You are on page 1of 32

Page 1 of 32 TRITECH CORPORATION

ESTIMATE OF QUANTITIES AND RATES FOR HT ELECTRIFICATION OF DD TRADE TOWER AT


KALOOR-KADAVANTHRA ROAD.
SL.NO DESCRIPTION UNIT QTY RATE(RS) AMOUNT(Rs.)

HT ELECTRIFICATION
1.0 SUPPLY & LAYING OF CABLES Rs0
Supply,Laying, testing and commissioning of the Rs0
following PVC Insulated Armoured Aluminium Rs0
L.T.Cables (AYWY/AYFY) /XLPE (A2XCEFY) H.T Rs0
Cables through excavated trenches, built up cable Rs0
trenches, cable trays, hume pipes,including supply Rs0
and fixing of clamps, nuts and bolts, screws, Rs0
identification tags, route markers etc. required for Rs0
clamping intervals as necessry. Rs0

1.1 H.T. 11KV(E) CABLES


a) 3Cx300 SQ.MM. MTRS UR Rs1,500

b) 3Cx185 SQ.MM. MTRS 150 Rs1,300 Rs195,000

1.2 L.T.CABLES Rs0


a) 3.5CX400 SQMM AYFY MTRS 400 Rs2,350 Rs940,000

b) 3.5CX240 SQMM AYFY MTRS 250 Rs1,525 Rs381,250

c) 3.5CX185 SQMM AYFY MTRS UR Rs1,200

d) 3.5CX120 SQMM AYFY MTRS 35 Rs800 Rs28,000

e) 3.5CX70 SQMM AYFY MTRS 200 Rs500 Rs100,000

f) 3.5CX35 SQMM AYFY MTRS 65 Rs280 Rs18,200

g) 4CX10 SQMM AYFY MTRS 2750 Rs150 Rs412,500


Rs0
h) 4C X 6.0 SQ.MM AYFY MTRS 80 Rs145 Rs11,600
Rs0
2) CABLE TERMINATION Rs0
H.T.CABLE TERMINATION Rs0
Supply & Labour charges for termination of HT cables Rs0
using Epoxy type 11KV(E), XLPE Cable termination Rs0
kits, Cable identification tags etc. for the following Rs0
Cross linked Polyethylene Insulated (XLPE)and Rs0
Armoured Aluminium H.T.Cables (A2XCEFY) . Rs0
Rs0
2.1 INDOOR TYPE: Rs0
3Cx300SQ.MM. NOS. UR Rs11,500 Rs0
Page 2 of 32 TRITECH CORPORATION

ESTIMATE OF QUANTITIES AND RATES FOR HT ELECTRIFICATION OF DD TRADE TOWER AT


KALOOR-KADAVANTHRA ROAD.
SL.NO DESCRIPTION UNIT QTY RATE(RS) AMOUNT(Rs.)
3CX185SQ.MM. NOS 1 Rs10,000 Rs10,000

2.2 OUTDOOR TYPE: Rs0


3Cx300SQ.MM. NOS. UR Rs13,500 Rs0

3Cx185SQ.MM. NOS. 1 Rs11,500 Rs11,500


.
2.3 L.T.CABLE TERMINATION Rs0
Supply of all materials and termination of the Rs0
following PVC Insulated Armoured Aluminium Rs0
L.T.Cables (AYWY / AYFY) using single compression Rs0
type cadmium plated brass cable glands, Copper Rs0
crimped type cable lugs, cable identification Rs0
tags and including gland earthing using copper Rs0
conductor of adequate size , AL-CU strip for Rs0
termination of Cables etc. Rs0
Rs0
a) 3.5CX400 SQMM AYFY NOS. 4 Rs950 Rs3,800
Rs0 18 15 19 35
b) 3.5CX240 SQMM AYFY NOS. 6 Rs750 Rs4,500 21 18 22 38
Rs0 24 21 25 41
c) 3.5CX185 SQMM AYFY NOS UR Rs625 27 24 28 44
Rs0 30 27 31 47
d) 3.5CX120 SQMM AYFY NOS. 4 Rs570 Rs2,280 33 30 34 50
Rs0 36 33 37 53
e) 3.5CX70 SQMM AYFY NOS. 20 Rs500 Rs10,000 39 36 40 56
Rs0 42 39 43 59
f) 3.5CX35 SQMM AYFY NOS. 4 Rs400 Rs1,600 270 243 279 423
Rs0 2061
g) 4CX10 SQMM AYFY NOS. 120 Rs350 Rs42,000 130
Rs0 2191
h) 4C X 6.0 SQ.MM AYFY NOS. 4 Rs300 Rs1,200 2629.2
3) SWITCHBOARDS. Rs0
Design, fabrication, supply, erection , testing and Rs0
commissioning of following Cubicle type, fully Rs0
compartmentalised LT Switchboards dust tight Rs0
and vermin proof, fabricated out of 14/16 SWG Rs0
CRCA sheet, chemically treated and painted with Rs0
2 coats of primer and two coats of stoving Rs0
enamel paint of approved shade. The Rs0
Switchboards should have a Set of suitably Rs0
rated TPN Aluminium busbars with the Rs0
specified current and fault level, Insulated with Rs0
heat shrinkable, color coded PVC Sleeves and Rs0
supported using DMC/ SMC Pillar or Finger Rs0
Page 3 of 32 TRITECH CORPORATION

ESTIMATE OF QUANTITIES AND RATES FOR HT ELECTRIFICATION OF DD TRADE TOWER AT


KALOOR-KADAVANTHRA ROAD.
SL.NO DESCRIPTION UNIT QTY RATE(RS) AMOUNT(Rs.)
type busbar supports. The design should be Rs0
as per the standards of the State Electrical Rs0
Inspectorate. Rs0
Rs0
3.1 MSB
Top/Bottom cable entry for incoming and outgoing
feeders. Fabricated out of 16SWG CRCA sheet

1) Busbars:
1000A TPN Al. Busbar - 1no.
Earth bus - 31 x 6CU.
ISO INCOMER 18500 2850 INDICATION LAMPS
2) Incomer1&2(630KVA transformer) : OUT MCCB 51350 13000 OUT METER
Air circuit breaker 1000A, set 840A, 50KA Icw 1sec, TPN Pole 100% rated
Neutral, Manually drawout type with OC, SC, Shunt releases, Shutter
Assembly, with Open, Close and Trip, etc- 2nos
ACB 353250 DC METER 18700
Meters & Indications: SFU 320 25800 IND LAMP 2100
Digital Combination Meter(EM 6400 conzerv or equivalent model) SFU 400 61800 3PH VOLT 3080
with PF Meter KW meter, Ammeter, 3nos 2A Control fuse and FUSE 1000 23880
3nos metering CTs 'Class 1.0 10VA, 1000/5A, - 2sets CT 3700
CFUSE 1092
Red, Yellow, Blue , ON, OFF, TRIP LED Indication Lamps along 446642
with 3nos 2A Control fuses & toggle switch – 2sets. 1013319.0375
1037199.0375
3Phase Digital Voltmeter 0-500V Model DM3256 of Conzerv or
equivalent and 3Nos of 2A Control fuses – 2sets 614437.0375

Relays:
Stand by Earth fault relay 10-40% 1.3sec IDMT -2nos

3)Bus Coupler
Air circuit breaker 1000A,set 840KV, 50KA Icw 1sec, 4Pole 100% rated
Neutral, Manually drawout type without releases, Shutter Assembly - 1no
4) Outgoings:
Switch Disconnector Fuse Unit 400A with 315A Fuse links-6nos

Switch Disconnector Fuse Unit 320A with 160A Fuse links-2nos

Switch Disconnector Fuse Unit 320A with 160A Fuse links,


125A cut out fuses ,KSEB'S 3PH KWH Meter along with
metering CT of 150/5 CL:1 , 10VA, 415V
3nos of 2A control fuses – 1set

Provision shall be made for sealing of all shutters. NOS 1 Rs1,040,000 Rs1,040,000
Page 4 of 32 TRITECH CORPORATION

ESTIMATE OF QUANTITIES AND RATES FOR HT ELECTRIFICATION OF DD TRADE TOWER AT


KALOOR-KADAVANTHRA ROAD.
SL.NO DESCRIPTION UNIT QTY RATE(RS) AMOUNT(Rs.)
3.2 FSB1 & FSB2
Top/Bottom cable entry for incoming and outgoing
feeders. Fabricated out of 16SWG CRCA sheet

1) Busbars:
160A TPN Al. Busbar - 1no.
Earth bus - 25.4 x 3.175mm CU.

