You are on page 1of 9

Journal of International Council on Electrical Engineering

ISSN: (Print) 2234-8972 (Online) Journal homepage: http://www.tandfonline.com/loi/tjee20

Study on High Resistance Distance Relay in


Directly Earth System

Liu Huan-Zhang & Li Ying-Hong

To cite this article: Liu Huan-Zhang & Li Ying-Hong (2011) Study on High Resistance Distance
Relay in Directly Earth System, Journal of International Council on Electrical Engineering, 1:4,
410-417, DOI: 10.5370/JICEE.2011.1.4.410

To link to this article: https://doi.org/10.5370/JICEE.2011.1.4.410

© 2011 Taylor and Francis Group, LLC

Published online: 10 Sep 2014.

Submit your article to this journal

Article views: 303

Full Terms & Conditions of access and use can be found at


http://www.tandfonline.com/action/journalInformation?journalCode=tjee20
410 Journal of International Council on Electrical Engineering Vol. 1, No. 4, pp. 410~417, 2011

Study on High Resistance Distance Relay in Directly Earth System

LIU Huan-zhang† and LI Ying-hong*

Abstract – The coverage of transition resistance and the avoidance of load impedance is in essence a
contradiction for distance protection. It’s evident from the impedance plane that the requirement to avoid
the load impedance results in that the action space of the distance relay is greatly limited, which
accordingly reduces the ability of the relays to cover the transition resistance. In fact, there are some
limitations to analyze the distance relays in the impedance plane. It would be better in the voltage plane.
The three elements of distance relay in the voltage plane are the polarization voltage, operation voltage
and operation characteristic, of which the polarization voltage is most important. The relay could ideally
select pre-fault voltage as polarization voltage, while it practically employs the positive voltage. The
difference between the two kinds of polarization voltage is negligible in the state of low impedance
ground fault, while significant in the state of high impedance ground fault. Thus, this paper uses the
memory and the non-fault phase parameters to gain the pre-fault voltage, that is, the new polarization
voltage, and puts forward a new self-adaptive high impedance ground distance relay.

Keywords: High resistance ground fault, Voltage plane, Impedance plane, Selecting phase with current

1. Introduction protection [2]. Most investigations show that the load


resistance is less than short circuit resistance due to heavy
Distance protection is prone to incorrect operation due to load, which would make the ground distance relay unable
three major reasons: PT disconnection, system oscillation to distinguish the two kinds of resistance and possible to
and transition resistance. The first two problems have been operate incorrectly [3]. However, if the ground distance
well solved, but the coverage of transition resistance of the relay is able to cover transition resistance, the selectivity is
ground distance relay is far from been solved satisfactorily. certainly further enhanced. For example, a high resistance
In general, the voltage of short circuit point in phase-to- ground distance protection could be considered as an
phase fault is less than 0.05pu, thus the transition resistance complement to the traditional ground distance protection,
could be neglected in phase-to-phase distance protection. If whose setting values of zone-I, II, III are the same to
there is a ground fault and the short circuit current is higher traditional ground distance relay zone-I, II, III, respectively
than 1kA, the ground distance relay should be able to and the operation time are: 2.5s, 3.0s, 3.5s, respectively.
tolerant 100Ω or 300Ω transition resistance to clear the The setting value and operation time of directional zero
fault timely and correctly when the voltage level is 220kV sequence current for zone-II are 500A and 4s respectively,
or 500kV respectively. Since it is impossible to design a while those of non-directional zero sequence current for
ground distance relay to tolerate such high transition zone-III are 300A and 4.5s respectively. The high
resistance, many researchers have to adopt zero sequence resistance ground distance protection mentioned above
current protection to make up the disadvantage of ground shows an ideal inverse time characteristic, simple setting
distance relay [1]. However, the over current protection is calculations and reasonable time coordination, which is of
too easy to reconcile its sensitivity and selectivity. In order great significance to the safe operation of the large complex
to avoid incorrect operation, it is an acceptable solution to power grid [4].
ensure the selectivity and sacrifice the sensitivity in setting The operation characteristic can be analyzed in the
calculation of traditional ground distance relay. impedance plane or the voltage plane [5], [6]. Traditionally,
In fact, coverage of transition resistance and the the former is mostly used, but the requirement to avoid the
avoidance of load impedance is a contradiction for distance load impedance results in that the action space of the
distance relay is greatly limited, which reduces the ability
† Corresponding Author: Central China Grid Company Limited,
of the relays to cover the transition resistance. So the later
Wuhan 430077, China (liuhz@cc.sgcc.com.cn)
* Dept. of Electrical and Electronic Engineering, Huazhong
would be better because of the disadvantages and
University of Science and Technology, Wuhan 430074, China limitations of the former. The three elements of distance
Received: September 28, 2011; Accepted: September 28, 2011 relay in the voltage plane are the polarization voltage,
LIU Huan-zhang and LI Ying-hong 411

