Tata Steel, KPO-BOD

Technical Particulars of LT PVC Cables (Copper conductor)


CONTROL CABLE
S.No Particulars 4 X 1.5 7 X 1.5 10 X 1.5 12 X 1.5 16 X 1.5 19 X 1.5 24 X 1.5
1 Name of Manufacturer KEI INDUSTRIES LTD.
2 Type of cable YWY YWY YWY YFY YFY YFY YFY
3 Voltage Grade V 1100
4 No of cores X size in sqmm 4 X 1.5 7 X 1.5 10 X 1.5 12 X 1.5 16 X 1.5 19 X 1.5 24 X 1.5
5 Conductor
a) Material Plain annealed Copper to IS:8130/1984
b)
Max. d.c. resistance of
7.41 7.41 7.41 12.1 12.1 12.1 12.1
conductor at 20° C (ohm/km)
Stranded Stranded Stranded Stranded Stranded Stranded Stranded
Shape of the conductor
c) Circular Circular Circular Circular Circular Circular Circular
6 Insulation
a) Material PVC as per IS 1554, Latest
b) Nominal thickness (mm) 0.8 0.8 0.8 0.8 0.8 0.8 0.8
7 Inner Sheath
a) Material Extruded PVC Type ST2 as per IS:5831/84
b) Minimum thickness (mm) 0.3 0.3 0.3 0.3 0.3 0.3 0.3
8 Armouring
Galvanise Galvanise Galvanise Galvanise Galvanise Galvanise Galvanise
Material
a) d Steel d Steel d Steel d Steel d Steel d Steel d Steel
Round Round Round
Type of armouring Flat Strip Flat Strip Flat Strip Flat Strip
b) Wire Wire Wire
c) Nominal size of armour (mm) 1.40 1.40 1.40 4.0 x 0.8 4.0 x 0.8 4.0 x 0.8 4.0 x 0.8
9 Outer Sheath
a) Material PVC Type 'ST2' as per IS:5831/84
1.24 1.24 1.24 1.40 1.40 1.40
1.4 (Min.)
b) Thickness (mm) (Min.) (Min.) (Min.) (Min.) (Min.) (Min.)
10 Electrical Parameters
a)
Max. a.c. resistance of 9.45 9.45 9.45 14.500 14.500 14.500 14.500
conductor at 90° C (ohm/km)

Advent Envirocare CABLE - GTP 1/4


Tata Steel, KPO-BOD
S.No Particulars 4 X 1.5 7 X 1.5 10 X 1.5 12 X 1.5 16 X 1.5 19 X 1.5 24 X 1.5
b) Calculated Cable reactance (ohm/km)
0.0978 0.0978 0.0978 0.0978 0.0978 0.0978 0.0978
c) Impedance of cable (ohm/km) 9.451 9.451 9.451 14.500 14.500 14.500 14.500
d Approx. Cable Capacitance (mfd/km)
0.19 0.19 0.19 0.19 0.19 0.19 0.19
11 Maximum conductor
temperature under normal 70°C
operating conditions
Maximum conductor
12 temperature at the termination 160°C
of short circuit
13 Short Circuit rating of
conductor for the duration of 1 0.36 0.36 0.36 0.21 0.21 0.21 0.21
sec (kA)
14 Continuous Current carrying
capacities :-
(a) In Ground at 30°C (A) 27 20 18 12 11 10 9
(b) In Air at 40°C (A) 24 17 15 10 9 9 8
15 Applicable Standard IS 8130/84,IS 7098 Part I/88, IS 5831/84, IS 3975/88 etc. with latest up to
16 Approx. overall diameter of the
14.5 16.5 18.5 19.4 21.7 22.5 25.9
cable in mm
17 Minimum bending radius 12 times Overall diameter
18 Max. Tensile strength
(i) for Cables pulled with stocking (kg.) 7x D2 where D is the overall diameter of the cable
ii) for Cables pulled with pulling eyes (kg)
51 89 127 153 204 250 306
19 Colour of outer sheath. Black
Note :
1 The values given above are
2 Interval marking, packing, cores identification, drum length, etc. shall be as per IS standard
3 All routing test shall be conducted as per IS standard. Copy of type test certificates shall be submitted for our
4 Packing, identification marking, drum length, etc. shall be as per IS standard.