2) Incomer:
160A TPN isolator - 1no. ISO INCOMER 4400 1050 INDICATION LAMPS
SFU 160 9640 156 C FUSE
SFU 100 3400
Red, Yellow, Blue LED Indication Lamps along with 3nos 17440 1206
2A Control fuses - 1set. 39567
40773
3) Outgoings:
Switch Disconnector Fuse Unit 160A with 125A Fuse links – 2Nos

Switch Disconnector Fuse Unit 100A with 80A Fuse links -1No

Provision shall be made for sealing of all shutters. NOS 2 Rs41,000 Rs82,000

3.3 FSB3 TO FSB8


Bottom cable entry for incoming and outgoing
feeders. Fabricated out of 16SWG CRCA sheet

1) Busbars:
315A TPN Al. Busbar - 1no.
Earth bus - 25.4 x 3.18mm CU. ISO INCOMER 7200 1050 INDICATION LAMPS
SFU 100 13600 780 C FUSE
2) Incomer: CUTOUT 3000 11000 OUT METER
315A TPN isolator - 1no. 23800 12830
53996.25
Meters & Indications: 66826.25
3 nos. R Y B Indication Lamps along with 3nos. 2A
Control fuses. -1set.

3) Outgoings:
Switch Disconnector Fuse Unit 100A with 80A Fuse links,
with 80A cut out fuses ,KSEB'S 3PH KWH Meter along
with metering CT of 100/5 CL:1 , 10VA, 415V
3nos of 2A control fuses – 4set

Provision shall be made for sealing of all shutters. NOS 6 Rs67,000 Rs402,000
Page 5 of 32 TRITECH CORPORATION

ESTIMATE OF QUANTITIES AND RATES FOR HT ELECTRIFICATION OF DD TRADE TOWER AT


KALOOR-KADAVANTHRA ROAD.
SL.NO DESCRIPTION UNIT QTY RATE(RS) AMOUNT(Rs.)
3.4 SSB1,SSB2,SSB4&SSB5
Bottom cable entry for incoming and outgoing
feeders. Fabricated out of 16SWG CRCA sheet

1) Busbars:
125A TPN Al. Busbar – 1no. INC 7500 1206 INDICATION LAMPS
Earth bus - 25.4 x 3.18mm CU. MCB 9216 22000 OUT METER
CUT OUT 1216 23206
2) Incomer:
125A TPN isolator – 1no 17932
40683.225
Meters & Indications:
3 nos. R Y B Indication Lamps along with 3nos. 2A 63889.225
Control fuses. -1set.

3) Outgoings:
Miniature Circuit Breaker TPN 32A, 32A Cutout fuses,
KSEB's three phase KWH Meter – 8sets

Provision shall be made for sealing all shutters NOS 4 Rs64,000 Rs256,000

3.5 SSB3&SSB6
Bottom cable entry for incoming and outgoing
feeders. Fabricated out of 16SWG CRCA sheet

1) Busbars:
80A TPN Al. Busbar – 1no. INC 3000 1206 INDICATION LAMPS
Earth bus - 25.4 x 3.18mm CU. MCB 5760 13750 OUT METER
CUT OUT 760 14956
2) Incomer:
80A TPN isolator – 1no 9520
21598.5
Meters & Indications:
3 nos. R Y B Indication Lamps along with 3nos. 2A 36554.5
Control fuses. -1set.

3) Outgoings:
Miniature Circuit Breaker TPN 32A, 32A Cutout fuses,
KSEB's three phase KWH Meter – 5sets

Provision shall be made for sealing all shutters NOS 2 Rs37,000 Rs74,000

3.6 DG SB
Top/Bottom cable entry for incoming & outgoing feeders Floor
mount type Fabricated out of 16SWG CRCA sheet.
Page 6 of 32 TRITECH CORPORATION

ESTIMATE OF QUANTITIES AND RATES FOR HT ELECTRIFICATION OF DD TRADE TOWER AT


KALOOR-KADAVANTHRA ROAD.
SL.NO DESCRIPTION UNIT QTY RATE(RS) AMOUNT(Rs.)

1) Busbars:
400A TPN Al. Busbar – 1no.
Earth bus - 25.4 x 3.18mm CU.

2) Incomer: SFU 200 6850 DCM 18700


Moulded Case Circuit Breaker TP, 320A, Set 250A SFU100 9500 KWH 3025
with Electronic release FD KIT, OC, SC, EF, Shunt & Isolation SFU 63 14250 indicator 1050
duty Current Limiting type -1no mccb 16500
47100 22775
Meters & Indications: 106858.125
Digital Combination Meter(EM 6400 conzerv or equivalent model) 129633.125
with PF Meter KW meter, Ammeter, 3nos 2A Control fuse and
3nos metering CTs 'Class 1.0 10VA, 200/5A, - 1set

KSEB' 3PH KWH Meter along with metering CT of 200/5 CL:1 , 10VA,
415V,3nos of 2A control fuses – 1set.

Red, Yellow, Blue,ON,OFF,TRIP LED Indication Lamps 107908.125 cof


along with 3 nos. 2A Control fuses - 1set.

Relays:
Stand by Earth fault relay 10-40% 1.3sec IDMT -1no

3) Outgoings:
Switch Disconnector Fuse Unit 200A with 160A Fuse links-1No

Switch Disconnector Fuse Unit 100A with 80A Fuse links-2Nos

Switch Disconnector Fuse Unit 100A with 63A Fuse links-3Nos NOS 1 Rs130,000 Rs130,000

3.7 UTIL PANEL isolator 14200


Top/Bottom cable entry for incoming & outgoing feeders Floor mccb 9200
mount type Fabricated out of 16SWG CRCA sheet. 23400 indicator
36260.3305785124 cof
1) Busbars: 37850.3305785124
160A TPN Al. Busbar - 1no.
Earth bus - 25.4 x 3.18mm CU. 0

2) Incomer 1: AMF 350000


160A TPN isolator – 1no SFU 100 14250
160A 4 pole contactor - 1no ISO INCOMER 8800 1050 INDICATION LAMPS 2100
SFU 160 6100 780 C FUSE
3) Incomer 2: CONTA 19200
160A TPN isolator - 1no 398350 1830
160A 4 pole contactor - 1no 903756.5625
Page 7 of 32 TRITECH CORPORATION

ESTIMATE OF QUANTITIES AND RATES FOR HT ELECTRIFICATION OF DD TRADE TOWER AT


KALOOR-KADAVANTHRA ROAD.
SL.NO DESCRIPTION UNIT QTY RATE(RS) AMOUNT(Rs.)
905586.5625
4) AMF Controls
uP based AMF Relay for controlling 2nos Incoming & 1no
outgoing Contactors - 1set
Synchronous timer for 24hour operation - 1nos

Meters & Indications:


Red, Yellow, Blue LED ON, OFF Indication Lamps along
with 3nos 2A Control fuses - 2sets.

5) Outgoings:
Switch Disconnector Fuse Unit 160A with 125A Fuse links-1No

Switch Disconnector Fuse Unit 100A with 63A Fuse links-3Nos NOS 1 Rs905,600 Rs905,600

3.8 UTIL PANEL1 isolator 1725 1050 INDICATION LAMPS


Top/Bottom cable entry for incoming & outgoing feeders Floor mcb 6912 156 C FUSE
mount type Fabricated out of 16SWG CRCA sheet. 8637
19595.19375 1206
1) Busbars: 20801.19375
80A TPN Al. Busbar - 1no.
Earth bus - 25.4 x 3.18mm CU. 0
0
2) Incomer 1:
80A TPN isolator – 1no

Meters & Indications:


Red, Yellow, Blue LED ON, OFF Indication Lamps along
with 3nos 2A Control fuses - 1set.

5) Outgoings:
25A TPN MCB – 6nos NOS 1 21000 Rs21,000
63mcb 3416
3.9 UTIL PANEL2 mcb 3416
Top/Bottom cable entry for incoming & outgoing feeders Floor isolator 3750 1050 INDICATION LAMPS
mount type Fabricated out of 16SWG CRCA sheet. mcb 3456 780 C FUSE
14038
1) Busbars: 31848.7125 1830
125A TPN Al. Busbar - 1no. 33678.7125
Earth bus - 25.4 x 3.18mm CU.
0
2) Incomer 1:
125A TPN isolator – 1no

Meters & Indications:


Red, Yellow, Blue LED ON, OFF Indication Lamps along
Page 8 of 32 TRITECH CORPORATION

ESTIMATE OF QUANTITIES AND RATES FOR HT ELECTRIFICATION OF DD TRADE TOWER AT


KALOOR-KADAVANTHRA ROAD.
SL.NO DESCRIPTION UNIT QTY RATE(RS) AMOUNT(Rs.)
with 3nos 2A Control fuses - 1set.

