Product data sheet

catrone
®

MicaFlex Microcontroller-based Differential


pressure transmitter with digital indication MF-PD
md-1323gb / 2008-10-21

Application
MF-PD is a pressure transmitter designed for
measuring of low positive, negative and differential
pressure.

ü Output signal in Volt and mA


ü Simple One-Key zero-setting
ü Two selectable measuring ranges, full
range or half range
ü Selectable damping
ü Calibration certificate attached
© AB MICATRONE 2008-10-21 [h: \ appdok \ typeset \ datablad \ md-1323gb_081021.vp]

ü Negative or Positive indication of


pressure
Pressure connections
Pressure connections should be made with
Micatrone mounting kits for safe and tight function.
Connect the measurement outputs with HT-plastic
tube 8/6 mm. Setting of damping
The MF-PD offers a possibility to set different
Display unit damping (time constant). At delivery the damping
MF-PD is fitted with a 4-digit LED display and mi- is set to 1,50 seconds damping.
nus [-] sign when indicating negative pressure.
Half measuring range
Zero adjustment Through a miniature switch the measuring range
Press down the "zero-setting"-button until the LED can be set to full range (100%) or to half measu-
turns off. Release the button and the zero-setting ring range (50%).
is finished. NOTE! The accuracy is always for the full range.
Output signal setting Adjusting the measuring range
The Volt/mA-output signal has different terminals. The measuring range can be adjusted to correct a
Check that the correct output is connected. measuring deviation. Instruction can be found on
R35 D6 D7 R32 IC2 AC2
our web site, www.micatrone.se.
K1
C22 C20

AC9 IC9 R33 R37


Adjustment keys 5 6.
R36

R31

H1
FM1
IC7
R102
R34 C19
IC101 C102
R30

H2
K4 Programming
D5
Micaflex PD is programmable with 4 keys on the
RP101

FM1 R109
IC8 R110 R40
FM2

C4 R9 R7
IC3 R4 R5 AB Micatrone R47
C101 P3761 INC
display unit and include programmable parameters
K101

AC8
K2

C24 Top Silk


R112
R6
AC1

DIG1 DIG2 AC3 DIG3 DIG4

8888
AC7A
LED104

R42 R39
for the alarm function and negative indication.
D101

R46 C1 C2
AC7D

IC1
R2

R20

R8
J1 R38 R41 R10
RP102

LED103
R18
C3

R111 C23
TG1
C6 R11 C9
Alarm function
LED105

R13

J101 R1 R45
R14 D1

RGND R23 R15


C10 R12

MF-PD include a visual alarm indicated by a


R25

R21

R16

C12 R29 C15 C13


PGM R22 ESC
R19
FM3 R24 T3 LED101 LED102R17 T1
IC5 DEC
D103

D2
flashing display on alarm state if this function is
D105R26SW4

C7 C5
C11
R48

C14 R27 R28 C17


IC6
SW3

SW2

SW1

D3
C16
SNAP1 D104 R101 C8
LED T2
D102 LED1 activated. By using an optional plug-in module, a
miniature switch IC4 C18
D4

K3
R44
J2
ZERO
potential-free changing relay output can be obtai-
VDR1
ned. Alarm can be set for High or Low pressure.
C21

R43 ZERO
DIL1 A time delay can be set for 0...600 seconds.
PL2
PL1

Top Silk
P3778 v3.01
AB Micatrone

DIL1 * 1 2 3 4 5 Zero-setting button


1 RANGE
2 TEST G G0G0OutOut
3 OUTPUT
4 DAMPING
(+)(-) (-) V mA
5 DAMPING
* see cover FM2 FM3
Technical data EU Compliences:
Supply voltage: 24 ± 15% VAC, 20...32 VDC EMC SS-EN 50081-1
24, 115, 230 (with trans- SS-EN 50082-2
former), 50/60 Hz LVD SS-EN 610101-1
Power cons.: Max. 3 VA (24VAC)
Max 6 VA (230VAC) Service
Range: -50..50 Pa MF-PD needs normally no service, but we recom-
0...50 (0...25*) Pa mend to check the zero point once a year.
0...100 (0...50*) Pa Cleaning
0...200 (0...100*) Pa MF-PD should be cleaned with a soft cloth and a
0...500 (0...250*) Pa light detergent. Do not use scouring powder or
0...1 (0...0,5*) kPa dissolvent.
0...2 (0...1,0*) kPa
0...5 (0...2,5*) kPa Transformer (Optional)
Other ranges on request. The output signal is normally NOT galvanically se-
*) Half range using a parated to the supply voltage. To obtain galvanic

© AB MICATRONE 2008-10-21 [h: \ appdok \ typeset \ datablad \ md-1323gb_081021.vp]


miniature switch. Measuring separation between the output signal and the sup-
range with zero-crossing can ply voltage on a standard transmitter, the appara-
not be divided. tus must be equipped with a plug-in transformer.
Max. load: £ 50 kPa
Accessories
Output signal: 4...20 mA max RL = 400 W
• Mounting kit VR-DR
0...10 Volt Ri = 0 W
Ambient temp.: 0...55°C • HT-plastic tubing 8/6 yellow, per meter or
Accuracy: Max error ± 0,5% of the full roller 50 m
range plus ± 0,5 Pa. • Manifold valve 2-TK
Temp.drift: Max. 0,5 % per 10°C • MFM-Panel (wall/cabin-door) mounting kit
Damping: Selectable; 0.05, 0.7, 1.5 or • Mounting kit for DIN-rail
2.2 s
Degree of protec.: IP 65 • Transformer 24, 115, 230 VAC, built in
El. connections,
-rigid cable: 1 x 2.5 mm2 / terminal
1 x 1.5 mm 2 / terminal

3
-flexible cable:
Cable entries: 2 st threaded holes M16x1,5

RoHS
(cable glands not attached)
Pressure. conn.: 8/6 mm HT-plastic tube
Dimensions: WxHxD = 122x120x90 mm
Weight: 0,53 kg COMPLIANT

Connection 24 VAC / 20...32 VDC Connection with transformer


(without transformer) (Transformers available for 24/115/230 VAC)
G [+]
G0 [-]
G0 [-]
Out [V]
Out [mA]

N
G0 [-]
Out [V]
Out [mA]
L

AB Micatrone Telephone: +46 8-470 25 00


Åldermansvägen 3 Fax: +46 8-470 25 99
SE-171 48 SOLNA Internet: www.micatrone.se
SWEDEN E-mail: info@micatrone.se

2 web reference - http://www.micatrone.se/prod_detail.php?secID=2&lang=gb&id=60