Professional Documents
Culture Documents
HT ELECTRIFICATION
1.0 SUPPLY & LAYING OF CABLES Rs0
Supply,Laying, testing and commissioning of the Rs0
following PVC Insulated Armoured Aluminium Rs0
L.T.Cables (AYWY/AYFY) /XLPE (A2XCEFY) H.T Rs0
Cables through excavated trenches, built up cable Rs0
trenches, cable trays, hume pipes,including supply Rs0
and fixing of clamps, nuts and bolts, screws, Rs0
identification tags, route markers etc. required for Rs0
clamping intervals as necessry. Rs0
1) Busbars:
1000A TPN Al. Busbar - 1no.
Earth bus - 31 x 6CU.
ISO INCOMER 18500 2850 INDICATION LAMPS
2) Incomer1&2(630KVA transformer) : OUT MCCB 51350 13000 OUT METER
Air circuit breaker 1000A, set 840A, 50KA Icw 1sec, TPN Pole 100% rated
Neutral, Manually drawout type with OC, SC, Shunt releases, Shutter
Assembly, with Open, Close and Trip, etc- 2nos
ACB 353250 DC METER 18700
Meters & Indications: SFU 320 25800 IND LAMP 2100
Digital Combination Meter(EM 6400 conzerv or equivalent model) SFU 400 61800 3PH VOLT 3080
with PF Meter KW meter, Ammeter, 3nos 2A Control fuse and FUSE 1000 23880
3nos metering CTs 'Class 1.0 10VA, 1000/5A, - 2sets CT 3700
CFUSE 1092
Red, Yellow, Blue , ON, OFF, TRIP LED Indication Lamps along 446642
with 3nos 2A Control fuses & toggle switch – 2sets. 1013319.0375
1037199.0375
3Phase Digital Voltmeter 0-500V Model DM3256 of Conzerv or
equivalent and 3Nos of 2A Control fuses – 2sets 614437.0375
Relays:
Stand by Earth fault relay 10-40% 1.3sec IDMT -2nos
3)Bus Coupler
Air circuit breaker 1000A,set 840KV, 50KA Icw 1sec, 4Pole 100% rated
Neutral, Manually drawout type without releases, Shutter Assembly - 1no
4) Outgoings:
Switch Disconnector Fuse Unit 400A with 315A Fuse links-6nos
Provision shall be made for sealing of all shutters. NOS 1 Rs1,040,000 Rs1,040,000
Page 4 of 32 TRITECH CORPORATION
1) Busbars:
160A TPN Al. Busbar - 1no.
Earth bus - 25.4 x 3.175mm CU.
2) Incomer:
160A TPN isolator - 1no. ISO INCOMER 4400 1050 INDICATION LAMPS
SFU 160 9640 156 C FUSE
SFU 100 3400
Red, Yellow, Blue LED Indication Lamps along with 3nos 17440 1206
2A Control fuses - 1set. 39567
40773
3) Outgoings:
Switch Disconnector Fuse Unit 160A with 125A Fuse links – 2Nos
Switch Disconnector Fuse Unit 100A with 80A Fuse links -1No
Provision shall be made for sealing of all shutters. NOS 2 Rs41,000 Rs82,000
1) Busbars:
315A TPN Al. Busbar - 1no.
Earth bus - 25.4 x 3.18mm CU. ISO INCOMER 7200 1050 INDICATION LAMPS
SFU 100 13600 780 C FUSE
2) Incomer: CUTOUT 3000 11000 OUT METER
315A TPN isolator - 1no. 23800 12830
53996.25
Meters & Indications: 66826.25
3 nos. R Y B Indication Lamps along with 3nos. 2A
Control fuses. -1set.
