InteliVision 5

InteliVision 5 RD
CONTROLLER COLOUR DISPLAY UNIT

InteliVision 5

Plug and play Front ScreenEditor Short Tier 4 Configurable


Description
interface IP65 distance soft keys

InteliVision 5 and InteliVision 5 RD


– new generation colour display
panels compatible with the following
product line of controllers:

cc InteliGenNT
cc InteliSysNT
cc InteliMainsNT

There are two versions available:


cc InteliVision 5 – for localized
visualisation and intended
for shorter distances (up to
2 meters) from the controller
InteliVision 5 RD cc InteliVision 5 RD – for remote
visualisation and intended
for longer distances (up to
1000 meters) from the controller

They are designed as a simple, easy


to use Plug and play solution.

Galvanically Plug and play Front ScreenEditor Long Tier 4

Order codes
separated interface IP65 distance
RS-485 interface

Product Order code


InteliVision 5 INTELIVISION 5
Configurable Backlit dimming Binary output Internal buzzer Backlit
soft keys analog input InteliVision 5 RD INTELIVISION 5 RD

ComAp is a member of ComAp products meet the highest


AMPS (The Association of standards, with every stage of production
Manufacturers of Power undertaken in accordance with the ISO The product has
MEMBER generating Systems). certification obtained in 1998. the UL Certification.
Benefits Features
cc P lug and play operation (auto configuration cc 5,7” Colour TFT display with resolution 320 × 240 pixels
based on controller application) cc Local display intended for shorter distances (up to 2 meters)1)
cc Simple, fast and intuitive control cc Remote display intended for longer distances (up to 1000 meters)2)
cc Easy drag and drop screen configuration in graphical editor cc Direct connection to the controller (converters are not needed)
cc Fast access to important data cc Communication connection via RS-4851)
cc Five configurable soft keys: cc Communication connection via galvanic separation of RS-4852)
• Fast skip to any screen cc Same cut out as InteliGenNT
• Binary signal activation – S/R button / toggle cc Backlit buttons2)
button / pulse generator cc Equipped with internal buzzer2)
• Association to various Genset commands cc Binary output for external horn/buzzer control2)
cc Support of Tier 4 icons cc Analog input to control backlit intensity2)
cc Mounting screw available at the rear face of cc Operating temperature: –40 to +70°C
InteliVision 5 to mount a compatible controller cc Face is sealed to IP65
cc Same language support as the controller cc EMC, climatic and mechanical tests
including graphic languages cc CE, UL certification

KEY
1)
Only for InteliVison 5
2)
Only for InteliVison 5 RD

Function Overview of InteliVision 5 and InteliVision 5 RD


RS-485 Distance Binary Analog Backlit Protected Internal
isolated [m] output input (display buttons) IP buzzer

InteliVision 5 No 2 No No No IP-65 (face) No

InteliVision 5 RD Yes 1000 Yes Yes Yes IP-65 (face) Yes

Typical application
MS
ROO

2
CAN

RO OM LIFT
EN GINE

x+
eBo
NT Bas
5
liGen ion
Inte InteliVis

-SET J193
9
GEN
HEN
KITC

x+
eBo
NT Bas
ns 5
liMai liVision
Inte Inte x+
eBo
NT Bas
5
liGen ion
Inte InteliVis

-SET 9
GEN J193

ION
EPT
REC

io n8
liVis
Inte

ion8
ROL liVis
T Inte
CON M
ROO
INS
MA

YOUTUBEMANUFACTURER:
LOGO SPECS LOCAL DISTRIBUTOR / PARTNER:

PRINT on light backgrounds on dark backgrounds

standard standard
main red
PMS 1795C
C0 M96 Y90 K2
ComAp a.s.
gradient bottom
PMS 1815C
C13 M96 Y81 K54

white
WHITE
C0 M0 Y0 K0
Czech Republic
black
BLACK
C100 M100 Y100 K100
no gradients no gradients

Phone: + 420 246 012 111
Fax: + 420 266 316 647watermark watermark

E-mail: info@comap.cz
Internet: www.comap.cz
stacked logo (for sharing only) stacked logo (for sharing only)

Customer satisfaction is our mission. We continuously develop our people to be the best to succeed in our mission.

