QRO
TESTLA
Elektrik Laboratuvarlari Tic. Ltd. Sti.
Kuzuluk Mah. Ankara Cad. No:34
‘Akyazi ! SAKARYA / TURKIYE A8-0386-7
Tel:+90 264 437 97 70 Faks:+90 264 437 97 80
TEST REPORT
www testia.com.tr
a
1812.20.01100
28.12.2015
Hu
Sigma Elektrik San. ve Tic. AS.
Client Name/Address. | Yunus Emre Mh. Yenidogan Yolu Cd. No:30/A 34792 Sancaktepe/
ISTANBUL/ TURKIYE T: +90 216 429 72 01 F: +90 484 4101
Name And Identity Of
Bodne $20 / Low voltage current transformers,
Rated Characteristics | . .
Gen By The Ghent 0:72KV- SOIGOHz- 150/5A- 10VA- 0,Scl-
|
Order No. 1512.20 | Sample Acceptance Date
(> amalbinl Test Date(s) “| 14,12.2015-18.12.2015
TS EN 60947-4-1: 13.12.2011
Test Standard(s) Low-Voltage Switchgear and Control gear ~- Part 4-1: Contactors and Motor-Starters -
Electromechanical Contactor
Test Result(s) Details, are given on the following pages which are part ofthis report.
Remarks
‘The test results relate only to the itoms tested.
‘Tests marked (#) in this test report are not included in the TURKAK accreditation schedule for this laboratory.
TESTLA Elektrik Laboratuvarian accredited by TURKAK under registration number AB-0386-T for TS EN ISO/TS EN
17025:2012 as test laboratory.
Turkish Accreditation Agency (TURKAK) is a signatory to the European co-operation for Accreditation (EA) Multilateral
Agreement (MLA) and to the International Laboratory Accreditation Cooperation (ILAC) Mutual Recognition Arrangement
(MIRA) for the recognition of test reports.
‘The test andlor moasuromont results, the uncertainties (if applicable) with confidence probability and test methods are given
on the following pages which are part of this report.
Person in Charge
28.12.2015
2010+ | Mehmet SUMNU Nihat GESMECi[33 TESTLA Elektrik Laboratuvarlari Tic. Ltd. Sti.
Page:2/7
Contents :
1. Test of attendees
2. Applied Experiments
3. Short Circuit Withstand Test
3.1. Experiment laboratory
3.2. Standards
3.3. Experiment on mechanism
3.4. Product features
4. Types of experiments
4.1. The result of the experiment
4.2. The Evaluation of the Experiment
4.3. Images of test samples
1. Witnesses By :
:Reyhan USTA SIGMA
2. Applied Tests :
Short-time current tests 7.1
Temperature-tise test 7.2
Lightning impulse test 7.3.2
Accuracy class test. 11.1.1
3.Short Circuit Withstand Test
3.1. Experiment laboratory
Experiments in a laboratory environment met the conditions of the standards.
3.2. Standards
3.3. Experiment on mechanism
|] POWER TRANSFORMER
] CIRCUIT BREAKER
TEST
‘SAMPLE
386.
28.12.2015
TELFRTSTREVOOs-00867
[Sj +e12200109
TESTLA Elektrik Laboratuvarlari Tic. Ltd. Sti.
29.12.2018
Page:3/7 -
3.4. Product features
Product : Current transformer
Type 2820
Manufacturer = SIGMA.
Rated Operating Voltage ( Ue) 1 0,72kV
Declared Conversion Rate (Kn) + 100/5A-125/5A-150/5A
Declared a short-time current (ith) = (In x 100)
Rated insulation level 3kV
Rated Frequency 50-60Hz
cL 05
Power 1100-125 / SVA , 150/ 10VA
‘4. Types of experiments
7.1Short-time current tests
#37,5kA Peak / 15kA Effective Current Adjustment
Phase Peak( Ipk Effective (I) Test voltage Cosa
kA, v
oi
2 37,8211 15,346 430V 03
B
* Test 1: 150/5A-37,5kA Peak / 15kA effective current test (1sec.)
Test | Phase Effective (I) Time Test voltage
number kA msec. v
ir
1 @ 37,754] 16,322 1010 430V
B
7.3.2 Lightning impulse test
Type Test Primary - Secondary | Primary Body | Primary -Frame
Voltage
Jak Lag
S20 150/54 3KV Ok ok oK £4 _
“a §
3 2,
eo
8
2010+
TELFR.18/REVOO