Professional Documents
Culture Documents
K. H. EDELMOSER
Institute of Electrical Drives and Machines
Technical University Vienna
Gusshausstr. 27-29, A-1040 Wien
AUSTRIA
Abstract: In case of medium voltage (several tenth up to hundred volts on DC-side) solar inverter applications a
DC-to-DC converter for voltage level adaptation is required in front of the DC-to-AC inverter. This leads to a
two-stage concept with accumulation of the losses. In our case a concept has to be chosen, where the efficiency
in each stage is maximized by usage of the best-fit topology. The given requirements force the application of a
non-isolated design to avoid additional transformer losses. In this paper a 60V-120V DC (input) to 230V AC
(output) / 1kW converter with minimal conversion losses is derived. A simple modification in the inverters
output section lead to a significant improvement of the losses in the inverter system. Only three additional
components (two diodes and one inductor) are necessary to optimize the inverters power stage. The topology
presented here shows a remarkable improvement of the switching losses and significantly reduced EMC. It is
well suited for solar power inverter applications.
Keywords: Inverter, Solar Power, PWM, efficiency
-10
switched PWM stage operated at the same ambient
conditions. In this model a load power factor of 1 is
assumed, so that the polarity of the mains current
-20
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1
-3
400
x 10
IM depend only on the polarity of the mains voltage
300
V(L1B)
shape. Figure 7 shows the simulation results of the
V(L1B),+UZK[V]
V(+UZK)
200 power stage. In the upper trace one can see the
100 reference current (standardized mains voltage),
0 below the resulting output current shape is shown.
-100
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 The lower trace depicts the PWM signals of each
t[s] -3
x 10 power switch (S3 respectively S4).
Fig. 5 DC-to-DC converter in Step-Up mode
20
IC
20
ISoll[A]
VG(S1) 0
10
V(S1)[V]
0 -20
0 0.002 0.004 0.006 0.008 0.01 0.012 0.014 0.016 0.018 0.02
-10 20
IM
IIst[A]
-20
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 0
-3
x 10
200 -20
V(L1A) 0 0.002 0.004 0.006 0.008 0.01 0.012 0.014 0.016 0.018 0.02
V(L1A),-UZK[V]
V(-UZK) 20
0 VG(S3)
SW1,SW2
VG(S4)
0
-200
-20
-400 0 0.002 0.004 0.006 0.008 0.01 0.012 0.014 0.016 0.018 0.02
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1
t[s]
t[s] -3
x 10
Fig. 6 DC-to-DC converter in inverting mode Fig. 7 switching behaviour of the improved inverter
stage
The simulation results are compared to a
To determine the quality of the mains current one
conventional Step-Up / Step-Down and an isolated
can see the output spectrum of the inverter in
(transformer coupled) PWM DC-to-DC converter
Figure 8. Here no additional filter is used. A simple
switching stage. Every case uses the same
mains coupling filter (which is always required in
component models so that simulation results can be
practical applications but not taken into
compared directly. The conclusion is given in
considerations here) will lead to a further
Table 1. As one can see the used topology can
improvement of the switching harmonics.
compare with a conventional Step-Up / -Down
solution. As an advantage here only one inductor is 2
-1
10
AC-to-DC – rectifier, Filter).
-2
10