3) Outgoings:
Switch Disconnector Fuse Unit 100A with 80A Fuse links,
with 80A cut out fuses ,KSEB'S 3PH KWH Meter along
with metering CT of 100/5 CL:1 , 10VA, 415V
3nos of 2A control fuses – 4set
Provision shall be made for sealing of all shutters. NOS 6 Rs67,000 Rs402,000
Page 5 of 32 TRITECH CORPORATION
1) Busbars:
125A TPN Al. Busbar – 1no. INC 7500 1206 INDICATION LAMPS
Earth bus - 25.4 x 3.18mm CU. MCB 9216 22000 OUT METER
CUT OUT 1216 23206
2) Incomer:
125A TPN isolator – 1no 17932
40683.225
Meters & Indications:
3 nos. R Y B Indication Lamps along with 3nos. 2A 63889.225
Control fuses. -1set.
3) Outgoings:
Miniature Circuit Breaker TPN 32A, 32A Cutout fuses,
KSEB's three phase KWH Meter – 8sets
Provision shall be made for sealing all shutters NOS 4 Rs64,000 Rs256,000
3.5 SSB3&SSB6
Bottom cable entry for incoming and outgoing
feeders. Fabricated out of 16SWG CRCA sheet
1) Busbars:
80A TPN Al. Busbar – 1no. INC 3000 1206 INDICATION LAMPS
Earth bus - 25.4 x 3.18mm CU. MCB 5760 13750 OUT METER
CUT OUT 760 14956
2) Incomer:
80A TPN isolator – 1no 9520
21598.5
Meters & Indications:
3 nos. R Y B Indication Lamps along with 3nos. 2A 36554.5
Control fuses. -1set.
3) Outgoings:
Miniature Circuit Breaker TPN 32A, 32A Cutout fuses,
KSEB's three phase KWH Meter – 5sets
Provision shall be made for sealing all shutters NOS 2 Rs37,000 Rs74,000
3.6 DG SB
Top/Bottom cable entry for incoming & outgoing feeders Floor
mount type Fabricated out of 16SWG CRCA sheet.
Page 6 of 32 TRITECH CORPORATION
1) Busbars:
400A TPN Al. Busbar – 1no.
Earth bus - 25.4 x 3.18mm CU.
KSEB' 3PH KWH Meter along with metering CT of 200/5 CL:1 , 10VA,
415V,3nos of 2A control fuses – 1set.
Relays:
Stand by Earth fault relay 10-40% 1.3sec IDMT -1no
3) Outgoings:
Switch Disconnector Fuse Unit 200A with 160A Fuse links-1No
Switch Disconnector Fuse Unit 100A with 63A Fuse links-3Nos NOS 1 Rs130,000 Rs130,000
5) Outgoings:
Switch Disconnector Fuse Unit 160A with 125A Fuse links-1No
Switch Disconnector Fuse Unit 100A with 63A Fuse links-3Nos NOS 1 Rs905,600 Rs905,600
5) Outgoings:
25A TPN MCB – 6nos NOS 1 21000 Rs21,000
63mcb 3416
3.9 UTIL PANEL2 mcb 3416
Top/Bottom cable entry for incoming & outgoing feeders Floor isolator 3750 1050 INDICATION LAMPS
mount type Fabricated out of 16SWG CRCA sheet. mcb 3456 780 C FUSE
14038
1) Busbars: 31848.7125 1830
125A TPN Al. Busbar - 1no. 33678.7125
Earth bus - 25.4 x 3.18mm CU.