operation voltage and operation characteristic. The essence In the voltage plane, once the reference voltage is
of studying the distance relay in the voltage plane is as selected, the operation area of the operation voltage is
follows: supposing the short circuit fault on the setting divided. The reference voltage must be determined by “the
point, the trip boundary of operation voltage is determined conditions before faults”, which is not exactly the
through the trajectory of the setting point voltage changing conditions before the moment of short-circuit, but the
with the transition resistance. It is obvious that such relay’s conditions before faults in the failure analysis. What is the
operation characteristic depends on the fault boundary, so it difference? For example, when a single-phase ground fault
is self-adaptive and its performance would be better than happens in the process of power system all-phase
those studied in any other impendence plane. A high oscillation, the short-circuit current would vary with
resistance distance relay in the voltage plane is proposed in oscillation, which is due to the voltage at fault point “before
this paper to improve the sensitivity of ground distance faults” varied with oscillation. However, the voltage at fault
protection on the premise of ensuring its selectivity. point before the moment of short-circuit should be
unchanged. Obviously, to gain “the conditions before
faults” after faults is the key to distance relay.
2. Principle of distance relays in voltage plane The polarization voltage which is also called reference
voltage plays an important role. As is known to all, the
It is known that the research on distance protection is emergence of microcomputer protection contributes much
rooted in the research on polarization components, which is to the success of break variable protection, because of the
the essence of the distance protection. Operation voltage memory function of microcomputer. The polarization
and polarization voltage are two elements of distance relays. component with memory can easily gain “the conditions
Invariably, the compensation voltage is selected as before faults”. But, after faults, as time goes by, many
operation voltage (This is why distance protection is called changes (the excitation of generator, the changes of power-
impedance protection; the compensation impedance angle, etc) would make the memory not able to reflect “the
determines protection range, and the protection range is conditions before faults” correctly, so it’s conditional to use
proportional to the compensation impedance). Failure the memory. When the memory disappears, for the single-
analysis results point out the variation area of operation phase ground fault, supposing the positive power grid the
voltage in voltage plane under different situations (internal same to the negative one (the following analysis is based on
faults and external faults, forward and backward faults). this), the fault sequence component of non-fault-phase is
Fig. 1 is one-line diagram of two generator system, in only zero-sequence component, so the difference of electric
which the relay is installed on M, F0 (fault at setting-point); quantum of non-fault-phase could reflect “the conditions
F1 (internal fault); F2 (forward external fault); F3 before faults”. It shows that phase selection is the key!
(backward fault). Fig. 2 is trajectory of compensation There is a paradox during the determination of polarization
voltage when internal or external fault happens in the voltage: to the single-phase ground fault, right phase
sending and receiving end. selection can reckon “the conditions before faults”; and if
“the conditions before faults” can be known firstly, the
relay will select phase rightly. Therefore, it’s a key point to
untie the contradiction of chicken and egg [7].
To instantaneous protection, it’s certain to make full use
of memory. To the delayed protection, it’s necessary to
Fig. 1. One-line diagram of two generator system. make sense of its position firstly: high impedance ground
distance relay protection is the complement when the
traditional distance relay protection can not cut the high
impedance ground faults, which provides a very
comfortable environment for the phase selection of high
impedance ground distance relay. Since it need not consider
the problem of transient stability, a long time-delay is
(a) Sending side F0~F2 (b) Sending side F3 permitted in high impedance single-phase ground fault.
(c) Receiving side F0~F2 (d) Receiving side F3 Meanwhile, complex faults will hardly happen, traditional
distance relay can not operate to trip, and still, it shows the
Fig. 2. Trajectory of compensation voltage. characteristics of the ground fault, so it can be almost
412 Study on High Resistance Distance Relay in Directly Earth System

