7208 Function type in accord, with IEC 60780-5-103 160 7211 Data format for PC interface. DIGSI V3 7214 Transmission gaps for PC-interface. 1.0 s 7215 Transmission baud rate for PC-interface. 9600 Baud 7216 Parity and stop-bits for PC-interface. DIGSI V3 7221 Data format for system-interface. IEC 60870 Compatible. 7224 Transmission gaps for system-interface. 0.0 s 7225 Transmission baud rate for system-interface. 9600 Baud. 7226 Parity and stop-bits for system-interface. IEC/DIGSI V3/LSA. 7233 Supervision time for system-interface. 10 s 7235 Parameterizing via system-interface. No
7800 SCOPE OF FUNCTIONS.
7801 Characteristics of O/C protection Marshalling. Definite Time.
Settings Parameter Group A
1100 POWER SYSTEM DATA. 1101 Rated system frequency. 50 Hz 1105 Primary rated current. 600 1106 Secondary rated current. 5A 1110 Matching factor Ie/Iph for earth current. 0.15 s 1134 Minimum trip command duration. 1.00 s
1300 O/C PROTECTION PHASE FAULTS.
1301 o/c Protection for phase faults. On 1303 Pick up value of the high set inst. stage I>>> +* I/In block. 1305 Pick up value of the high set stage I>> 6.0 In block. 1307 Trip time delay of the high set stage I>> 0.02 s 1311 Measurement repetition. No 1312 Characteristic of the O/C stage Ip Definite 1313 Trip time delay inverse time O/C stage Ip 0.8 Sec. 1316 Pick up value inverse time O/C stage Ip 1.4 x In 1318 RMS format for inverse time O/c protection. Without harmonics. 1320 Manual close. I >> undelayed.
Setting: Chakwal Choa Saidan
1400 O/C PROTECTION EARTH FAULS. 1401 O/C protection for earth faults. On 1402 Pick up value of the high set stage IE>> 6 I/In block. 1404 Trip time delay of the high set stage IE>> 0.03 s 1408 Measurement repetition. No 1409 Characteristic of the O/C stage IEp Definite 1410 Trip time delay inverse time O/C stage IEp. 0.8 sec 1413 Pickup value inverse time O/C stage IEp. 0.2 In 1415 RMS format for inverse time O/C protection. Without harmonics. 1416 Manual close. IE >> undelayed.
2900 MEASUREMENT VALUE SUPERVISION.
2901 Summation threshold for current monitoring. 0.10 I/In 2902 Factor for current summation monitoring. 0.10 s
3800 ANNUNCIATION DELAY TIMES.
3801 Delay time for 1st user defined annunciation. 0.01 s 3802 Delay time for 1st user defined annunciation. 0.01 s 3803 Delay time for 1st user defined annunciation. 0.01 s 3804 Delay time for 1st user defined annunciation. 0.01 s
Calculated by ________________________ ____________________________
(Khalid Hassan Khan) D.M. (Fasihud Din) D.M.
Checked by Muhammad Siddique Sindhu, Manager (S.P) North.