0
2) Incomer 1:
125A TPN isolator – 1no
5) Outgoings:
63A TPN MCB – 2nos
40A TPN MCB – 2nos
32A TPN MCB – 3nos NOS 1 33750 Rs33,750
b) 7.5HP Star Delta starter with Contactor and timer NOS 2 Rs1,150 Rs2,300
c) 50HP Star Delta Starter with Contactor and Timer NOS 1 Rs7,000 Rs7,000
Rs0
5) 11KV, 3PANEL VCB SUPPLY & ERECTION (11KV PANEL)
Supply, Erection, testing and commissioning of 11KV, 50c/s,630A
350MVA, Panel with 24 Volt DC tripping mechanism with
remote trip facility Indoor, Floor mounting type complete
with Opening, Closing, Tripping and Earthing Mechanisms
and the following with CPRI and CEIG Approval
Incomer
11KV,350MVA,630A VCB -1 No
Ouitgoings
11KV,350MVA,400A LBS without metering - 2nos
Supply: NOS 60
Supply: NOS 15
Supply: NOS 25
Supply: NOS 15
1.6 1 No, Ceiling fan point along with 1 No 250W 2 module step type
Electronic Fan Regulator, controlled by 1 No 6A, SP Switch.
1.7 1 No, Ceiling fan point along with 1 No 250W 2 module step type
Electronic Fan Regulator, controlled by 2 No 6A, SP Switch.
Supply: NOS 54
2.2 Power point wiring using two runs of 2.5 sq.mm PVC
insulated copper wires alongwith one run of 14SWG
bare copper conductor for continuous earthing.
3.2 Supply and fixing of GI mounting box and blank plate for 1 No,16A
Socket outlet and 1No 16A SP Switch
Supply: NOS UR
3.4 GI mounting box and blank plate for 30A flush type DP switch
Supply: NOS UR
Supply: NOS 54
Supply: NOS 60
4.3 Supply & wiring of Telephone socket using one run 0.5mm
annealed CU two pair unarmoured telephone wire through
20mm conduits wire upto the Terminal Connector for DOT/
Intercom (including conduits)
Page 16 of 32 TRITECH CORPORATION
Supply: NOS 4
Supply: NOS 4
Supply: NOS 1
Supply: NOS 1
Supply: NOS 2
Supply: MTRS 50
Supply: MTRS 65
Supply: MTRS 45
Supply: NOS 9
Supply: NOS 1
Incomer:
ELCB 40A, 4Pole with
O/C & 30mA Earth Leakage trip - 1No.
Outgoings:
MCB 6A , SP - 6nos.
MCB 10A , SP - 6nos.
MCB 16A , SP - 6nos.
Supply: NOS 54
Incomer:
ELCB 40A, 4Pole with
O/C & 30mA Earth Leakage trip - 1No.
Outgoings:
MCB 6A , SP - 20nos.
Supply: NOS 1
Incomer:
ELCB 40A, 4Pole with
O/C & 30mA Earth Leakage trip - 1No.
Outgoings:
MCB 6A , SP - 12nos.
Supply: NOS 5
Incomer:
ELCB 40A, 4Pole with
O/C & 30mA Earth Leakage trip - 1No.
Outgoings:
MCB 6A , SP - 12nos.
Supply: NOS 1
7.1 1X40W Fluorescent Surface mounted luminar with acrylic Diffuser NOS 25
7.2 2X18 W CFL surface mounted low glare mirror optic luminare NOS 95
7.3 4X18 W CFL surface mounted low glare mirror optic luminare NOS UR
HT ELECTRIFICATION
10.0 SUPPLY & LAYING OF CABLES
Supply,Laying, testing and commissioning of the
following PVC Insulated Armoured Aluminium
L.T.Cables (AYWY/AYFY) /XLPE (A2XCEFY) H.T
Cables through excavated trenches, built up cable
trenches, cable trays, hume pipes,including supply
and fixing of clamps, nuts and bolts, screws, Rs0
identification tags, route markers etc. required for Rs0
clamping intervals as necessry. Rs0
Page 20 of 32 TRITECH CORPORATION
1) Busbars:
630A TPN Al. Busbar - 1no.
Earth bus - 31 x 3CU.
2) Incomer :
630A TP MCCB 35KA Extra Current Limiting type
set at 533A with O/C, S/C and E/F releases- 1no
Red, Yellow, Blue , ON, OFF, TRIP LED Indication Lamps along
with 3nos 2A Control fuses & toggle switch - 1set.