© ComAp. Features and specification are subject to change without prior notice. 2014-04/CPLEIV5
InteliGenNT BaseBox
Gen-set controller

Datasheet
Product description
l Comprehensive paralleling gen-set controller
l Parallel operation up to 32 gen-sets
l High level control for complex systems

Key features
l Load sharing and VAr sharing via CAN
l Virtual shared inputs and outputs via CAN
l Support of wide range of applications
l o Single or multiple gen-sets in parallel to mains Application overview
operation with automatic back up function,
multiple island operation
l Advanced power management function
l Customizable load control in parallel to mains
l Wide range of ECU support
l Highly configurable
o Timers,Internal PLC , Force values and more
l Compatible with ComAp's InteliVision displays
l Active e-mail messaging and SMS
l Extensive built-in protection functions
o Standard protections
o User configurable protection
l Extendable with ComAp's extension modules

|InteliGen NT BaseBox |Related HW ver: 2.0 |Related SW ver: 3.1.0 |Date of issue: 19.1.2015 1
Analog inputs
Technical data
Number 3 non-isolated
Power supply Switchable (Voltage, Resistance,
Type
Power supply range 8-36 VDC Current)

0.4A / 8VDC Resolution 10bits, max 4 decimals


Power consumption 0.15A / 24VDC Range 0-5VDC/0-2500Ω/0-20mA
0.1A / 36VDC Input impedance >100kΩ/>100kΩ/180Ω
10 years (replacable by official ±1% of meas value ±1mV
RTC battery
service) Accuracy ±2% of meas value ±2Ω
Fusing 2A (without BOUT consumption) ±1% of meas value ±0.5mA

Operating conditions Magnetic pick-up


Operating temperature -40°C to +70°C Voltage input range 2 Vpk-pk to 50Veff
Storage temperature -40°C to +80°C Frequency input range 4Hz to 15 kHz
Operating humidity 95% w/o condensation Frequency measurement tolerance 0.2 %
5-25Hz, ±1.6mm
Vibration
25-100Hz, a=4g
Voltage regulator output
Shocks a=200m/s2 Type 5 V TTL PWM / ± 10 VDC with IG-AVRi interface

Voltage measurement Speed governor outputoutput


3ph-n Gen voltage Voltage output ± 10 VDC / max.15 mA
Measurement inputs
3ph-n Mains/Bus voltage Voltage output
± 10 VDC via 10 kΩ resistor / max . 1 mA
Measurement range 277V via resistor

Max allowed voltage 125% PWM 500÷3000 Hz / 5V / max. 10mA

Accuracy 1% of 277V
Communications
Frequency range 40-70Hz (at accy 0.1Hz)
RS232 Direct/Modbus, non-isolated
0.6MΩ ph-ph
Input impedance non-isolated RS485, only terminal
0.3MΩ ph-n Display port
connection
Current measurement External modules
CAN1
250kbps, max 200m, Isolated
3ph Gen current
Measurement inputs
1ph Mains current Intercontroller and comm extensions
CAN2
250/50kbps, max 200/1000m, Isolated
Measurement range 5A
Max allowed current 1000%/200%
Accuracy 2% of 5A
Input impedance <0.1Ω

Binary inputs
Number 12 non-isolated
Input resistance 4.7kΩ
0-2VDC close contact
Close/Open indication
>4VDC open contact

Binary outputs
Number 12 non-isolated
Max current 0.5A (2A per group)
Switching to negative/positive supply terminal

InteliGen NT BaseBox 2
Dimensions, terminals and mounting

Panel door mounting DIN-rail mounting Panel door mounting


with InteliVision 5 with InteliVision 8

① InteliVision5
② InteliGenNT BaseBox
③ DIN-rail
④ InteliVision 8

Note: InteliGenNT BaseBox can be mounted on a standard DIN rail or, in combination with InteliVision 5 or
InteliVision 8, it can be door mounted. InteliVision 5 features mounting rail for direct mounting. Mounting in
combination with InteliVision 8 uses four screws provided in the InteliGenNT BaseBox package.