5) Outgoings:
63A TPN MCB – 2nos
40A TPN MCB – 2nos
32A TPN MCB – 3nos NOS 1 33750 Rs33,750

4) MOTOR STARTERS Rs0


Wall mounting type dust tight and verminproof, Rs0
fabricated out of 16 SWG CRCA sheet, treated and Rs0
painted with 2 coats of primer and two coats of Rs0
paint and shall include the following with Rs0
TPN isolator & illuminated LED type ON Off push Rs0
buttons, Contactors, Overload Relays, Rs0
Power terminals, Control Terminals Rs0
Power and Control Wiring etc. with the following Rs0

STAR DELTA STARTERS


a) 10HP Star Delta starter with Contactor and timer NOS 2 Rs1,600 Rs3,200

b) 7.5HP Star Delta starter with Contactor and timer NOS 2 Rs1,150 Rs2,300

c) 50HP Star Delta Starter with Contactor and Timer NOS 1 Rs7,000 Rs7,000
Rs0
5) 11KV, 3PANEL VCB SUPPLY & ERECTION (11KV PANEL)
Supply, Erection, testing and commissioning of 11KV, 50c/s,630A
350MVA, Panel with 24 Volt DC tripping mechanism with
remote trip facility Indoor, Floor mounting type complete
with Opening, Closing, Tripping and Earthing Mechanisms
and the following with CPRI and CEIG Approval

Incomer
11KV,350MVA,630A VCB -1 No

Ouitgoings
11KV,350MVA,400A LBS without metering - 2nos

The 11KV Panel shall be supplied with Canopy and Outdoor


type Enclosure
Make: UNIPOWER NOS 1 Rs600,000 Rs600,000

6) CAST RESIN TRANSFORMER SUPPLY & ERECTION


6.1 Supply, Erection,Testing and Commissioning of 11KV/433V, 630KVA,
Fire retardant Cast Resin Dry type, Vector group DYN-11,Copper
wound Indoor Transformer with Cable entry provision at 11KV
Page 9 of 32 TRITECH CORPORATION

ESTIMATE OF QUANTITIES AND RATES FOR HT ELECTRIFICATION OF DD TRADE TOWER AT


KALOOR-KADAVANTHRA ROAD.
SL.NO DESCRIPTION UNIT QTY RATE(RS) AMOUNT(Rs.)
side and LT side.as per Electrical Inspectorate Norms
with +5% and -7.5% tapping links with CPRI and CEIG Approval NOS 2 Rs9,000 Rs18,000

7.0 D.G.SET ERECTION


Erection, Testing and commissioning of 125KVA Rs0
415Volts, 3Phase, 50c/s, Diesel Engine coupled Rs0
Alternator working at 0.8 p.f. comprising of Rs0
Starting equipment for the Diesel Engine and Rs0 11kv panel
including the following. Rs0 cast resin xer erection
Rs0 starter rating
Fixing of anitvibration mountings for the D.G.Set. Rs0 panel outs
Fixing of battery including supply of battery stand. Rs0
Assembly & Installation of Acoustic enclosure for DG Set Rs0
Fuel line for the diesel engine. Rs0
Fixing of residential silencer for the engine. Rs0
Erection of Generator Control Panel Rs0
Supply and fixing of MS exhaust line of 35m length Rs0
asbestos rope insulation for 6mtrs of exhaust line (The Rs0
Client will supply only the D.G.set, enclosure, antivibration Rs0
mountings, battery, residential silencer and fuel tank) NOS 1 Rs8,000 Rs8,000

8.0 EARTHING. Rs0


8.1 PLATE EARTH STATION. Rs0
Supply of all materials and providing plate earth Rs0
station with 1200 x 1200 x 12.5 mm. C.I. plate earth Rs0
electrode, water pipe, earthing strips, clamps, funnel, Rs0
terminal Electrodes etc., excavation in all classes of Rs0
soil, filling with alternate layers of charcol and salt and Rs0
back filling ,construction of Earthpit Inspection Rs0
Chamber and Heavy duty C.I. Chequered Rs0
plate for Earthpit Inspection Chamber cover. The Rs0
Earthing Station should conform to IS 3043/1987. NOS 8 Rs9,500 Rs76,000
Rs0
8.2 EARTHING CONDUCTORS. Rs0
Supply,laying & clamping at site Copper earthing Rs0
conductors inclusive of providing earthing Rs0
terminations and bracing of the terminations etc. Rs0
Rs0
a) 10SWG Copper wire. MTRS 1600 Rs55 Rs88,000
Rs0
b) 4SWG Copper wire. MTRS UR Rs150
Rs0
c) 25.4x3mm Copper Strip. MTRS 350 Rs445 Rs155,750

d) 31x3mm Copper Strip. MTRS 110 Rs800 Rs88,000


Page 10 of 32 TRITECH CORPORATION

ESTIMATE OF QUANTITIES AND RATES FOR HT ELECTRIFICATION OF DD TRADE TOWER AT


KALOOR-KADAVANTHRA ROAD.
SL.NO DESCRIPTION UNIT QTY RATE(RS) AMOUNT(Rs.)

9.0 LIGHTNING PROTECTION Rs0


9.1 PIPE EARTH STATION. Rs0
Supply of all materials and providing pipe earth Rs0
station with 2500mm long, 38mm Diameter G.I Rs0
Pipe, earthing strips, clamps, funnel, terminal Rs0
Electrodes etc., excavation in all classes of soil, filling Rs0
with alternate layers of charcol and salt and back Rs0
filling ,construction of Earthpit Inspection Chamber Rs0
and Heavy duty C.I. Chequered plate for Earthpit Rs0
Inspection Chamber cover. The Earthing Station Rs0
should conform to IS 3043/1987. Rs0
Rs0
9.2 Supply & Installation of GI strip type lightning Rs0 114
conductors 25x6mm size MTRS 135 Rs120 16,200 2.85
Rs0
9.3 Supply & Installation of GI strip type lightning Rs0
conductors 32x6mm size MTRS 50 Rs135 6,750

9.4 Supply and installation of Test Joint for Lighting down 0


conductors at 2mtrs from Ground level NOS 4 Rs500 2,000
Rs0
9.5 Supply and installation of Spike for lightning protection system NOS 2 Rs3,000 Rs6,000

10.0 CABLE TRAYS & M.S./ G.I. ITEMS. Rs0


10.1 Supply and Erection of Vertical/Horizontal type Rs0
M.S. Cable Trays and cable supports Rs0
fabricated out of M.S.Angles (ISA) and M.S. flats Rs0
with sufficient width and Spacing between Rs0
successive cross members and supported at Rs0
adequate spacing. The cable trays and supports Rs0
shall be painted with 2coats of Zinc chromate Rs0
primer and 2coats of enamel paint. The design Rs0
of the cable trays and details shall be got approved Rs0
by the Electrical Consultant. KGS 800 Rs52 Rs41,600
Rs0
10.2 Supply,fabrication and installation of 6mm thick Rs0 16.128
chequered plate and filling for fire proof partitions Rs0
between floors in electrical ducts. SQ.MT. 16 Rs3,500 Rs56,000
Rs0 20.25
10.3 Supply,fabrication and installation of cable trench Rs0
covers using 6mm thick MS Chequered plates for Rs0
covering Cable trenches in Electrical switchgear Rs0
and Equipment rooms. SQ.MT 10 Rs2,000 Rs20,000
Rs0
Page 11 of 32 TRITECH CORPORATION

ESTIMATE OF QUANTITIES AND RATES FOR HT ELECTRIFICATION OF DD TRADE TOWER AT


KALOOR-KADAVANTHRA ROAD.
SL.NO DESCRIPTION UNIT QTY RATE(RS) AMOUNT(Rs.)
11.0 MISCELLANEOUS ITEMS. Rs0
Rs0
11.1 Supply and Installation of 2kg Dry Chemical Powder Rs0
type (DCP) fire extinguishers having ISI mark along Rs0
with mounting supports etc. NOS Rs2,000 #VALUE!
Rs0
11.2 Supply and Installation of 5kg Dry Chemical Powder Rs0
type (DCP) fire extinguishers having ISI mark along Rs0
with mounting supports etc. NOS 2 Rs2,500 Rs5,000
Rs0
11.3 Supply of Electrical Grade Rubber Mat suitable for Rs0
11000Volts Switchboards. (6' x 3' x 1/2"). NOS 2 Rs1,500 Rs3,000
Rs0
11.4 Supply of Electrical Grade Rubber Mat suitable for Rs0
440Volts Switchboards. (6' x 3' x 1/4"). NOS 8 Rs1,000 Rs8,000
Rs0
11.5 Supply and installation of 3nos of fire buckets along Rs0
with stand painted with enamel paint of red colour. NOS 2 Rs1,500 Rs3,000
Rs0
11.6 Supply and installation of metal L.T.\HT danger sign Rs0
boards. NOS 15 Rs950 Rs14,250
Rs0
11.7 Supply and installation of L.T. Cable route Rs0
marker. NOS 5 Rs175 Rs875
Rs0
11.8 Earth excavation including back filling without supply Rs0
sand and brick for cable laying. CuMt 15 Rs400 Rs6,000
Rs0
11.9 Earth excavation including back filling with supply of Rs0
sand and brick for cable laying. CuMt UR Rs500
Rs0
11.10 Supply, Installation & wiring of emergency trip push button station NOS 1 Rs1,500 Rs1,500
Rs0
12.0 DOCUMENTS & APPROVAL. Rs0
Preparation of necessary forms, documents, Rs0
drawings etc. and procuring approval and Rs0
energisation certficate from the Electrical Inspectorate, Rs0
and getting power from KSEB. All expenses except statutory Rs0
charges shall be met by the Contractor LS 1 Rs20,000 Rs20,000
Rs0
TOTAL ELECTRIFICATION COST #VALUE!

