Tested & Commissioned By

Te s t R e p o r t f o r 1 0 0 0 K VA
Tr a n s f o r m e r Te s t i n g A t C & S
Solar Power Plant Bhiwani

Naubasta Engineers
PVT LTD.

PLANT: C&S ELECTRIC IMW SOLAR POWER PLANT


CLIENT C & S ELECTRIC DATE 11/6/2014
PROJECT
VOLTAGE RATIO = 11000/270/270 V
MAKE EMCO COOLING ONAN
RATING 1000 KVA
Sr. No.
Current HV = 52.48 A 3812
LV1 = 1069.2 A
LV2 = 1069.2 A YEAR 2011
TEMP HV-LV1= 5.93%
RISE OIL:50 WIND:55 IMP VOLATGE HV-LV2 = 5.85%

Dyn11yn11
VECTOR
GROUP
NO.OF
TAPS 5

BETWEEN 15 sec 60 sec 600 sec PI

HV-EARTH 13 18.4 35.3 1.91


HV-LV1 18.0 25.9 40.9 1.57
HV-LV2 18.2 27.1 43.2 1.59
LV1-EARTH (at
500 V) >1
LV2-EARTH (at
500 V) >1

RATIO TEST:- (voltage applied on primary and secondary measured)

TAP NO Primary Applied Voltage Secondary Volts Measured


1U-1V 1V-1W 1W-1U 2U-2V 2V-2W 2W-2U 2U-2N 2V-2N 2W-2N
1 445 440 441 10.30 10.21 10.34 6.0 5.91 5.93
2 445 440 441 10.56 10.45 10.59 6.14 6.06 6.08
3 447 441 443 10.84 10.73 10.87 6.30 6.21 6.25
4 447 441 442 11.07 10.94 10.09 6.42 6.32 6.33
5 444 439 439 11.32 11.20 11.34 6.58 6.50 6.49

RATIO TEST:- (voltage applied on primary and secondary measured)

NAUBASTA ENGINEERS PVT


CLIENT
LTD.
Tested & Commissioned By

Te s t R e p o r t f o r 1 0 0 0 K VA
Tr a n s f o r m e r Te s t i n g A t C & S
Solar Power Plant Bhiwani

Naubasta Engineers
PVT LTD.

TAP NO Primary Applied Voltage Secondary Volts Measured


1U-1V 1V-1W 1W-1U 3U-3V 3V-3W 3W-3U 3U-3N 3V-3N 3W-3N
1 445 440 441 10.30 10.21 10.34 6.0 5.92 5.93
2 445 440 441 10.55 10.45 10.59 6.13 6.06 6.07
3 447 441 443 10.82 10.71 10.85 6.28 6.21 6.22
4 447 441 442 11.01 10.91 10.04 6.39 6.33 6.33
5 444 439 439 11.30 11.19 11.31 6.56 6.48 6.49

MAGNETISING BALANCE Test


(VOLTS)AT NORMAL TAP HV SIDE

VOLTAGE MEASURED VOLTAGE


APPLIED ACROSS
APPLIED
R-Y Y-B B-R

1U & 1V PHASE 443.3 342.5 98.3

PHASE TO PHASE 1V & 1W PHASE 219.2 438.8 218.3

1W & 1U PHASE 88.0 351.0 440.9

MAGNATISING CURRENT Test


AT NORMAL TAP (3 Tap)

VOLTAGE MEASURED VOLTAGE


APPLIED ACROSS
APPLIED
IU-1V 1V-1W 1W-1U
PHASE 434.6 430.3 431.6
Three
Phase PHASE 1U 1V 1W

CURRENT(mA) 2.3 2.0 1.4

VECTOR GROUP CHECK:- (3Ph 415V Applied on HV Winding And 1U-


2UShorted)

NAUBASTA ENGINEERS PVT


CLIENT
LTD.
Tested & Commissioned By

Te s t R e p o r t f o r 1 0 0 0 K VA
Tr a n s f o r m e r Te s t i n g A t C & S
Solar Power Plant Bhiwani

Naubasta Engineers
PVT LTD.

Measured Voltage
CONDITION
1 1U-1V 439
2 1U-2N 6.21 1U-1V = 1U-2N +
3 1V-2N 433 1V-2N
4 1W-2W 426
Dyn11 1W-2W < 1W-2V
5 1W-2V 435
6 1V-2W 429
1V-2W = 1V-2V
7 1V-2V 429

Remarks- All protections of transformer are checked and

Found ok.

1. OTI alarm Setting – 85 degree Celsius


2. OTI Tripping Setting – 95 degree Celsius
3. Buchholz Alarm – ok
4. Buchholz Tripping- ok
5. MOG Alarm – ok
6. PRV Trip - ok

TESTED BY
NAUBASTA ENGINEERS PVT LTD

NAUBASTA ENGINEERS PVT


CLIENT
LTD.