This document describes the IEC103 protocol for the ADR241S overcurrent protection relay. It defines the semantics of information numbers for system functions, status indications, fault indications, and measurands that are communicated in the monitor direction. It also defines the semantics of information numbers for system functions and general commands that are communicated in the control direction. The information numbers indicate values like protection active status, trip indications, voltage and current measurements, reset commands, and trip commands.
This document describes the IEC103 protocol for the ADR241S overcurrent protection relay. It defines the semantics of information numbers for system functions, status indications, fault indications, and measurands that are communicated in the monitor direction. It also defines the semantics of information numbers for system functions and general commands that are communicated in the control direction. The information numbers indicate values like protection active status, trip indications, voltage and current measurements, reset commands, and trip commands.
This document describes the IEC103 protocol for the ADR241S overcurrent protection relay. It defines the semantics of information numbers for system functions, status indications, fault indications, and measurands that are communicated in the monitor direction. It also defines the semantics of information numbers for system functions and general commands that are communicated in the control direction. The information numbers indicate values like protection active status, trip indications, voltage and current measurements, reset commands, and trip commands.
IEC103 Protocol for ADR241S Thursday, November 08, 2012
Revision No.: 01
IEC103 Protocol for ADR241S
Function Code: 160 (A0h) for Over- current Protection Relay
Semantics of INFORMATION NUMBER: System Functions in monitor direction
(Ref. IEC60870-5-103 tabel-8) INF Description GI TYP COT FUN (typical) <0> End of general interrogation - 8 10 <255> <0> Time synchronization - 6 8 <255> <2> Reset FCB - 5 3 160 <3> Reset CU - 5 4 160 <4> Start/Restart - 5 5 160 <5> Power on - 5 6 160
Semantics of INFORMATION NUMBER: Status indications in monitor direction
(Ref. IEC60870-5-103 table-9) INF Description GI TYP COT FUN (typical) <18> Protection active X 1 1,7,9,11,12,20,21 160 <19> LED Reset - 1 1,7,11 160 <21> Test X 1 9,11 127 <22> Local Parameter setting X 1 9,11 160 <23> Char. 1 (Setting group1 active) X 1 1,7,9,11,12,20,21 160 <24> Char. 2 (Setting group2 active) X 1 1,7,9,11,12,20,21 160 <25> Char. 3 (Setting group3 active) X 1 1,7,9,11,12,20,21 160 <26> Char. 4 (Setting group4 active) X 1 1,7,9,11,12,20,21 160 <27> Status 1 X 1 1,7,9,11 160 <28> Status 2 X 1 1,7,9,11 160 <29> Status 3 X 1 1,7,9,11 160 <30> Status 4 X 1 1,7,9,11 160 <124> Trip X 1 1,7,9,11,12,20,21 127
ASHIDA Electronics PVT. Ltd., Thane Page 1 of 4
IEC103 Protocol for ADR241S Thursday, November 08, 2012 Revision No.: 01
Semantics of INFORMATION NUMBER: Fault indications in monitor direction
IEC103 Protocol for ADR241S Thursday, November 08, 2012 Revision No.: 01
Semantics of INFORMATION NUMBER: Measurands in monitor direction
(Ref. IEC60870-5-103 table-14) INF Description GI TYP COT FUN (typical) <147> Measurand IN, VEN - 3.4 2, 7 160 <148> Measurand IL 1,2,3, VL 1,2,3. , P, Q, f - 9 2, 7 160 (Note : VL 1,2,3. , P, Q, f are invalid)
ASHIDA Electronics PVT. Ltd., Thane Page 3 of 4
IEC103 Protocol for ADR241S Thursday, November 08, 2012 Revision No.: 01
Semantics of INFORMATION NUMBER: System Functions in control direction
(Ref. IEC60870-5-103 table-16) INF Description TYP COT FUN (typical) <0> Initialization of general interrogation 7 9 <255> <0> Time synchronization 6 8 <255>
Semantics of INFORMATION NUMBER: General commands in control direction
(Ref. IEC60870-5-103 tabel-17) INF Description COM* TYP COT FUN (typical) <19> LED Reset ON 20 20 160 <124> Trip ON 20 20 127
* Permissible selections of DCO values are specified in COM column (Ref. IEC60870-5-103 Section7.2.6.4)