SUMMARY OF ELECTRIFICATION COST


1) HT Electrifcation Contract Value(Above) LS 1 #VALUE! #VALUE!
Page 12 of 32 TRITECH CORPORATION

ESTIMATE OF QUANTITIES AND RATES FOR HT ELECTRIFICATION OF DD TRADE TOWER AT


KALOOR-KADAVANTHRA ROAD.
SL.NO DESCRIPTION UNIT QTY RATE(RS) AMOUNT(Rs.)
2) Cast Resin Transformer 11KV/433V, 630KVA NOS 2 Rs950,000 Rs1,900,000 132,000.00 95,000.00
3) DG Set 125KVA with Enclosure NOS 1 Rs700,000 Rs700,000 132,000.00 95,000.00
4) Miscellaneous expenses, Consulting fee etc. LS 1 Rs125,000 Rs125,000
TOTAL ELECTRIFICATION COST #VALUE!
Page 13 of 32 TRITECH CORPORATION

SCHEDULE OF QUANTITIES FOR ELECTRIFICATION OF PLATINUM PRIDE AT ELAMAKKARA.


SL.NO DESCRIPTION UNIT QTY RATE(RS) AMOUNT(Rs.)
LT ELECTRIFICATION
1.0 POINT WIRING USING MODULAR SWITCHES
Supply and Point wiring for 230Volts A.C Circuits
through PVC conduits, 1.0 sq.mm(14/0.3)
single core PVC insulated copper wire for distribution
16SWG bare Copper conductor for continuous
earthing, 6A control switches, 6A
sockets, MS mounting boxes etc. as necessary for
the following items.The wiring should be done
over the surface / open/ concealed type with modular
switches & Sockets (including conduits)

1.1 1 No. light point controlled by 1 No 6A, SP Switch.

Supply: NOS 1275

Labour / Installation / Erection: NOS 1275

1.2 1 No. light point controlled by 2 Nos. 6A, SP Switch.

Supply: NOS 60

Labour / Installation / Erection: NOS 60

1.3 2 Nos. light points group controlled by 1 No 6A, SP Switch.

Supply: NOS 15

Labour / Installation / Erection: NOS 15

1.4 3 Nos. light points group controlled by 1 No 6A, SP Switch.

Supply: NOS 25

Labour / Installation / Erection: NOS 25

1.5 4 Nos. light points group controlled by 1 No 6A, SP Switch.

Supply: NOS 15

Labour / Installation / Erection: NOS 15

1.6 1 No, Ceiling fan point along with 1 No 250W 2 module step type
Electronic Fan Regulator, controlled by 1 No 6A, SP Switch.

Supply: NOS 165

Labour / Installation / Erection: NOS 165

1.7 1 No, Ceiling fan point along with 1 No 250W 2 module step type
Electronic Fan Regulator, controlled by 2 No 6A, SP Switch.

Supply: NOS 160

Labour / Installation / Erection: NOS 160

1.8 1 No, Exhaust fan point controlled by 1 No 6A, SP Switch.

Supply: NOS 220

Labour / Installation / Erection: NOS 220


Page 14 of 32 TRITECH CORPORATION

SCHEDULE OF QUANTITIES FOR ELECTRIFICATION OF PLATINUM PRIDE AT ELAMAKKARA.


SL.NO DESCRIPTION UNIT QTY RATE(RS) AMOUNT(Rs.)
1.9 1 No, 6A Socket outlet controlled by 1 No 6A,
SP Switch along with other switches.

Supply: NOS 600

Labour / Installation / Erection: NOS 600

1.10 1 No, 6A Socket outlet controlled by 1 No 6A,


SP in an independent position.

Supply: NOS 385

Labour / Installation / Erection: NOS 385

1.11 1 No. Calling bell point controlled by 1 No 6A, SP Switch.

Supply: NOS 54

Labour / Installation / Erection: NOS 54

2.0 CIRCUIT & POWER POINT WIRING


Supply and Installation charges for laying and
Termination of PVC Insulated copper
wires through PVC conduits for the following
type of wiring

2.1 Circuit mains wiring using two runs of 1.5 sq.mm


PVC insulated copper wires alongwith one run of
14SWG bare copper conductor for continuous 'earthing

Supply: MTRS 7100

Labour / Installation / Erection: MTRS 7100

2.2 Power point wiring using two runs of 2.5 sq.mm PVC
insulated copper wires alongwith one run of 14SWG
bare copper conductor for continuous earthing.

Supply: MTRS 3650

Labour / Installation / Erection: MTRS 3650

2.3 Power point wiring using two runs of 4 sq.mm PVC


insulated copper wires alongwith one run of 14SWG
bare copper conductor for continuous earthing.

Supply: MTRS 2150

Labour / Installation / Erection: MTRS 2150

2.4 DB incomer wiring using four runs of 6 sq.mm PVC


insulated copper wires alongwith two run of 10SWG
bare copper conductor for continuous earthing.

Supply: MTRS 460

Labour / Installation / Erection: MTRS 460

2.5 DB incomer wiring using four runs of 10 sq.mm PVC


insulated copper wires alongwith two run of 10SWG
bare copper conductor for continuous earthing.
Page 15 of 32 TRITECH CORPORATION

SCHEDULE OF QUANTITIES FOR ELECTRIFICATION OF PLATINUM PRIDE AT ELAMAKKARA.


SL.NO DESCRIPTION UNIT QTY RATE(RS) AMOUNT(Rs.)
Supply: MTRS UR

Labour / Installation / Erection: MTRS UR

3.0 POWER POINTS


Supply and Installation of the following modular type 440/230Volts A.C
Power Sockets, Controlling Switches, bell pushes
MCBs etc. in combined or independant position
including mounting boxes for Sockets, Controlling
Switches,bell pushes, MCBs, termination of incoming
and outgoing wires etc.

3.1 1 No,16A Socket outlet and 1No 16A SP Switch


controlling the Socket outlet in independent position.

Supply: NOS 265

Labour / Installation / Erection: NOS 265

3.2 Supply and fixing of GI mounting box and blank plate for 1 No,16A
Socket outlet and 1No 16A SP Switch

Supply: NOS UR

Labour / Installation / Erection: NOS UR

3.3 1 No, 32A, flush type DP Switch.

Supply: NOS 155

Labour / Installation / Erection: NOS 155

3.4 GI mounting box and blank plate for 30A flush type DP switch

Supply: NOS UR

Labour / Installation / Erection: NOS UR

4.0 TELEPHONE WIRING.


4.1 Supply & fixing of 2 x RJ11(DOT/ Intercom) Dual
telephone sockets, recessed G.I.mounting box and
front plate for Telephone sockets and terminating two pair
telephone wires of the incoming line from telephone
terminal connector located elsewhere.

Supply: NOS 54

Labour / Installation / Erection: NOS 54

4.2 Supply & fixing of RJ11 Telephone Sockets


recessed G.I.mounting box and front plate
for Telephone sockets and terminating two pair
telephone wires of the incoming line from telephone
terminal connector located elsewhere.

Supply: NOS 60

Labour / Installation / Erection: NOS 60

4.3 Supply & wiring of Telephone socket using one run 0.5mm
annealed CU two pair unarmoured telephone wire through
20mm conduits wire upto the Terminal Connector for DOT/
Intercom (including conduits)
Page 16 of 32 TRITECH CORPORATION

SCHEDULE OF QUANTITIES FOR ELECTRIFICATION OF PLATINUM PRIDE AT ELAMAKKARA.