believed as single-phase ground fault. On this condition, If the fault is ) , then


it’s easy to select fault phase, and the following research
begins with the phase selection. If the fault is ) , and is in zone A,
then is in zone A ;
If the fault is ) , and is in zone A, then
3. Phase selection and pre-fault operation voltage
lag behind by , nearing zone A.
The first work is to select phase, so as to calculate pre-
fault operation voltage of single-phase high impedance 3.1 Phase selection for instantaneous protection
ground fault. There are only two results: the fault phase is
Phase selection is discussed when the high impendence
selected or phase selection failed. Since the high impedance
distance relay is used as instantaneous trip protection. Take
distance relay protection is a complement protection, it is
zone A for example, in order to prevent incorrect phase
better to phase selection failure rather than incorrect phase
selection. selection, the area of should be narrowed according to
A necessary condition for phase selection is given in (1) above-mentioned zoning and analysis. is in the area
without the condition phase selection would fail.
ahead of by and behind by , so the fault
must be , or phase selection fails. The Logical
(1)
diagram is shown in Fig.4.

The following analysis is based on this condition.


Following traditional practices, divide the plane to three
zones (A, B, C) by coordinate, leading it by and
lagging it by , as shown in Fig. 3.
Take zone A for example, when is in zone A, there
Fig. 4. Logical diagram of selecting phase.
are three possible fault types:
) : single phase ground short circuit, the fault
Where is the break variable of positive-sequence
phase is A
current of phase A by memory parameters.
) : two-phase ground short circuit, the fault Because the security of instantaneous segment is highly
phases are B and C required, the pre-fault operation voltage of fault phase
) : two-phase ground short circuit, the fault A( ) should be confirmed more times. is pre-
phases are A and B fault compensation voltage using the memory parameters,

while , the formula is used to

calculate pre-fault compensation voltage by non-fault phase


parameters after a fault.
To further ensure the correctness of phase selection, if
the following formula holds, phase selection fails.

(2)

To prevent steady-state exceeding caused by : Set


Fig. 3. Phasor diagram of selecting phase with current.
, when ; Set
If the break variable of positive-sequence current ( )
is known, the problem of phase selection can be easily , when ; Otherwise,
solved. Failure analysis shows:
LIU Huan-zhang and LI Ying-hong 413

phase selection fails. When the fault is :

3.2 Phase selection for time delay protection No-load,


Considering load: load current of sending end leads
Phase selection is discussed when the high impendence , almost positively overlapping; load current of
distance relay is used as time delay protection. Taking zone receiving end and sending end are reverse, almost
A for example. If merely take current parameters to select negatively overlapping.
phase, there are only three current( , , ) can be According to the analysis above, can not simultaneously
used, because will disappear with time after the fault. satisfy those two conditions. If the fault is ) with
At first, could be excluded, because if the fault is high impendence, the following formula does not hold
, phase A is non-fault phase and if the fault is
), phase A is fault phase, the current direction of
in these two kind of faults is reverse. Thus in these When the fault is ) with high impendence and

two cases, is impossible in the same zone, even though is in zone A, then this kind of fault is almost the same
considering load. The next step is to determine whether the with ), and must be far less than . Therefore
fault is or ). In these two faults phase C the non-fault current is nearly unchanged.
is non-fault phase, to the fault , the current of
phase C are nearly unchanged, so can be calculated (4)
from post-fault current of phase C. The Logical diagram of
selecting phase with current is shown in Fig.5. Then does not satisfy the following formula:

