontrolled and the responsibility rests with the user to ensure it is in line with the authorised
version on the system.
No part of this document may be reproduced without the expressed consent of the copyright holder, Eskom Holdings SOC Ltd, Reg No 2002/015527/30.
Template Rev 5
240-43921804
MATLA POWER STATION Identifier
Document Rev 2
15738
Electrical Operating Desk Identifier
Plant Inspection Effective Date 21 August 2017
Review Date August 2020
Unit 2 Service & Dry Transformer bay (Indicate Y for Yes & N for No) A B C D SO3 Precip A Precip B Lighting
Any water buildup underneath the Trfr (Report to LCO & Unit SS)
Any oil leaks evident on and around the Trfr. (Defect if any)
Trfr oil level Normal (Defect if below 0,3 (30%))
Trfr Oil temperatures normal. (Report High Temperatures to LCO)
Trfr Winding temperatures normal, use thermal gun on dry Trfr’s. (Report High Temperatures to LCO)
Trfr Fan in working condition. (Defect if Not)
Trfr Fan control cubicle indication lights working? (Replace blown bulbs)
Lights in the Trfr area in working condition. (Defect if Not (Outage defect for dry Trfr.))
Any water or steam leaks evident into the Trfr area. (Report leaks to LCO & SM A.S.A.P.)
Excessive dust build-up on the Dry Trfr? (Outage Defect if Not)
Housekeeping in order around the Trfr. (Defect if Not)
Trfr gate closed and locked. (Replace any broken locks A.S.A.P.)
When downloaded from the document management system, this document is uncontrolled and the responsibility rests with the user to ensure it is in line with the authorised
version on the system.
No part of this document may be reproduced without the expressed consent of the copyright holder, Eskom Holdings SOC Ltd, Reg No 2002/015527/30.
Template Rev 5
240-43921804
MATLA POWER STATION Identifier
Document Rev 2
15738
Electrical Operating Desk Identifier
Plant Inspection Effective Date 21 August 2017
Review Date August 2020
11kV 11kV 11kV A B Loop 3,3kV 3,3kV 3,3kV 3,3kV 400V 400V 400V
Unit 1 MV Switchgear room (Indicate Y for Yes & N for No)
MIB MIB MIB Lighting
A B C A B C D C D
Each board Live from normal supply? (If not investigate and report)
Any Fault alarms sustained on any of breakers (Report to LCO and defect if any)
All breaker indication lamps still in working condition? (Replace if not)
All breakers IED screens still in working condition? (Report to LCO and defect if any)
Normal supply breakers to relative boards closed? E.g. Supply to N closed from C (If
not investigate)
Remote blocks in position and without defect on all supply & incoming breakers
Bus Zone Protection panel Test blocks in position and without defect (If not Report &
Defect)
All breaker panels and doors closed and without defect (If not Report & defect)
Are the Lights in the switchgear room all in working condition? (Defect if Not)
Loop Supply breaker Closed? (If not follow up) Yes No Description if no:
Are both access doors closed and locked? (Defect any damage to doors & locks) Yes No Description if no:
Housekeeping, fire extinguishers & diagrams in order. (Defect if Not) Yes No Description if no:
D. D. N P SO3
Unit 1 LV Switchgear room & 380V boards (Indicate Y for Yes & N for No) A B
Gen A Gen B
Each 380V board Live from its normal supply? (If not investigate and report to LCO ASAP)
All 380V breaker keys switched on i.e. s/by (If not investigate and rectify)
All breaker indication lamps still in working condition? (Replace if not)
Normal supply breakers to relative boards closed? E.g. Supply to D.Gen closed from A (If
not investigate)
All breaker panels and doors closed and without defect (If not Report & defect)
Are the Lights in the switchgear room all in working condition? (Defect if Not)
Are both access doors closed and locked? (Defect any damage to doors & locks) Yes No
Housekeeping, fire extinguishers & diagrams in order. (Defect if Not) Yes No
When downloaded from the document management system, this document is uncontrolled and the responsibility rests with the user to ensure it is in line with the authorised
version on the system.
No part of this document may be reproduced without the expressed consent of the copyright holder, Eskom Holdings SOC Ltd, Reg No 2002/015527/30.
Template Rev 5
240-43921804
MATLA POWER STATION Identifier
Document Rev 2
15738
Electrical Operating Desk Identifier
Plant Inspection Effective Date 21 August 2017
Review Date August 2020
Unit 1 Service & Dry Transformer bay (Indicate Y for Yes & N for No) A B C D SO3 Precip A Precip B Lighting
Any water buildup underneath the Trfr (Report to LCO & Unit SS)
Any oil leaks evident on and around the Trfr. (Defect if any)
Trfr oil level Normal (Defect if below 0,3 (30%))
Trfr Oil temperatures normal. (Report High Temperatures to LCO)
Trfr Winding temperatures normal, use thermal gun on dry Trfr’s. (Report High Temperatures to LCO)
Trfr Fan in working condition. (Defect if Not)
Trfr Fan control cubicle indication lights working? (Replace blown bulbs)
Lights in the Trfr area in working condition. (Defect if Not (Outage defect for dry Trfr.))
Any water or steam leaks evident into the Trfr area. (Report leaks to LCO & SM A.S.A.P.)
Excessive dust build-up on the Dry Trfr? (Outage Defect if Not)
Housekeeping in order around the Trfr. (Defect if Not)
Trfr gate closed and locked. (Replace any broken locks A.S.A.P.)
When downloaded from the document management system, this document is uncontrolled and the responsibility rests with the user to ensure it is in line with the authorised
version on the system.
No part of this document may be reproduced without the expressed consent of the copyright holder, Eskom Holdings SOC Ltd, Reg No 2002/015527/30.
Template Rev 5
240-43921804
MATLA POWER STATION Identifier
Document Rev 2
15738
Electrical Operating Desk Identifier
Plant Inspection Effective Date 21 August 2017
Review Date August 2020
Assistant shift
Supervisor:
Name: Signature: Date: Time:
Local Control
Officer:
Name: Signature: Date: Time: