You are on page 1of 4

CALCULATION SHEET

Project Name PLTU MALINAU

Subject IDF

Total base shear force of building due to earthquake load shall be calculated as follow (for the seismic

Non Bulding Structures (UBC 97) for Tank w/ Supported Bottoms :

C = 0.30 Earthquake Respone Factor


I = 1.50 Importance Faactor
R = 2.20 Earthquake Reduction Factor
H = 1.5/2 0.75 Height of Trafo

Vt = Wt x C I/R = Wt x Cd
= 0.00 x
Hx = Vt = 0.00 ton

Mom = Vt x H = 0.00 x
Mx = 0.00 tm

c. Beban Angin
UBC, 1997 Edition, Chapter 16 Div III shall be applied
Basic Wind Speed : 125 Km/h (77.64 mph)
Wind stagnation pressure (qs) 70 kg/m2
Exposure :C
Height variation : As per UBC - 1997
The wind force shall be calculated based on equation 20 -1 in UBC code, 1997.
W = Ce x Cg qs x I x A = PxA
Where :
P : Design wind pressure (kg/m 2)
Ce : Combined height, exposure and gust factor coefficient
Cq : Pressure coefficient
qs : Wind stagnation pressure
I : Importance factor
A : Projected area of all the elements of the wind ward face (m 2)

Wx = Ce x Cq x qs x I x A = PxA
Wx = 1.06 x 1.4 x 70
= 229.06 kg
= 0.23 ton

Mom = Wx x H = 0.23 x
Mx = 0.17 tm
Owner PT. PLN (Persero)

culated as follow (for the seismic coefficient for each facility):

0.20

0.75

1.06 in UBC97
1.4 in UBC97
70 in UBC97
1 in UBC97

x 1 x 2.205

0.75