3) Outgoings:
Moulded Case Circuit Breaker TP, 250A, 35KA Set 200A Rs0
with Electronic release FD KIT, OC, SC, EF, Shunt & Isolation
duty Current Limiting type - 3nos
1) Busbars:
200A TPN Al. Busbar - 1no.
Page 22 of 32 TRITECH CORPORATION
2) Incomer:
200A TPN isolator - 1no.
3) Outgoings:
Moulded Case Circuit Breaker TP, 125A, 35KA Set 100A Rs0
with Electronic release FD KIT, OC, SC, EF, Shunt & Isolation Rs0
duty Current Limiting type - 3nos
1) Busbars:
100A TPN Al. Busbar - 1no.
Earth bus - 25.4 x 3.175mm CU.
2) Incomer:
100A TPN isolator - 1no.
3) Outgoings:
32A TPN MCB, 32A Cutout fuses and 1no KSEB's three phase Rs0
KWH Meter - 6nos Rs0
12.4 DG SB
Top/Bottom cable entry for incoming & outgoing feeders Floor
mount type Fabricated out of 16SWG CRCA sheet.
1) Busbars:
160A TPN Al. Busbar - 1no.
Earth bus - 25.4 x 3.18mm CU.
2) Incomer:
160A TPN isolator - 1no.
3) Outgoings:
Moulded Case Circuit Breaker TP, 160A, Set 125A
with Electronic release FD KIT, OC, SC, EF, Shunt & Isolation
duty Current Limiting type - 1no. Rs0
1) Busbars:
125A TPN Al. Busbar - 1no.
Earth bus - 25.4 x 3.18mm CU.
2) Incomer 1:
125A TPN isolator - 1no
125A 4 pole contactor -1no
(electromechanically interlocked)
3) Incomer 2:
125A TPN isolator - 1no
125A 4 pole contactor - 1no
(electromechanically interlocked)
4) AMF Controls
uP based AMF Relay for controlling 2nos Incoming & 1no
outgoing Contactors - 1set
Synchronous timer for 24hour operation - 1nos
5) Outgoings:
32A TPN MCB - 3nos
25A TPN MCB - 4nos
63A TPN MCB - 1no NOS 1 Rs0
1) Busbars:
32A TPN Al. Busbar - 1no
Earth bus - 25.4 x 3.15mm CU.
2) Incomer:
32A TPN Isolator -1no
3) Outgoings:
25A 4P RCBO ,100mA - 1no
10A 2P RCBO, 30mA - 1no NOS 2 Rs0
b) 7.5HP Star Delta starter with Contactor and timer NOS 1 Rs0
F) EMERGENCY LOADS
1ST TO 14THFLOOR
1 Total Flats 54 300 16200
16200
TOTAL EMERGENCY LOAD 1 16.20 16.20
630
Page 29 of 32 TRITECH CORPORATION
24 1080
3 135
3 135
3 135
4 180
5 225
3 135
7 315
8 360
25 225
2 18
4 36
2 18
4 36
4 36
2 18
7 63
8 72
Page 30 of 32 TRITECH CORPORATION
E UTILITIES
a) PARKING & COMMON AREA( PASSAGE )
1 Flourescent lamp 1X40W Ceiling Mount 25 40 1000
2 2x18W CFL Square Ceiling Mount 95 36 3420
LOAD 4420 4.42 4.42
F) EMERGENCY LOADS
1ST TO 9THFLOOR
1 Total Flats 54 300 16200
16200
TOTAL EMERGENCY LOAD 1 16.20 16.20
630
Page 32 of 32 TRITECH CORPORATION
KVA A
6.415 8.981
KVA A
6.396 8.9544
KVA A
6.396 8.9544
KVA A
6.415 8.981
KVA A
6.415 8.981
KVA A
4.58 6.412
5.525
2.8125
7.03125
4.6875
1.5
1.5
4.6875
4.6875