You are on page 1of 4

Job Number

Calc. Sheet no. Rev. 0


Job Name UJ Drawings nos.

Structure Calculations by Date


Bifurcate area
Checked by Date
Section Reviewed by Date
Fan calculation
#REF!

REF CALCULATIONS OUTPUT

Volume

Volume = 176573.35 ft3 5000.00 m3


Air change / hr = 1.00
Total air quantity = 2942.89 cfm 1.39 m3/s

Design criteria
Design velocity = 2200.00 fpm 11.18 m/s (1800-2400fpm)
Duct area = 1.34 ft2 0.12 m2
Round Duct diameter = 16.00 in 398 mm
Friction rate = 0.39 in. wg/100ft

Losses
Duct length = 1508.80 ft 460.00 m
Friction Loss = 5.81 in.wg
Velocity pressure = 0.30 in.wg
Elbow =
90 3 nos 0.49
Total static pressure = 6.30 in.wg 1567.41 Pa
110% 6.93 in.wg 1724.15 Pa

surge chamber

130m

junction to
surge chamber
fan
330m

bifurcate area
(estimate volume 5000m3)

Schematic diagram