SL.NO DESCRIPTION UNIT QTY RATE(RS) AMOUNT(Rs.)

Supply: MTRS 1700

Labour / Installation / Erection: MTRS 1700

4.4 Supply and fixing of 20 pair terminal connector(IDF) for DOT


in a suitable GI mounting box, including termination
of conduits, two pair telephone wires, incoming Multicore
Telephone cable etc.

Supply: NOS 4

Labour / Installation / Erection: NOS 4

4.5 Supply and fixing of 20 pair terminal connector(IDF) for


Intercom, in a suitable GI mounting box, including termination
of conduits, two pair telephone wires, incoming Multicore
Telephone cable etc.

Supply: NOS 4

Labour / Installation / Erection: NOS 4

4.6 Supply and fixing of 10 pair terminal connector(IDF) for DOT


in a suitable GI mounting box, including termination
of conduits, two pair telephone wires, incoming Multicore
Telephone cable etc.

Supply: NOS 1

Labour / Installation / Erection: NOS 1

4.7 Supply and fixing of 10 pair terminal connector(IDF) for


Intercom, in a suitable GI mounting box, including termination
of conduits, two pair telephone wires, incoming Multicore
Telephone cable etc.

Supply: NOS 1

Labour / Installation / Erection: NOS 1

4.8 Supply and fixing of lockable Main telephone terminal Box


(MDF) for DOT /Intercom, dust tight and vermin proof fabricated
out of 16SWG CRCA Sheet treated and painted with
approved enamel paint suitable for 1sets of 100
pair of outgoing telephone cables. The
work should also include supply of all materials and
termination of cables, wires and earthing.

Supply: NOS 2

Labour / Installation / Erection: NOS 2

4.9 Supply & laying of telephone cable using one run


of 100 pair Armored telephone cable from Terminal
Connector upto the Main Telephone Terminal Connector
Located elsewhere along with 1run of 16SWG
bare copper conductor for earthing

Supply: MTRS 50

Labour / Installation / Erection: MTRS 50


Page 17 of 32 TRITECH CORPORATION

SCHEDULE OF QUANTITIES FOR ELECTRIFICATION OF PLATINUM PRIDE AT ELAMAKKARA.


SL.NO DESCRIPTION UNIT QTY RATE(RS) AMOUNT(Rs.)
4.10 Supply & laying of telephone cable using one run
of 10 pair Armored telephone cable from Terminal
Connector upto the Main Telephone Terminal Connector
Located elsewhere along with 1run of 16SWG
bare copper conductor for earthing

Supply: MTRS 65

Labour / Installation / Erection: MTRS 65

4.11 Supply & laying of telephone cable using one run


of 20 pair Armored telephone cable from Terminal
Connector upto the Main Telephone Terminal Connector
Located elsewhere along with 1run of 16SWG
bare copper conductor for earthing

Supply: MTRS 125

Labour / Installation / Erection: MTRS 125

5.0 TELEVISION WIRING.


5.1 Supply of all materials and fixing of co-axial TV
sockets, recessed G.I.mounting box and front plate
for TV sockets and terminating RG 6 TV cable.

Supply: NOS 108

Labour / Installation / Erection: NOS 108

5.2 Supply and laying of RG 6/RG 8 Co-axial TV cable using 20mm


PVC conduit.

Supply: MTRS 1500

Labour / Installation / Erection: MTRS 1500

5.3 Supply and laying of RG 11 Co-axial TV cable using


25mm PVC conduit.

Supply: MTRS 45

Labour / Installation / Erection: MTRS 45

5.4 Supply and fixing of Multi adaptor in each floor

Supply: NOS 9

Labour / Installation / Erection: NOS 9

5.5 Supply and fixing of Line / Hybrid Amplifier

Supply: NOS 1

Labour / Installation / Erection: NOS 1

6.0 MCB DISTRIBUTION BOARDS AND ENCLOSURES


Supply,Erection, Testing and Commissioning
of the following recessed, double door type
MCB Distribution Boards with RCBO / Isolator
incomer side and MCBs on the outgoing side.
The work includes, termination of incoming
and outgoing wires, cables, conduits and earh wire.
Page 18 of 32 TRITECH CORPORATION

SCHEDULE OF QUANTITIES FOR ELECTRIFICATION OF PLATINUM PRIDE AT ELAMAKKARA.


SL.NO DESCRIPTION UNIT QTY RATE(RS) AMOUNT(Rs.)

6.1 6WAY TPN MCB D.B. - CONSUMER DB1


6Way TPN MCB DB with Three phase incomer and
single phase out goings with loose wire box as per the
following.

Incomer:
ELCB 40A, 4Pole with
O/C & 30mA Earth Leakage trip - 1No.

Outgoings:
MCB 6A , SP - 6nos.
MCB 10A , SP - 6nos.
MCB 16A , SP - 6nos.

Supply: NOS 54

Labour / Installation / Erection: NOS 54

6.2 8WAY TPN MCB D.B. - COMMON


8Way TPN MCB DB with three phase incomer and
single phase out goings as per the following.

Incomer:
ELCB 40A, 4Pole with
O/C & 30mA Earth Leakage trip - 1No.

Outgoings:
MCB 6A , SP - 20nos.

Supply: NOS 1

Labour / Installation / Erection: NOS 1

6.3 4WAY TPN MCB D.B. EMERGENCY


4Way TPN MCB DB with three phase incomer and
single phase out goings as per the following.

Incomer:
ELCB 40A, 4Pole with
O/C & 30mA Earth Leakage trip - 1No.

Outgoings:
MCB 6A , SP - 12nos.
Supply: NOS 5

Labour / Installation / Erection: NOS 5

6.4 6WAY TPN MCB D.B. EXTERIOR


6Way TPN MCB DB with three phase incomer and
single phase out goings as per the following.

Incomer:
ELCB 40A, 4Pole with
O/C & 30mA Earth Leakage trip - 1No.

Outgoings:
MCB 6A , SP - 12nos.
Supply: NOS 1

Labour / Installation / Erection: NOS 1


Page 19 of 32 TRITECH CORPORATION

SCHEDULE OF QUANTITIES FOR ELECTRIFICATION OF PLATINUM PRIDE AT ELAMAKKARA.


SL.NO DESCRIPTION UNIT QTY RATE(RS) AMOUNT(Rs.)
6.5 Supply and installation of Load limiter cum automatic changeover
with 2 nos 2 pole 30A Changeover relay in suitable enclosure NOS 54

7.0 LIGHTING FIXTURES/OTHER FIXTURES/


STREET LIGHTING FIXTURES AND POLES.
Installation of the following outdoor/indoor type light
fittings, including supply of all materials required for
erection, all wiring, terminations and
interconnections, earthing from the terminal block
/ceiling rose to the light fitting/luminaire. All
minor civil works such as chasing , foundations
etc. shall be under the scope of the Contractor(Only
luminaire will be supplied by the client).

7.1 1X40W Fluorescent Surface mounted luminar with acrylic Diffuser NOS 25

7.2 2X18 W CFL surface mounted low glare mirror optic luminare NOS 95

7.3 4X18 W CFL surface mounted low glare mirror optic luminare NOS UR

7.4 1x18W GLS surface mounted luminare NOS 5

7.5 1x11W CFL surface mounted mirror luminare NOS UR

7.6 Gate light NOS 2

7.7 1x60W bulk hed fixture NOS 20

8.0 CEILING / EXHAUST / WALL FANS


Installation and testing of the following ceiling fans,
exhaust fans, Wall fans etc. as required with all
wiring,terminations and interconnections including
earthing from terminal block / ceiling rose to the fan.

8.1 1no 60Watt ceiling fan of 1200mm Sweep. NOS 2

8.2 1no Light Duty Exhaust fan of 300mm Sweep. NOS 3

9.0 FABRICATED BOX


Supply and Installation of Cable termination box for
joining incoming PVC Insulated Armoured Aluminium
Cables with PVC Insulated Unsheathed Copper wires
with 4nos 32A strip type terminal connectors suitable
for 6sq.mm cables and having a size of
150mm width x 150 height x 50mm depth fabricated
out of 18SWG CRCA hot dip galvanised sheet and
painted with enamel paint of approved colour. NOS 54

TOTAL LT ELECTRIFICATION COST

HT ELECTRIFICATION
10.0 SUPPLY & LAYING OF CABLES
Supply,Laying, testing and commissioning of the
following PVC Insulated Armoured Aluminium
L.T.Cables (AYWY/AYFY) /XLPE (A2XCEFY) H.T
Cables through excavated trenches, built up cable
trenches, cable trays, hume pipes,including supply
and fixing of clamps, nuts and bolts, screws, Rs0
identification tags, route markers etc. required for Rs0
clamping intervals as necessry. Rs0
Page 20 of 32 TRITECH CORPORATION

SCHEDULE OF QUANTITIES FOR ELECTRIFICATION OF PLATINUM PRIDE AT ELAMAKKARA.