When is in four different quadrants of positive


sequence power, phase selection criteria is summarized in

Fig.6, where and is the

impendence angle.

Fig. 5. Logical diagram of selecting phase with current.

(3)

When the fault is ):


No-load:
Considering load: load current of sending end leads
, almost positively overlapping, and satisfies

the formula: ; load

current of receiving end and sending end are reverse,


almost negatively overlapping, and satisfies the (a) (b)
(c) (d)
formula: Fig. 6. Specific programs of selecting phase with current.
414 Study on High Resistance Distance Relay in Directly Earth System

Miss tripping of conventional distance relay is the For ∆ ZGI & ∆ ZG are designed as a component of high
premise of using the high impedance distance relay impedance ground fault, they are only put in operation
protection. Current phase selection improves the security. when normal distance relay can not trip correctly and
In addition, a voltage involved phase selection approach timely. The first work of ∆ ZGI & ∆ ZG is to select phase, if
is discussed here, as shown in Fig. 7. Taking zone A for phase selection fails, ∆ ZGI & ∆ ZG would be blocked; if
example, where , phase selection success, calculate fault phase and block
non-fault phase. ∆ ZGI and ∆ ZG are triggered by the
mutation protection. ∆ ZGI needs use memory, so it works
temporarily. Besides, it must avoid transient process, so
only 30~40ms can it be in operation.
For example, phase A is the fault phase, then:

; (5)

; (6)
(7)

(8)

Fig. 7. selecting phase with current and voltage. (9)

By the way, calculate the voltage of abrupt change


4. High-impedance distance relay direction relay:

Fig. 8 shows the high-impedance distance relay ∆ ZGI


and ∆ ZG . is used as polarization voltage and the (10)

circle with diameter of is used as operating


characteristic. is on the circle, namely the load is on Where L represents line length (km), and ZL1 represents
the boundary of operating zone, so load limitation line positive sequence impedance of the line.
should be adopted. To the sending end and receiving end, To illustrate the physical meaning of formulas above,
rewrite their forms:
load limited line is the straight line and ,
respectively. Load limited line reduces the coverage of
transition resistance, and the situation of receiving end is (11)
worse. However, receiving end will become sending end
after the operation of sending end. The high-impedance
distance relay of former receiving end can clear the fault Physical meaning: It equals that PT is put forward to the
with high impedance correctly and quickly. 25% of the line; so that the dead-zone resulted from back
strong source is gone. Then compare them after positive
and negative compensation 250km of the line.
The operation equations and the settings of high-
impedance distance relay are given in Fig. 9 and Table 1,
respectively.
Sending end: cosØBC > 0 or IBC < 0.2In where In repre-
sents rated secondary current of CT.
(a) sending end (b) receiving end
Fig. 8. high-impedance distance relay in the voltage plane.
LIU Huan-zhang and LI Ying-hong 415

