Professional Documents
Culture Documents
Auxiliary Speaker:
Engr. Raulito C. Baldonado Jr, PEE
Objectives:
5. Select the surge arrester housing porcelain creepage distance in
accordance with the environmental conditions and state to the
manufacturer if live line washing is electricity supply company practice.
6. Determine the surge arrester protective level and match with standard
IEC 60099 recommendations. Typical protective levels are given in
Table 1
Rated Voltage
The power frequency voltage across an arrester must never exceed its rated
voltage otherwise the arrester may not reseal and may catastrophically fail
after absorbing the energy of a surge.
Arrester voltage rating > 0.8 x 132 x 1.1 = 116 kV and 120 kV arresters are
usually selected for effectively grounded system.
Arrester voltage rating > 132 x 1.1 = 145kV, for non-effectively grounded
system.
Rated Current
Arresters are tested with 8/20_ms discharge current waves of varying
magnitude: 1.5 kA, 2.5 kA, 5 kA, 10 kA and 20 kA yielding increasing values of
residual discharge voltage. Maximum residual discharge voltages are detailed
in IEC 60099-1 and this parameter is usually taken care of in the
manufacturer’s design specification. For areas with high isokeraunic levels
(e.g. the tropics) or at locations near to generators or for unshielded lines 10
kA arresters should be specified. Lower rated arresters can be selected for
well-screened systems if it can be demonstrated that the surge discharge
current is less than 10 kA.
However, the cost of arresters is small compared to the overall system
cost and therefore if some doubt exists regarding the discharge
current it is safer to specify the higher-rated heavy duty type of
arrester. Although lightning strikes have impressive voltage and
current values (typically hundreds to thousands of kV and 10–100 kA)
the energy content of the discharge is relatively low and most of the
damage to power plant is caused by the ‘power follow-through
current’. The lightning simply provides a suitable ionized discharge
path. The likelihood of power follow-through current after a lightning
discharge is statistical in nature and depends in a complicated way on
the point on the wave of lightning discharge relative to the faulted
phase voltage.
Arrester Separation Distance and Lead Length
This section will provide us guide for determining maximum separation distances
between arrester lead tap and transformer, considering the effect of arrester lead
length.
1. Arrester separation distance (S) is defined as the distance from the line
arrester lead junction to the transformer bushing. Voltage reflections result
when the discharge voltage traveling as a wave arrives at the transformer. If
the arrester is very close to the transformer, these reflection are cancelled
almost instantaneously by opposite polarity reflections from the arrester. As
the separation distance increases, the cancellation becomes less and less
effective and the voltage at the transformer may increase to almost twice the
arrester discharge voltage.
Standard Outdoor
Substation Structures
Straight Column Line Dead End Structure 23 or 15 kV
14
O.H.G.W.
1
23 16
7
19
Distribution Line
13 17
4
20
Arrester separation distance (S)
3
19
19
6 6 17
2
11 24
Secondary
Terminal Box
Tabulation
12 23
3Ø
23 kV 15 kV
Transformer
A 12'-0" 10'-0"
B 4'-0" 3'-0"
C 2'-0" 2'-0"
D 7'-0" 6'-0"
2'-0" 6'-0"
Figure 1
2. Arrester lead length (L) is defined as
the total length of the conductor from
the junction of the surge arrester lead
with the line or transformer circuit to
physical ground, but not including the
length of the arrester itself. When the
arrester discharges, surge current
flows to ground over the lead length.
The resulting voltage drop, L di/dt, is
proportional to the length and adds to
the arrester discharge voltage.
Standard Outdoor
Substation Structures
Straight Column Line Dead End Structure 23 or 15 kV
14
O.H.G.W.
1
23 16
7
19
Distribution Line
13 17
4
20
Arrester Lead Length (L)
3
19
19
6 6 17
2
11 24
Secondary
Terminal Box
Tabulation
12 23
3Ø
23 kV 15 kV
Transformer
A 12'-0" 10'-0"
B 4'-0" 3'-0"
C 2'-0" 2'-0"
D 7'-0" 6'-0"
2'-0" 6'-0"
Figure 1
Figure 2. Maximum Safe
Separation Distance of
Lightning Arresters from
Protected Equipment
Nominal System Voltage
23kV Through 46kV
L = Arrester Lead Length,
S = Separation Distance
(IEEE Std. C62.22,1991)
Figure 3. Maximum Safe
Separation Distance of
Lightning Arresters from
Protected Equipment
Nominal System Voltage
69kV Through 138kV
L = Arrester Lead Length,
S = Separation Distance
(IEEE Std. C62.22,1991)
Classifications of Surge Arresters
Station Class
Intermediate Class
Distribution Class
Discharge Voltage: The voltage that appears across the terminals of an arrester
during the passage of discharge current. Maximum values are usually available from
the manufacturer for currents of 1.5, 3, 5, 10, 20, and 40 kA with a wave shape of 8
x 20 ms. The discharge voltage resulting from a standard 8 x 20 ms current wave
shape approximates the standard 1.2 x 50 ms voltage wave shape reasonably well
between the current magnitudes of 5 kA and 20 kA.
The 8 x 20 ms standard current wave shape is one that rises to crest in 8 ms and
decays to one-half crest value in 20 ms. The 1.2 x 50 ms voltage wave shape is one
that rises to crest in 1.2 ms and decays to one half crest value in 50 ms.
Discharge-Voltage Current Characteristic: The discharge-voltage current characteristic
is the variation of the crest values of discharge voltage with respect to discharge current.
Silicon-Carbide Valve Arrester This technology relied on both the gap and the
silicon-carbide valve block to operate properly. It has a very good service history.
However, utilities continue to evaluate their over-voltage protection needs, in
particular at critical locations that are currently protected by gapped silicon- carbide
arresters.
Types of Surge Arrester
Metal Oxide Surge Arresters
It’s primary component is zinc oxide
valve that has significantly greater non-
linear volt – current characteristics as
compared to previous devices.
The zinc oxide valve operates more
closely to that of a zener diode that is
applied in the electronic industry. The
valve is capable of being applied without
any gaps in the design, eliminating the
sparkover characteristic of previous
arresters (see Figure 4) as it eases into
conduction. The zinc oxide valve typically
provides lower discharge voltages than
available with previous designs.
“End of Topic”