SL.NO DESCRIPTION UNIT QTY RATE(RS) AMOUNT(Rs.)
10.1 H.T. 11KV(E) CABLES
a) 3Cx300 SQ.MM. MTRS UR

b) 3Cx185 SQ.MM. MTRS 60 Rs0

10.2 L.T.CABLES Rs0


a) 3.5CX400 SQMM AYFY MTRS 25 Rs0

b) 3.5CX240 SQMM AYFY MTRS 70 Rs0

c) 3.5CX185 SQMM AYFY MTRS UR

d) 3.5CX120 SQMM AYFY MTRS 35 Rs0

e) 3.5CX70 SQMM AYFY MTRS 200 Rs0

f) 3.5CX35 SQMM AYFY MTRS 65 Rs0

g) 4CX10 SQMM AYFY MTRS 2750 Rs0


Rs0
h) 4C X 6.0 SQ.MM AYFY MTRS 80 Rs0
Rs0
11.0 CABLE TERMINATION Rs0
H.T.CABLE TERMINATION Rs0
Supply & Labour charges for termination of HT cables Rs0
using Epoxy type 11KV(E), XLPE Cable termination Rs0
kits, Cable identification tags etc. for the following Rs0
Cross linked Polyethylene Insulated (XLPE)and Rs0
Armoured Aluminium H.T.Cables (A2XCEFY) . Rs0
Rs0
11.1 INDOOR TYPE: Rs0
3Cx300SQ.MM. NOS. UR Rs0

3CX185SQ.MM. NOS 1 Rs0

11.2 OUTDOOR TYPE: Rs0


3Cx300SQ.MM. NOS. UR Rs0

3Cx185SQ.MM. NOS. 1 Rs0

11.3 L.T.CABLE TERMINATION Rs0


Supply of all materials and termination of the Rs0
following PVC Insulated Armoured Aluminium Rs0
L.T.Cables (AYWY / AYFY) using single compression Rs0
type cadmium plated brass cable glands, Copper Rs0
crimped type cable lugs, cable identification Rs0
tags and including gland earthing using copper Rs0
conductor of adequate size , AL-CU strip for Rs0
termination of Cables etc. Rs0
Rs0
a) 3.5CX400 SQMM AYFY NOS. 4 Rs0
Rs0
b) 3.5CX240 SQMM AYFY NOS. 6 Rs0
Rs0
c) 3.5CX185 SQMM AYFY NOS UR
Rs0
d) 3.5CX120 SQMM AYFY NOS. 4 Rs0
Rs0
e) 3.5CX70 SQMM AYFY NOS. 20 Rs0
Rs0
f) 3.5CX35 SQMM AYFY NOS. 4 Rs0
Rs0
Page 21 of 32 TRITECH CORPORATION

SCHEDULE OF QUANTITIES FOR ELECTRIFICATION OF PLATINUM PRIDE AT ELAMAKKARA.


SL.NO DESCRIPTION UNIT QTY RATE(RS) AMOUNT(Rs.)
g) 4CX10 SQMM AYFY NOS. 120 Rs0
Rs0
h) 4C X 6.0 SQ.MM AYFY NOS. 4 Rs0
Rs0
Design, fabrication, supply, erection , testing and Rs0
commissioning of following Cubicle type, fully Rs0
compartmentalised LT Switchboards dust tight Rs0
and vermin proof, fabricated out of 14/16 SWG Rs0
CRCA sheet, chemically treated and painted with Rs0
2 coats of primer and two coats of stoving Rs0
enamel paint of approved shade. The Rs0
Switchboards should have a Set of suitably Rs0
rated TPN Aluminium busbars with the Rs0
specified current and fault level, Insulated with Rs0
heat shrinkable, color coded PVC Sleeves and Rs0
supported using DMC/ SMC Pillar or Finger Rs0
type busbar supports. The design should be Rs0
as per the standards of the State Electrical Rs0
Inspectorate. Rs0
Rs0
12.1 MSB
Top/Bottom cable entry for incoming and outgoing
feeders. Fabricated out of 16SWG CRCA sheet

1) Busbars:
630A TPN Al. Busbar - 1no.
Earth bus - 31 x 3CU.

2) Incomer :
630A TP MCCB 35KA Extra Current Limiting type
set at 533A with O/C, S/C and E/F releases- 1no

Meters & Indications:


Digital Combination Meter(EM 6400 conzerv or equivalent model)
with PF Meter KW meter, Ammeter, 3nos 2A Control fuse and
3nos metering CTs 'Class 1.0 15VA, 600/5A, - 1set

Red, Yellow, Blue , ON, OFF, TRIP LED Indication Lamps along
with 3nos 2A Control fuses & toggle switch - 1set.

3Phase Digital Voltmeter 0-500V Model DM3256 of Conzerv or


equivalent and 3Nos of 2A Control fuses - 1set

3) Outgoings:
Moulded Case Circuit Breaker TP, 250A, 35KA Set 200A Rs0
with Electronic release FD KIT, OC, SC, EF, Shunt & Isolation
duty Current Limiting type - 3nos

Moulded Case Circuit Breaker TP, 160A, Set 125A Rs0


with Electronic release FD KIT, OC, SC, EF, Shunt & Isolation Rs0
duty Current Limiting type & 125A Cut Out fuse and Rs0
1no KSEB's three phase KWH Meter with 3nos 2A Control
fuse and 1nos metering CTs 'Class 1.0 15VA, 75/5A, - 1set

Provision shall be made for sealing of all shutters. NOS 1 Rs0

12.2 FSB1 TO FSB3


Top/Bottom cable entry for incoming and outgoing
feeders. Fabricated out of 16SWG CRCA sheet

1) Busbars:
200A TPN Al. Busbar - 1no.
Page 22 of 32 TRITECH CORPORATION

SCHEDULE OF QUANTITIES FOR ELECTRIFICATION OF PLATINUM PRIDE AT ELAMAKKARA.


SL.NO DESCRIPTION UNIT QTY RATE(RS) AMOUNT(Rs.)
Earth bus - 25.4 x 3.175mm CU.

2) Incomer:
200A TPN isolator - 1no.

Meters & Indications:


Red, Yellow, Blue LED Indication Lamps along with 3nos
2A Control fuses - 1set.

3) Outgoings:
Moulded Case Circuit Breaker TP, 125A, 35KA Set 100A Rs0
with Electronic release FD KIT, OC, SC, EF, Shunt & Isolation Rs0
duty Current Limiting type - 3nos

Provision shall be made for sealing of all shutters. NOS 3 Rs0

12.3 SSB1 TO SSB9


Top/Bottom cable entry for incoming and outgoing
feeders. Fabricated out of 16SWG CRCA sheet

1) Busbars:
100A TPN Al. Busbar - 1no.
Earth bus - 25.4 x 3.175mm CU.

2) Incomer:
100A TPN isolator - 1no.

Meters & Indications:


Red, Yellow, Blue LED Indication Lamps along
with 3nos 2A Control fuses - 1set.

3) Outgoings:
32A TPN MCB, 32A Cutout fuses and 1no KSEB's three phase Rs0
KWH Meter - 6nos Rs0

Provision shall be made for sealing of all shutters. NOS 9 Rs0

12.4 DG SB
Top/Bottom cable entry for incoming & outgoing feeders Floor
mount type Fabricated out of 16SWG CRCA sheet.

1) Busbars:
160A TPN Al. Busbar - 1no.
Earth bus - 25.4 x 3.18mm CU.

2) Incomer:
160A TPN isolator - 1no.

Meters & Indications:


Red, Yellow, Blue,ON,OFF, TRIP LED Indication Lamps along with 3nos
2A Control fuses - 1set.

3) Outgoings:
Moulded Case Circuit Breaker TP, 160A, Set 125A
with Electronic release FD KIT, OC, SC, EF, Shunt & Isolation
duty Current Limiting type - 1no. Rs0

Moulded Case Circuit Breaker TP, 100A, Set 63A


with Electronic release FD KIT, OC, SC, EF, Shunt & Isolation
duty Current Limiting type - 1no.

100A TPN isolator - 1no.


Page 23 of 32 TRITECH CORPORATION

SCHEDULE OF QUANTITIES FOR ELECTRIFICATION OF PLATINUM PRIDE AT ELAMAKKARA.