In order to demonstrate the effectives of the proposed


(12) high impendence ground distance relay, simulation tests are
carried out based on PSCAD model as shown in Fig. 10.
Suppose the line length between breakers B1 to breaker B2
is 100km. The relay is on the breaker B1, and the line
(13) parameter is as follows: Z1 = 42.21∠78.86°, Z0 =
128.19∠73.00°; the ratio of CT is 1200A/1A, the ratio of
PT is 220kV/100V. FT1~FT5 are the fault on the side of B1
by 0%, 25%, 50%, 75%, 100% , respectively. FT7 is on the
Receiving end: cos ØBC ≤ 0 and IBC ≥ 0.2In
bus back of breaker B1, and FT9 is on the bus back of
breaker B2.
The simulation results are given in Table.2 and Table.3.
It is necessary to mention that the current of heavy load is
(14) static current (975A) in this simulation, and it is extremely
heavy current. Even in such case, the high-impedance
distance relay has the better characteristic on the coverage
of transition resistance than that of common distance relay.
The simulation results illustrate that: firstly, the high
impedance distance relay has a clear direction and it would
not overreach the steady-state; secondly, it can avoid load
impedance adaptively, which acts better with light load, as
well as on the sending end. Take stage I of a 220kV 100km
line for example: light load: Line near-end, 130Ω; 50% of
the line, 70Ω; 75% of the line, 30Ω. Sending end with
heavy load: line near-end, 120Ω; 50% of the line, 70Ω;
75% of the line, 30Ω. Receiving end with heavy load: line
Fig. 9. Logical diagram of high-impedance distance relay near-end, 120Ω; 50% of the line, 70Ω.

Table 1. Settings of high-impedance distance relay


Relay stage m α β t(s) 6. Conclusions
set
0 0
I 0.25 30 15 2.5
II 0.20 20
0
10
0
3.0 Although the characteristic analysis of ground distance
III 0.15
0 0
3.5
relay can be in the impedance plane or the voltage plane,
10 5
the later would be better than the former after some
comparisons. The three elements of distance relay in the
voltage plane are the polarization voltage, operation voltage
5. Simulation and operation characteristic. The polarization voltage is the
most important one, and it is best to select pre-fault
operation voltage as polarization voltage. This paper uses
memory and the non-fault phase parameters to obtain pre-
fault voltage, namely new polarization voltage, and puts
forward a new self-adaptive high impedance ground
distance relay. This high impedance ground distance relay
is self-adaptive, because its operating characteristic depends
on fault boundary. Finally, a plenty of simulation
calculation and dynamic testing demonstrate that the
performance of the proposed high impedance grounding
distance relay is better than those analyzed and designed in
Fig. 10. Simulation model of 220kV system. impendence plane.
416 Study on High Resistance Distance Relay in Directly Earth System

References [5] WANG Mei-yi. Analyze the Operation Characteristic of


Impedance Relay. Relay, 1979, (04): 1-65 (in Chinese).
[1] ZHU Sheng-shi. High Voltage-grid Relay Protection [6] LIU Huan-zhang. A Novel Impedance Protection
Principle and Technology. Beijing: Hydraulic Power Analysis Method Based on the Transform from the
Press, 1995 (in Chinese). Voltage Plane to the Impedance Plane. Proceedings of
[2] SHEN Guo-rong. Research on Frequency Variation the Chinese Society for Electrical Engineering, 2004,
Distance Relay. The fourth Chinese electrical 24(1): 40-43 (in Chinese).
engineering society Academic conference of relay [7] XU Qing-qiang, SUONAN Jia-le, LIU Huan-zhang, et
protection and auto-safety device, 1986, (10): 1-6 (in al. Fault Phase Selector for HV Transmission Line
Chinese). Protective Relaying Based on the Characteristic of the
[3] SHEN Gou-rong. A New Directional Relay Based on Arc Voltage Between Two Faulted Phases. Automation
the Variation of Power Frequency Components. of Electric Power Systems, 2006, 30(4):65-70 (in
Automation of Electric Power Systems, 1983, (01):28- Chinese).
38(in Chinese).
[4] ZHU Sheng-shi. Study on Grounding Distance Relays.
Automation of Electric Power Systems, 1977, (04): 28-
54 (in Chinese).

Table 2. Action of high-impedance distance relay under heavy load condition (load 975A)
LIU Huan-zhang and LI Ying-hong 417

Table 3. Action of high-impedance distance relay under light load condition

You might also like