You are on page 1of 6

Job Number

Calc. Sheet no. Rev. 0


Job Name UJ Drawings nos.

Structure Calculations by Date


Bifurcate area
Checked by Date
Section Reviewed by Date
Fan calculation
#REF!

REF CALCULATIONS OUTPUT

Volume

Volume = 176573.35 ft3 5000.00 m3


Air change / hr = 1.50
Total air quantity = 4414.33 cfm 2.08 m3/s

Design criteria
Design velocity = 1800.00 fpm 9.14 m/s (1800-2400fpm)
Duct area = 2.45 ft2 0.23 m2
Round Duct diameter = 22.00 in 539 mm
Friction rate = 0.18 in. wg/100ft

Losses
Duct length = 1508.80 ft 460.00 m
Friction Loss = 2.73 in.wg
Velocity pressure = 0.20 in.wg
Elbow =
90 3 nos 0.33
Total static pressure = 3.06 in.wg 761.82 Pa
110% 3.37 in.wg 838.00 Pa

surge chamber
130m

junction to
surge chamber
fan
330m

bifurcate area
(estimate volume 5000m3)

Schematic diagram
Job Number

Calc. Sheet no. Rev. 0


Job Name UJ Drawings nos.

Structure Calculations by Date


Bifurcate area
Checked by Date
Section Reviewed by Date
Fan calculation
#REF!

REF CALCULATIONS OUTPUT