You are on page 1of 3

Technical Particulars of HT XLPE Cables

CUSTOMER - Sri Siddharth Infratech & Services (I) Pvt. Ltd.

PROJECT - CONSTRUCTION OF 30MW SOLAR PV POWER PLANT AT NELLORE (D), ANDHRA PRADESH

CLIENT - GREENFLASH PRIVATE LIMITED


P.O. No. SRI SIDDHA/16-17/DPO/0065

Particulars 3 X 185 3 X 300


Cable Type A2XFY A2XFY
Voltage Grade kV 19/33 (E) 19/33 (E)
1.0 Conductor resistance 0.164 0.1
2.0 a) Thickness of insulation (Nominal) 8.8 8.8
b) Thickness of sheath (Minimum)
i. Inner 0.7 (Min.) 0.7 (Min.)
ii. Outer 3.00 (Min.) 3.00 (Min.)
Min. Insulation Resistance shall be such that the minimum vol. Res. of 1 x
3.0 Insulation resistance
10e12 shall be met with
4.0 Tensile strength of conductor Above 150 N/mm2
5.0 a) Tensile strength at break of
i. Insulation 12.5 N/mm2
ii. Inner sheath 12.5 N/mm2
iii. Outer sheath 12.5 N/mm2
b) Elongation at break of
i. Insulation 2
ii. Inner sheath 1.5
iii. Outer sheath 1.5
6.0 Oxygen index value Min. 29%
7.0 Smoke density Max. 60%
8.0 Acid gas generation Max. 20% by weight
9.0 Flame propagation as tested by flammability test. As per IEC 60332-1
B Technical Data
1.0 Make Polycab Wires Pvt. Ltd.
2.0 Type A2XFY A2XFY
3.0 Applicable Standard IS:7098 Pt(2)/2011
4.0 Voltage Grade 19/33 (E) 19/33 (E)
5.0 Suitable for system with
a Service voltage 33 33
b Neutral earthing 19 19
6.0 Maximum conductor temperature
a Continuous, oC 90
b Short time, oC 250
7.0 Conductor
a Material H4 Grade Aluminium as per Class 2 of IS: 8130/84,latest
b Shape of Conductor Compact Stranded Circular Compact Stranded Circular
c Size, mm2 185 300
8.0 Shielding on Conductor (HT Cables)
a Material Semi-conducting Compound
b Type - -
c Nominal Thickness, mm 0.3 0.3
d Whether extruded Yes
9.0 Insulation
a Material XLPE as per IS 7098(Pt-2)/2011, latest
b Type Extruded
c Nominal Thickness, mm 8.8 8.8
Technical Particulars of HT XLPE Cables

CUSTOMER - Sri Siddharth Infratech & Services (I) Pvt. Ltd.

PROJECT - CONSTRUCTION OF 30MW SOLAR PV POWER PLANT AT NELLORE (D), ANDHRA PRADESH

CLIENT - GREENFLASH PRIVATE LIMITED


P.O. No. SRI SIDDHA/16-17/DPO/0065

Particulars 3 X 185 3 X 300


Shielding on insulation (HT cables and
10.0
instrumentation cables)
a Material Extruded Semi-conducting Compound followed by Copper Tape
b Type - -
c Nominal thickness of Semi-conducting
0.3 0.3
compound (mm)
d Nominal thickness of Copper Tape (mm) 0.04 0.04
e Overlap 20% 20%
f Core Identification By coloured strips (Red, Yellow & Blue) over CU tape
11.0 Inner sheath
a Material Extruded PVC Type ST2 to IS:5831/84
b Type Extruded
c Minimum Thickness, mm 0.7 0.7
d Extruded? Yes Yes
e Approx. outside dia over sheath, mm 78.4 87.4
12.0 Armouring
a Material Gal.Steel Flat Strip
b Size, No. x dia 6.1 x 1.4 6.1 x 1.4
c D.C Resistance at 20oC, Ohm / km 0.574 0.510
13.0 Outer sheath
a Material Extruded FR-LSH PVC Type ST2 to IS:5831/84
b Type Extruded
c Minimum Thickness, mm 3.00 3.00
d Colour of Outer sheath Black
14.0 Approximate overall diameter, mm 87.0 ± 3.0 96.0 ± 3.0
15.0 Standard drum length with tolerance, mm 500 ± 5% 500 ± 5%
16.0 Net weight of cables, kg/km 8,864 11,039
Continuous current rating for standard IS
17.0
condition laid direct
a In ground 270 351
B In duct 245 317
c In air 336 448
18.0 a Short circuit current for 1 sec., kA 17.48 28.35
b Conductor temperature allowed for the
250°C
short circuit duty

Electrical parameters at maximum operating


temperature, i.e. 90oC for HT power, 85oC for LT
19.0
power, 70oC for Control cables and 85oC for
instrumentation cables.

a Conductor d.c. resistance at 20°C, Ohm / km 0.164 0.1


b Conductor a.c. resistance, Ohm / km 0.211 0.13
Min. Insulation Resistance shall be such that the minimum vol. Res. of 1 x
c Insulation resistance, Ohm / km
10e12 shall be met with
d Reactance at 50 Hz, Ohm / km 0.113 0.105
e Impedance, Ohm / km 0.239 0.167
Technical Particulars of HT XLPE Cables

CUSTOMER - Sri Siddharth Infratech & Services (I) Pvt. Ltd.

PROJECT - CONSTRUCTION OF 30MW SOLAR PV POWER PLANT AT NELLORE (D), ANDHRA PRADESH

CLIENT - GREENFLASH PRIVATE LIMITED


P.O. No. SRI SIDDHA/16-17/DPO/0065

Particulars 3 X 185 3 X 300


f Image attenuation (instrumentation cables) N.A.

g Cross talk attenuation (Instrumentation


N.A.
cables)
20.0 Recommended minimum bending radius 15 times Overall diameter
Derating factor for following ambient
21.0
temperature in Air/Ground
F At 30oC
F At 35oC
F At 40oC Refer Attached Annexure Refer Attached Annexure
F At 45oC
F At 50oC
Group factor for following nos. of cables laid
22.0
touching / 2 x diameter centre to centre apart
a Single core cable (in trefoil)
i. 2 nos.
ii. 3 nos.
iii. 4 nos.
b Multicore cable (in trefoil) Refer Attached Annexure Refer Attached Annexure
i. 3 nos.
ii. 4 nos.
iii. 5 nos.
iv. 6 Nos.
23.0 The cables shall be tested as specified As per IS 10810 As per IS 10810
Whether type test certificates for similar type of
24.0
cables enclosed with the Bid? Cross sectional Drawing attached Cross sectional Drawing attached
25.0 Cable sectional details submitted?
26.0 Embossing YEAR POLYCAB ELECTRIC 19/33 KV (E) GRADE XLPE FR-LSH
YEAR POLYCAB ELECTRIC 19/33 KV (E) GRADE XLPE FR-LSH, CABLE
27.0 Printing SIZE, CABLE TYPE Screen Fault current 0.6 KA for 1 Sec. WITH
SEQUENTIAL MARKING at every one meter interval.

Note:-The values given above are subject to tolerances as per the relevant standards.
GTP No.-160830-3261_Rev. 01.04.2017
SPR No.- 20
Swarup Bagul

You might also like