SL.NO DESCRIPTION UNIT QTY RATE(RS) AMOUNT(Rs.)
NOS 1 Rs0
12.5 UTIL PANEL
Top/Bottom cable entry for incoming & outgoing feeders Floor
mount type Fabricated out of 16SWG CRCA sheet.

1) Busbars:
125A TPN Al. Busbar - 1no.
Earth bus - 25.4 x 3.18mm CU.

2) Incomer 1:
125A TPN isolator - 1no
125A 4 pole contactor -1no
(electromechanically interlocked)

3) Incomer 2:
125A TPN isolator - 1no
125A 4 pole contactor - 1no
(electromechanically interlocked)

4) AMF Controls
uP based AMF Relay for controlling 2nos Incoming & 1no
outgoing Contactors - 1set
Synchronous timer for 24hour operation - 1nos

Meters & Indications:


Red, Yellow, Blue LED ON, OFF Indication Lamps along
with 3nos 2A Control fuses - 2sets.

5) Outgoings:
32A TPN MCB - 3nos
25A TPN MCB - 4nos
63A TPN MCB - 1no NOS 1 Rs0

12.6 LIFT PANEL(Control Panel)-1


Wall Mounting Panel board with
Top/Bottom cable entry for incoming and outgoing
feeders. Fabricated out of 16SWG CRCA sheet

1) Busbars:
32A TPN Al. Busbar - 1no
Earth bus - 25.4 x 3.15mm CU.

2) Incomer:
32A TPN Isolator -1no

Meters & Indications:


Red, Yellow, Blue LED Indication Lamps along with 3nos
2A Control fuses & toggle switch - 1set.

3) Outgoings:
25A 4P RCBO ,100mA - 1no
10A 2P RCBO, 30mA - 1no NOS 2 Rs0

13.0 MOTOR STARTERS Rs0


Wall mounting type dust tight and verminproof, Rs0
fabricated out of 16 SWG CRCA sheet, treated and Rs0
painted with 2 coats of primer and two coats of Rs0
paint and shall include the following with Rs0
TPN isolator & illuminated LED type ON Off push Rs0
buttons, Contactors, Overload Relays, Rs0
Power terminals, Control Terminals Rs0
Power and Control Wiring etc. with the following Rs0
Page 24 of 32 TRITECH CORPORATION

SCHEDULE OF QUANTITIES FOR ELECTRIFICATION OF PLATINUM PRIDE AT ELAMAKKARA.


SL.NO DESCRIPTION UNIT QTY RATE(RS) AMOUNT(Rs.)

STAR DELTA STARTERS


a) 20HP Star Delta starter with Contactor and timer NOS 1 Rs0

b) 7.5HP Star Delta starter with Contactor and timer NOS 1 Rs0

c) 5HP DOL starter with Contactor and timer NOS 4 Rs0


Rs0
14.0 UNITISED SUBSTATION ERECTION Rs0
Erection, tesing and commissioning of the following Rs0
Unitised Substation with Cast resin type Indoor Rs0
Transformer 11KV/433V 400KVA, Air break 11KV SFU Rs0
Panel 400Amps, 350MVA with 24V dc Tripping with Accessories Rs0
(The client will supply only The Unitised Substation Rs0
All other items shall be supplied by the Contractor). NOS 1 Rs0

15.0 D.G.SET ERECTION


Erection, Testing and commissioning of 62.5KVA Rs0
415Volts, 3Phase, 50c/s, Diesel Engine coupled Rs0
Alternator working at 0.8 p.f. comprising of Rs0
Starting equipment for the Diesel Engine and Rs0
including the following. Rs0
Rs0
Fixing of anitvibration mountings for the D.G.Set. Rs0
Fixing of battery including supply of battery stand. Rs0
Assembly & Installation of Acoustic enclosure for DG Set Rs0
Fuel line for the diesel engine. Rs0
Fixing of residential silencer for the engine. Rs0
Erection of Generator Control Panel Rs0
Supply and fixing of MS exhaust line of 35m length Rs0
asbestos rope insulation for 6mtrs of exhaust line (The Rs0
Client will supply only the D.G.set, enclosure, antivibration Rs0
mountings, battery, residential silencer and fuel tank) NOS 1 Rs0

16.0 EARTHING. Rs0


16.1 PLATE EARTH STATION. Rs0
Supply of all materials and providing plate earth Rs0
station with 1200 x 1200 x 12.5 mm. C.I. plate earth Rs0
electrode, water pipe, earthing strips, clamps, funnel, Rs0
terminal Electrodes etc., excavation in all classes of Rs0
soil, filling with alternate layers of charcol and salt and Rs0
back filling ,construction of Earthpit Inspection Rs0
Chamber and Heavy duty C.I. Chequered Rs0
plate for Earthpit Inspection Chamber cover. The Rs0
Earthing Station should conform to IS 3043/1987. NOS 8 Rs0
Rs0
16.2 EARTHING CONDUCTORS. Rs0
Supply,laying & clamping at site Copper earthing Rs0
conductors inclusive of providing earthing Rs0
terminations and bracing of the terminations etc. Rs0
Rs0
a) 10SWG Copper wire. MTRS 1600 Rs0
Rs0
b) 4SWG Copper wire. MTRS UR
Rs0
c) 25.4x3mm Copper Strip. MTRS 350 Rs0

d) 31x3mm Copper Strip. MTRS 110 Rs0

17.0 LIGHTNING PROTECTION Rs0


17.1 PIPE EARTH STATION. Rs0
Supply of all materials and providing pipe earth Rs0
Page 25 of 32 TRITECH CORPORATION

SCHEDULE OF QUANTITIES FOR ELECTRIFICATION OF PLATINUM PRIDE AT ELAMAKKARA.


SL.NO DESCRIPTION UNIT QTY RATE(RS) AMOUNT(Rs.)
station with 2500mm long, 38mm Diameter G.I Rs0
Pipe, earthing strips, clamps, funnel, terminal Rs0
Electrodes etc., excavation in all classes of soil, filling Rs0
with alternate layers of charcol and salt and back Rs0
filling ,construction of Earthpit Inspection Chamber Rs0
and Heavy duty C.I. Chequered plate for Earthpit Rs0
Inspection Chamber cover. The Earthing Station Rs0
should conform to IS 3043/1987. NOS 4 Rs0
Rs0
17.2 Supply & Installation of GI strip type lightning Rs0
conductors 25x3mm size MTRS 135 0
Rs0
17.3 Supply & Installation of GI strip type lightning Rs0
conductors 32x6mm size MTRS 56 0

17.4 Supply and installation of Test Joint for Lighting down 0


conductors at 2mtrs from Ground level NOS 4 0
Rs0
17.5 Supply and installation of Spike for lightning protection system NOS 2 Rs0

18.0 CABLE TRAYS & M.S./ G.I. ITEMS. Rs0


18.1 Supply and Erection of Vertical/Horizontal type Rs0
M.S. Cable Trays and cable supports Rs0
fabricated out of M.S.Angles (ISA) and M.S. flats Rs0
with sufficient width and Spacing between Rs0
successive cross members and supported at Rs0
adequate spacing. The cable trays and supports Rs0
shall be painted with 2coats of Zinc chromate Rs0
primer and 2coats of enamel paint. The design Rs0
of the cable trays and details shall be got approved Rs0
by the Electrical Consultant. KGS 800 Rs0
Rs0
18.2 Supply,fabrication and installation of 6mm thick Rs0
chequered plate and filling for fire proof partitions Rs0
between floors in electrical ducts. SQ.MT. 16 Rs0
Rs0
18.3 Supply,fabrication and installation of cable trench Rs0
covers using 6mm thick MS Chequered plates for Rs0
covering Cable trenches in Electrical switchgear Rs0
and Equipment rooms. SQ.MT 10 Rs0

19.0 MISCELLANEOUS ITEMS. Rs0


Rs0
19.1 Supply and Installation of 2kg Dry Chemical Powder Rs0
type (DCP) fire extinguishers having ISI mark along Rs0
with mounting supports etc. NOS 5 Rs0
Rs0
19.2 Supply and Installation of 5kg Dry Chemical Powder Rs0
type (DCP) fire extinguishers having ISI mark along Rs0
with mounting supports etc. NOS 2 Rs0
Rs0
19.3 Supply of Electrical Grade Rubber Mat suitable for Rs0
11000Volts Switchboards. (6' x 3' x 1/2"). NOS 2 Rs0
Rs0
19.4 Supply of Electrical Grade Rubber Mat suitable for Rs0
440Volts Switchboards. (6' x 3' x 1/4"). NOS 8 Rs0
Rs0
19.5 Supply and installation of 3nos of fire buckets along Rs0
with stand painted with enamel paint of red colour. NOS 2 Rs0
Rs0
19.6 Supply and installation of metal L.T.\HT danger sign Rs0
boards. NOS 15 Rs0
Page 26 of 32 TRITECH CORPORATION

SCHEDULE OF QUANTITIES FOR ELECTRIFICATION OF PLATINUM PRIDE AT ELAMAKKARA.