InteliGen NT BaseBox 3
Available extension modules
Product Description Order code
Inteli IO8/8 8 Binary inputs and 8 Binary outputs packed in a small unit (HW switchable to IO16/0) I-IO8/8
Inteli IO16/0 16 Binary inputs packed in a small unit (HW switchable to IO8/8) I-IO8/8
Inteli AIN8 8 Analog inputs and 1 pulse/frequency input in a small unit I-AIN8
InteliAIN8TC 8 Thermocouple Analog inputs in a small unit I-AIN8TC
IS-AIN8 8 Analog inputs packed in a rugged metal unit IS-AIN8
IGS-PTM 8 Binary inputs, 8 Binary outputs, 4 Analog inputs and 1 Analog output in a unit IGS-PTM
IGL-RA15 15 Binary LED output (3 colors) packed in a rugged metal unit IGL-RA15
I-AOUT8 8 Analog outputs packed in a rugged metal unit I-AOUT8
InternetBridge-NT Multiple Internet connections (PC and Modbus) to all controllers on CAN2 or RS485 IB-NT
I-LB+ Direct connection (PC) to all controllers on CAN2 or RS485 I-LB+

Related products
Product Description Order code
InteliVision 5 Color 5.6" display for monitoring and control INTELIVISION 5
InteliVision 5 RD Color 5.6" display for monitoring and control (RS485 isolated and backlit buttons) INTELIVISION 5 RD
InteliVision 8 Color 8" display for advanced monitoring, control & trending, USB capable INTELIVISION 8

Functions and protections


The described product fully supports the following functions and protections as defined by ANSI (American
National Standards Institute):

Description ANSI code Descritption ANSI code


Synchronism check 25 Earth fault current 50N+64
Undevoltage 27 Overcurrent (IDMT) 51
Overload 32 Earth fault current IDMT 51N+64
Load shedding 32P Power factor 55
Reverse power 32R Overvoltage 59
Undercurrent 37 Gas (fuel) level 71
Excitation loss 40 Vector shift 78
Current unbalance 46 AC reclosing 79
Voltage asymmetry and phase sequence 47 Overfrequency 81H
Temperature monitoring 49T Underfrequency 81L
Generator overcurrent 50 ROCOF 81R

Certificates and standards


This product is CE compliant.
l EN 60068-2-6 ed.2:2008
l EN 60068-2-27 ed.2:2010
l EN 60068-2-30, May 2000
l EN 60068-2-64
l EN 61010-1:2003

InteliGen NT BaseBox 4
InteliGenNTC BaseBox
Gen-set controller

Datasheet
Product description
l Comprehensive paralleling gen-set controller
l Parallel operation up to 32 gen-sets
l High level control for complex systems
l CHP and gas engine controller

Key features
l Load sharing and VAr sharing via CAN
l Virtual shared inputs and outputs via CAN
l Support of wide range of applications
l o Single or multiple gen-sets in parallel to mains
operation with automatic back up function,
Application overview
multiple island operation
l Advanced power management function
l Customizable load control in parallel to mains
l Wide range of ECU support
l Extended communication capabilities
o Built-in web server
o Full Modbus slave support
o GPS and AirGate support and more
l Highly configurable
o Timers,Internal PLC , Force values and more
l Compatible with ComAp's InteliVision displays
l Active e-mail messaging and SMS
l Extensive built-in protection functions
o Standard protections
o User configurable protection
l Extendable with ComAp's extension modules

|InteliGen NTC BaseBox Datasheet |Related HW ver: 2.0 |Related SW ver: 3.1.0 |Date of issue: 30.9.2015 1
Technical data

Power supply Analog inputs


Power supply range 8-36 VDC Number 3 non-isolated
0.4A / 8VDC Switchable (Voltage,
Type
Power consumption 0.15A / 24VDC Resistance, Current)
0.1A / 36VDC Resolution 10bits, max 4 decimals
10 years (replacable by official Range 0-5VDC/0-2500Ω/0-20mA
RTC battery
service)
Input impedance >100kΩ/>100kΩ/180Ω
Fusing 2A (without BOUT consumption)
±1% of meas value ±1mV
Accuracy ±2% of meas value ±2Ω
Operating conditions
±1% of meas value ±0.5mA
Operating temperature -40°C to +70°C
Storage temperature -40°C to +80°C Magnetic pick-up
Operating humidity 95% w/o condensation Voltage input range 2 Vpk-pk to 50Veff
5-25Hz, ±1.6mm Frequency input range 4Hz to 15 kHz
Vibration
25-100Hz, a=4g Frequency measurement tolerance 0.2 %
Shocks a=200m/s2
Voltage regulator output
Voltage measurement 5 V TTL PWM / ± 10 VDC with IG-AVRi
Type
3ph-n Gen voltage interface
Measurement inputs
3ph-n Mains/Bus voltage
Measurement range 110V / 277V
Speed governor output
Max allowed voltage 125% Voltage output ± 10 VDC / max.15 mA
Accuracy 1% of 110V / 277V Voltage output via ± 10 VDC via 10 kΩ resistor / max . 1
Frequency range 40-70Hz (at accy 0.1Hz) resistor mA

