Tabla 1

Latitude Y-Factor
Below 42º 0.32
Between 42º and 58º 0.25
Above 58º 0.20

Tabla 3 Heat Input SI

Wetted Area, m2 Design Pressure, Kpa (gauge) Heat Input, W

<18,6 <=103,4 63150*Atws


>=18,6 & <93 <=103,4 224200*(Atws^0,566)
>=93 & <260 <=103,4 630400*(Atws^0,338)
>=260 >7 & <=103,4 43200*(Atws^0,82)
>=260 <=7 4,129,700

Tabla 5 Venting Capacity SI


Normal Venting Capacity,
Wetted Area, m2 Design Pressure, Kpa (gauge)
Nm3/h
<260 <=103,4 Tabla 7
>=260 <=7 19,910.00

>=260 >7 & <=103,4 Ecuación

Tabla 7 Emergency Venting Required for Fire, SI

Wetted Area, m2 Venting Required, Nm3/h

2 608
3 913
4 1217
5 1521
6 1825
7 2130
8 2434
9 2738
11 3347
13 3955
15 4563
17 5172
19 5780
22 6217
25 6684
30 7411
35 8086
40 8721
45 9322
50 9895
60 10971
70 11971
80 12911
90 13801
110 15461
130 15751
150 16532
175 17416
200 18220
230 19102
260 19910
>260 -
Tabla 2
C-Factor para varias condiciones
Pv similar n-C6 Pv > n-C6 o desconocida
Latitud
Average storage temperature, ºC
< 25 >=25 <25 >=25
Below 42º 4 6.5 6.5 6.5
Between 42º and 58º 3 5 5 5
Above 58º 2.5 4 4 4

Tabla 4 Heat Input USC

Wetted Area, ft2 Design Pressure, psig Heat Input, Btu/h

<200 <=15 20000* Atws


>=200 & <1000 <=15 199300*(Atws^0,566)
>=1000 & <2800 <=15 963400*(Atws^0,338)
>=2800 >1 & <=15 21000*(Atws^0,82)
>=2800 <=1 14,090,000

Tabla 6 Venting Capacity USC


Normal Venting Capacity,
Wetted Area, ft2 Design Pressure, psig
SCFH
<=2800 <=15 Tabla 8
>=2800 <=1 742,000.00

>=2800 >1 and <=15 Ecuación

Tabla 8 Emergency Venting Required for Fire, USC

Wetted Area, m2 Venting Required, Nm3/h

20 21100
30 31600
40 42100
50 52700
60 63200
70 73700
80 84200
90 94800
100 105000
120 126000
140 147000
160 168000
180 190000
200 211000
250 239000
300 265000
350 288000
400 312000
500 354000
600 392000
700 428000
800 462000
900 493000
1000 524000
1200 557000
1400 587000
1600 614000
1800 639000
2000 662000
2400 704000
2800 742000
>2800 -
Insulation Conductance Insulation Thickness
Tank Design
F-factor
Configuration W/m2-K Btu/(h-ft2-F) cm in

Bare metal tank - - 0 0 1


22.7 4.00 2.5 1 0.3
11.4 2.00 5.11 2 0.15
5.7 1.00 10.2 4 0.075
3.8 0.67 15.2 6 0.05
Insulated tank
2.8 0.50 20.3 8 0.0375
2.3 0.40 25.4 10 0.03

1.9 0.33 30.5 12 0.025

Tanque de concreto a
- - -
prueba de fuego
Water application
- - 1
facilities
Depresuring and
- - 1
amplying facilities