SL.NO DESCRIPTION UNIT QTY RATE(RS) AMOUNT(Rs.)
Rs0
19.7 Supply and installation of L.T. Cable route Rs0
marker. NOS 5 Rs0
Rs0
19.8 Earth excavation including back filling without supply Rs0
sand and brick for cable laying. CuMt 15 Rs0
Rs0
19.9 Earth excavation including back filling with supply of Rs0
sand and brick for cable laying. CuMt UR
Rs0
19.10 Supply, Installation & wiring of emergency trip push button station NOS 1 Rs0
Rs0
20.0 DOCUMENTS & APPROVAL. Rs0
Preparation of necessary forms, documents, Rs0
drawings etc. and procuring approval and Rs0
energisation certficate from the Electrical Inspectorate, Rs0
and getting power from KSEB. All expenses except statutory Rs0
charges shall be met by the Contractor LS 1 Rs0
Rs0
TOTAL ELECTRIFICATION COST Rs0
Page 27 of 32 TRITECH CORPORATION

ROUGH ELECTRICAL LOAD CALCULATION FOR PROPOSED APARTMENT FOR PLATINUM


PRIDE
Sl.no Description Qty Watts Load(Watts) CL(KW) MD(KW)

A) TYPICAL FLOOR 1ST TO 9TH


A TYPE
1 CFL.Pendant 1X18W Ceiling Mount 3 18 54 1L
2 CFL 1X11W Mirror lamp 4 11 44 2S
3 Flourescent lamp 1X40W Wall Mount 6 40 240 F1S
4 18 W GLS Lamp 10 18 180 F2S
5 CFL 2X18W Round False Ceiling Mount 3 36 108 EX
6 Chandlier 1 150 150 16A
7 Exhaust fan 4 60 240 30A
8 Ceiling fan 6 60 360 6AIND
9 6A socket 15 60 900 6ADEP
10 16A socket outlet 2 500 1000
11 16A socket Outlet(geyser) 3 1000 3000
12 30A DP switch 3 2250 6750

LOAD PER FLAT 13026


TOTAL NO.OF FLATS PER FLOOR 5 65130
TOTAL LOAD 9 586.17 234.47

B) TYPICAL FLOOR 1ST TO 9TH


B TYPE
1 CFL.Pendant 1X18W Ceiling Mount 3 18 54 1L
2 CFL 1X11W Mirror lamp 4 11 44 2S
3 Flourescent lamp 1X40W Wall Mount 6 40 240 F1S
4 18 W GLS Lamp 10 18 180 F2S
5 CFL 2X18W Round False Ceiling Mount 3 36 108 EX
6 Chandlier 1 150 150 16A
7 Exhaust fan 4 60 240 30A
8 Ceiling fan 6 60 360 6AIND
9 6A socket 15 60 900 6ADEP
10 16A socket outlet 2 500 1000
11 16A socket Outlet(geyser) 2 1000 2000
12 30A DP switch 2 2250 4500

LOAD PER FLAT 9776


TOTAL NO.OF FLATS PER FLOOR 1 9776
TOTAL LOAD 9 87.98 35.19
E UTILITIES
a) PARKING & COMMON AREA( PASSAGE )
1 Flourescent lamp 1X40W Ceiling Mount 15 40 600
2 2x18W CFL Square Ceiling Mount 25 36 900
LOAD 1500 1.50 1.50

d) Exterior lighting 15 150 2250 2.25 2.25

f) Lift1 1 5595 5595 5.60 5.60


f) Lift2 1 3730 3730 3.73 3.73
g) Lift Light 20 60 1200 1.20 1.20
h) Lift Socket 20 60 1200 1.20 1.20
i) Water Pump 2 3730 7460 7.46 3.73
i) STP 1 3730 3730 3.73 3.73
j) Fire Pump (20HP) 1 14920 14920
j) jockey Pump (5HP) 1 3730 3730

F) EMERGENCY LOADS
1ST TO 14THFLOOR
1 Total Flats 54 300 16200
16200
TOTAL EMERGENCY LOAD 1 16.20 16.20

DEMAND LOAD (KW) 39.14


DEMAND LOAD , KVA 48.92
CONSIDERING 15% DERATING (85% CAPACITY) 57.55
Page 28 of 32 TRITECH CORPORATION

ROUGH ELECTRICAL LOAD CALCULATION FOR PROPOSED APARTMENT FOR PLATINUM


PRIDE
DG SET SIZE RECOMMENDED 62.5 KVA

CONNECTED LOAD, KW 697.09


DEMAND LOAD , KW 288.87
DEMAND LOAD , KVA 361.08
CONSIDERING 20% SPARE CAPACITY 433.30
TRANSFORMER SIZE RECOMMENDED 500KVA

630
Page 29 of 32 TRITECH CORPORATION

24 1080
3 135
3 135
3 135
4 180
5 225
3 135
7 315
8 360

25 225
2 18
4 36
2 18
4 36
4 36
2 18
7 63
8 72
Page 30 of 32 TRITECH CORPORATION

ROUGH ELECTRICAL LOAD CALCULATION FOR PROPOSED APARTMENT FOR PLATINUM


PRIDE
Sl.no Description Qty Watts Load(Watts) CL(KW) MD(KW)

A) TYPICAL FLOOR 1ST TO 9TH


A TYPE KW
LOAD PER FLAT 9 12830 115470 115.47 46.19 12.83
TOTAL LOAD

B) TYPICAL FLOOR 1ST TO 9TH


B TYPE KW
LOAD PER FLAT 9 12792 115128 115.13 46.05 12.792
TOTAL LOAD

C) TYPICAL FLOOR 1ST TO 9TH


C TYPE KW
LOAD PER FLAT 9 12792 115128 115.13 46.05 12.792
TOTAL LOAD

D) TYPICAL FLOOR 1ST TO 9TH


D TYPE KW
LOAD PER FLAT 9 12830 115470 115.47 46.19 12.83
TOTAL LOAD

E) TYPICAL FLOOR 1ST TO 9TH


E TYPE KW
LOAD PER FLAT 9 12830 115470 115.47 46.19 12.83
TOTAL LOAD

F) TYPICAL FLOOR 1ST TO 9TH


F TYPE KW
LOAD PER FLAT 9 9160 82440 82.44 32.98 9.16
TOTAL LOAD

E UTILITIES
a) PARKING & COMMON AREA( PASSAGE )
1 Flourescent lamp 1X40W Ceiling Mount 25 40 1000
2 2x18W CFL Square Ceiling Mount 95 36 3420
LOAD 4420 4.42 4.42

d) Exterior lighting 15 150 2250 2.25 2.25

f) Lift1 1 5625 5625 5.63 5.63


f) Lift2 1 3750 3750 3.75 3.75
g) Lift Light 20 60 1200 1.20 1.20
h) Lift Socket 20 60 1200 1.20 1.20
i) Water Pump 2 3750 7500 7.50 3.75
i) STP 1 3750 3750 3.75 3.75
j) Fire Pump (20HP) 1 15000 15000
j) jockey Pump (5HP) 1 3750 3750

F) EMERGENCY LOADS
1ST TO 9THFLOOR
1 Total Flats 54 300 16200
16200
TOTAL EMERGENCY LOAD 1 16.20 16.20

DEMAND LOAD (KW) 42.15


DEMAND LOAD , KVA 52.68
CONSIDERING 15% DERATING (85% CAPACITY) 61.98
DG SET SIZE RECOMMENDED 62.5 KVA

CONNECTED LOAD, KW 688.80


DEMAND LOAD , KW 289.59
DEMAND LOAD , KVA 361.98
CONSIDERING 15% SPARE CAPACITY 416.28
Page 31 of 32 TRITECH CORPORATION

ROUGH ELECTRICAL LOAD CALCULATION FOR PROPOSED APARTMENT FOR PLATINUM


PRIDE
TRANSFORMER SIZE RECOMMENDED 400KVA

630
Page 32 of 32 TRITECH CORPORATION

KVA A
6.415 8.981

KVA A
6.396 8.9544

KVA A
6.396 8.9544

KVA A
6.415 8.981

KVA A
6.415 8.981

KVA A
4.58 6.412

5.525

2.8125

7.03125
4.6875
1.5
1.5
4.6875
4.6875

You might also like