0.6MΩ ph-ph PWM 500÷3000 Hz / 5V / max. 10mA


Input impedance
0.3MΩ ph-n
Communications
Current measurement RS232 Direct/Modbus, non-isolated
3ph Gen current RS485 Direct/Modbus, isolated
Measurement inputs
1ph Mains current non-isolated RS485, only terminal
Display port
Measurement range 1A / 5A connection
Max allowed current 1000% / 200% USB port Direct, isolated
Accuracy 2% of 1A / 5A LAN/Internet, Modbus TCP, SNMP,
Ethernet port
Input impedance <0.1Ω WebServer, Airgate
External modules
CAN1
Binary inputs 250kbps, max 200m, Isolated

Number 12 non-isolated Intercontroller and comm extensions


CAN2 250/50kbps, max 200/1000m,
Input resistance 4.7kΩ
Isolated
0-2VDC close contact
Close/Open indication
>4VDC open contact

Binary outputs
Number 12 non-isolated
Max current 0.5A (2A per group)
Switching to negative/positive supply terminal

InteliGen NTC BaseBox Datasheet 2


Dimensions, terminals and mounting

Panel door mounting DIN-rail mounting Panel door mounting


with InteliVision 5 with InteliVision 8

① InteliVision5
② InteliGenNTC BaseBox
③ DIN-rail
④ InteliVision 8

Note: InteliGenNTC BaseBox can be mounted on a standard DIN rail or, in combination with InteliVision 5 or
InteliVision 8, it can be door mounted. InteliVision 5 features mounting rail for direct mounting. Mounting in
combination with InteliVision 8 uses four screws provided in the InteliGenNTC BaseBox package.

InteliGen NTC BaseBox Datasheet 3


Available extension modules
Product Description Order code
Inteli IO8/8 8 Binary inputs and 8 Binary outputs packed in a small unit (HW switchable to IO16/0) I-IO8/8
Inteli IO16/0 16 Binary inputs packed in a small unit (HW switchable to IO8/8) I-IO8/8
Inteli AIN8 8 Analog inputs and 1 pulse/frequency input in a small unit I-AIN8
InteliAIN8TC 8 Thermocouple Analog inputs in a small unit I-AIN8TC
IS-AIN8 8 Analog inputs packed in a rugged metal unit IS-AIN8
IGS-PTM 8 Binary inputs, 8 Binary outputs, 4 Analog inputs and 1 Analog output in a unit IGS-PTM
IGL-RA15 15 Binary LED output (3 colors) packed in a rugged metal unit IGL-RA15
I-AOUT8 8 Analog outputs packed in a rugged metal unit I-AOUT8
InternetBridge-NT Multiple Internet connections (PC and Modbus) to all controllers on CAN2 or RS485 IB-NT
I-LB+ Direct connection (PC) to all controllers on CAN2 or RS485 I-LB+

Related products
Product Description Order code
InteliVision 5 Color 5.6" display for monitoring and control INTELIVISION 5
InteliVision 5 RD Color 5.6" display for monitoring and control (RS485 isolated and backlit buttons) INTELIVISION 5 RD
InteliVision 8 Color 8" display for advanced monitoring, control & trending, USB capable INTELIVISION 8

Functions and protections


The described product fully supports the following functions and protections as defined by ANSI (American
National Standards Institute):

Description ANSI code Descritption ANSI code


Synchronism check 25 Earth fault current 50N+64
Undevoltage 27 Overcurrent (IDMT) 51
Overload 32 Earth fault current IDMT 51N+64
Load shedding 32P Power factor 55
Reverse power 32R Overvoltage 59
Undercurrent 37 Gas (fuel) level 71
Excitation loss 40 Vector shift 78
Current unbalance 46 AC reclosing 79
Voltage asymmetry and phase sequence 47 Overfrequency 81H
Temperature monitoring 49T Underfrequency 81L
Generator overcurrent 50 ROCOF 81R

Certificates and standards

l EN 60068-2-6 ed.2:2008
l EN 60068-2-27 ed.2:2010
l EN 60068-2-30, May 2000
l EN 60068-2-64
l EN 61010-1:2003

InteliGen NTC BaseBox Datasheet 4