mahingan fas Nerbiaec eels doee-3t6 arog asec Coury Code) Faces Bin ereenes pct om ® Underwriters Laboratories in February 24, 2000 System Sensor Attn: Mr. Zoltan Borbath 3820 Stem Ave. ‘St. Charles IL 60174 ‘Subject: Accuflow AFD and LFD Waterflow Indicators Panel Compatibility, Dear Mr. Borbath, Based on our investigation of the above referenced products, we found that the following statement was a sufficient specification for the panel compatibility of the The AFO and LFD walerfiow indicators may receive powor and operate on a fwo-wire Jnitating zone of a fire alarm contral panct, Veen determining compatiollly of these devices, the ‘standby operating volage of the cantral panel must be between 8.5 and 36 volts, Inthe standby mode, the AFD and LED draw a maximum corrent of 0.3.04, in alarm, the AFD and LFO act a8 & ‘Sher across the indiating rone (sina ta. a manual fire alarm box). Fartwo wire conventional fre ‘aiorm contri panels, nat move thai 5 waterflow indicators may be connected fe a singio inkinting ‘rena, The maximum ratarceset de of the watevflow indkcotar plus the inifiating zone shai not ‘exceed 90 seconds. two wirmaddressable control panots, the number of walerflow insficafors connected t0 the paner’s signatiog line citcul shall be kmied only by the crcis's curent capacty. Per our requirements, this statement shall appear in the installation instructions provided with each UL Listed AFD and LFD Series waterflow indicators. Should you have any questions or comments concerning the above, please do not hesitate to contact us. Very Truly Yours, Chris Storbeck (Ext. 41501) Associate Project Engineer Engineering Services - 3017A A neloapelt emanizaten ‘Srceated to publ slaty and commie sty sang