Advent Envirocare CABLE - GTP 2/4


Tata Steel, KPO-BOD
Technical Particulars of 1.1 KV, Copper conductor, EPR insulated, PCP sheathed flexible
cable
FLEXIBLE CABLE (POWER JB TO MOTOR)
S.No Particulars 1 X 16 1 X 25 1 X 35 1 X 50 1 X 70
1 Name of Manufacturer KEI INDUSTRIES LTD.
2 Type of cable Unarm. Unarm. Unarm. Unarm. Unarm.
3 Voltage Grade V 1100
Reference standards IS: 9968 (Part I)-1988, IS-6380-1984, IS: 8130-1984
4
5 Conductor
annealed tinned copper, class 5 conforming to
Material
IS:8130/1984 & IS:613(1964)
a)
b) Max. d.c. resistance of conductor
1.24 0.795 0.595 0.393 0.277
at 20° C (ohm/km)
Shape of the conductor Stranded Stranded Stranded Stranded Stranded
c) (strand/dia. As per IS:8130) Circular Circular Circular Circular Circular
d) Seperator Melinex/Polyster tape
6 Insulation
EPR type IE-2 as per IS:6380-1984
a) Material
b) Nominal thickness (mm) as per IS:9968/1
7 Inner Sheath
a) Material --
b) Minimum thickness (mm) -- -- --
7a Reinforcement/Braiding
a) Material --
b) Type -- -- --
8 Armouring
a) Material
Unarmour Unarmour Unarmour Unarmour Unarmour
b) Type of armouring
ed ed ed ed ed
c) Nominal size of armour (mm)
9 Outer Sheath
a) Material PCP type SE-4 as per IS:6380-1984
Extruded or wrapped Extruded
as per IS:9968
b) Thickness (mm)
Colour of outer sheath. Black
10 Electrical Parameters
a) Max. a.c. resistance of conductor
1.210 0.780 0.554 0.386 0.272
at 90° C (ohm/km)
Calculated Cable reactance
0.0000 0.0000 0.0000 0.0000 0.0000
b) (ohm/km)
c) Impedance of cable (ohm/km) 1.210 0.780 0.554 0.386 0.272
Approx. Cable Capacitance
0.000 0.000 0.000 0.000 0.000
d (mfd/km)
Maximum conductor temperature
11 90°C
under normal operating conditions

Maximum conductor temperature


12 250°C
at the termination of short circuit

Advent Envirocare CABLE - GTP 3/4


Tata Steel, KPO-BOD
13
Short Circuit rating of conductor
for the duration of 1 sec (kA)
14 Continuous Current carrying
capacities :-
(a) In conduit (A) 68 85 108 144 256
(b) In Air at 40°C (A) 82 103 132 174 290
15 Applicable Standard
IS 694 with latest up to date amendments

16 Approx. overall diameter of the


cable in mm
17 Minimum bending radius As per standards
18 Max. Tensile strength
(i) for Cables pulled with stocking (kg.)
for Cables pulled with pulling eyes
ii) (kg)
19 Colour of outer sheath. Unicolour
Note :
The values given above are subject to tolerances as per the elevant standards.
1
Interval marking, packing, cores identification, drum length, etc. shall be as per IS
2
standard
All routing test shall be conducted as per IS standard. Copy of type test certificates shall
3
be submitted for our review.
4
Packing, identification marking, drum length, etc. shall be as per IS standard.
any new size envisaged further as per project requirement, the same shall be supplied after
5
taking prior approval of TSL/TCE.

Advent Envirocare CABLE - GTP 4/4