Sequential Operation Process for TG-8

Display "formula", Che


Display "TG-8 Cooking" Is Tank bottom val
Display "TG-8 finishing " Is Ventilation valve

1. Start
Acquire devices
-AG-TG-8A -AG-TG-8B
Add TC-1 Slurry preparation -TIC-0601A -TIC-0601
(Complete feed and flushing) 8_TIMER -XV-0609
-XV-0606 -XV-0632

Ref. TC-1 preparation sheet.

2. By operator’s NO
NO
“continue command” Owned by ot

YES

Feed TBO 1 (111001-00T)_________kg. (A)


(Start Pump P-1),(Open XV-0601,0603)(Close XV-0602,0604,0605,0635,0636,0629) NO
(FT-0601 monitor the mass flow, FQI-0601 measure the mass) Ow

NO
Interupt feeding
NO
mass reach "set point"

YES

Stop Pump P-1,


(Close XV-0601,0603)

ALERT operator to check “complete”.

NO
4. Operator checks "complete"

YES

5. By operator’s NO
“continue command”

YES
Delete
ALERT operator
Pour Ca(OH)2 slurry from TC-1 (212019-0000) __100% kg.(M)
Start pump P-25 via (HS-0325)

Pour Ca(OH)2 slurry from TC-1 (212019-0000) ________%wt.(M)


Start pump P-25 via (HS-0325)
Pour Ca(OH)2 slurry from TC-1 (212019-0000) ________%wt.(M)
Start pump P-25 via (HS-0325)

NO
Operator checks "complete"

YES

4.By operator’s NO
“continue command”

YES

Add TP-1 TP-1/2 (212019-0000) 100% kg. to Z-1 (A)


Start Pump P-6 (WIC-0601 monitor and control the mass) NO
Ow

NO
mass reach "set point"

YES

Stop Pump P-6

NO
7. Operator checks “complete”

YES

8. By operator’s NO
“continue command”

YES

ALERT operator to START Agitator A/B (M)


(START Agitator AG-TG-8 A/B via HS-8 A/B)

9. Operator to START Agitator A/B (M)


(START Agitator AG-TG-8 A/B via HS-8 A/B)

START heating to and MAINTAIN temp. at 150 deg. C (A)


(open XV-0606/ 0609) (close XV-0607)
(TT-0601 control temperature inside vessel. TIC-0601 which adjusts the position of the control valve TCV-0601A)

NO
Temp. reach 150 deg. C
Temp. reach 150 deg. C

YES

ALERT operator to (A)


a) STOP agitator A/B
b) WAIT for operator’s “continue command’’

By operator’s NO
“continue command”

YES

10. Operator to STOP agitator A/B (M)


(STOP agitator AG-TG-8 A/B via HS-8 A/B)

ALERT (A) operator for "QC sampling."


Count จจจำนวน ครรงรั้ QC sampling #1,2,3
nQC=1,2,3…

11. QC sampling (M)

NO
12. Operator checks "complete"

YES

13. By operator’s NO
“continue command”

YES

ALERT operator to START Agitator A/B (M)


(START Agitator AG-TG-8 A/B via HS-8 A/B)

14. Operator to START Agitator A/B (M)


(START Agitator AG-TG-8 A/B via HS-8 A/B)
Set speed 8A = 32 RPM

NO
15. Admin. Room QC Signal

YES

Operator's Monitor displays the Acid and Base value.

YES
16. "QC PASS"

NO

POUR Ca(OH)2 to TG-8


I.ALERT operator
Add Ca(OH)2 slurry (212019-0000) _________Kg.(M) from TC-1
(Start Pump P-25 via Local HS-0325 )

I. Add Ca(OH)2 slurry (212019-0000) _________Kg.(M) from TC-1


(Start Pump P-25 via Local HS-0325 )
Stop Pump P-25
via Local HS-0325

ALERT (A) operator to pour raw materials.


- Ca(OH)2 (212019-000)_______kg. (M)

Monitor displays the amounts

Pour Ca(OH)2 (212019-000)_______kg. (M)

ALERT operator to check “complete”.

NO
Operator checks"complete"

YES

17. By operator’s NO
“continue command”

YES
18. Acquire devices
-P-6

II. Add TP-1 TP-1/2 (212018-0000) _______ Kg. FROM Z-1 (A)
Start Pump P-6 (WIC-0601 monitor and control the mass) NO
Owned by other?

NO
mass reach "set point"

YES

Stop Pump P-6

ALERT operator to check “complete”.

NO
19. Operator checks "complete"

YES

20. By operator’s NO
“continue command”

YES

21. Run for 30 min.


III. ALERT (A) operator to STOP Agitator A/B (M)
(STOP agitator AG-TG-8 A/B via HS-8 A/B )

By operator’s NO
“continue command”
YES

Operator to STOP agitator A/B (M)


(STOP agitator AG-TG-8 A/B via HS-8 A/B )

NO
Operator checks "complete"

YES

ALERT (A) operator for "QC sampling."

QC sampling (M)

NO
IV. QC sampling "completed"

YES

By operator’s NO
“continue command”

YES

ALERT operator to START Agitator A/B (M)


(START Agitator AG-TG-8 A/B via HS-8 A/B)

Operator to START Agitator A/B (M)


(START Agitator AG-TG-8 A/B via HS-8 A/B)

NO
Operator checks "complete"

YES

NO
V. Test sample (M)

YES 24. START h


(
(TT-0601 control temperature inside v
(
(TT-0601 control temperature inside

25. START coolin


Start pump
(TT-0601 control temperature inside

ALERT
a) ALE
b) Ad

(30 min. duration

ALERT (A) o

ALE
(S
A

AL
(ST

3
(ST
Operato
QC (Qua
QC (App

YES

35. I. START

(TT-0601 control temperature inside

Replete Step 13-14


Check All Status .
Is Tank bottom valve Closed ?
Is Ventilation valve properly opened?

devices
8A -AG-TG-8B -P-29
0601A -TIC-0601B -TG-
R -XV-0609 -XV-0607
6 -XV-0632 -TC1-PREPARE

YES
Owned by other?

3. Acquire devices
-FQI-0601

YES
Owned by other?

Interupt feeding?

YES
6. Acquire devices
-P-6

YES
Owned by other?

ALERT operator to Close upper and open lower jacket (M)

By Operator's Close upper and open lower jacket (M)

By operator’s NO
“continue command”

YES
sampling #1,2,3

UR Ca(OH)2 to TG-8
8. Acquire devices
-6

YES
Owned by other?
NO
nQC = 1

YES

23. By operator’s NO
“continue command”

YES

24. START heating to and MAINTAIN temp. at 170 deg. C (A)


(open XV-0606/0609) (close XV-0607)
rol temperature inside vessel. TIC-0601 which adjusts the position of the control valve TCV-0601A)

ALERT operator to open upper and low


NO
Temp. reach 170 deg. C

YES

By Operator's open upper and low


By Operator's open upper and low
11.END heating supply (A)
(Close XV-0606/ 0609) (close XV-0607)
rol temperature inside vessel. TIC-0601 which adjusts the position of the control valve TCV-0601A)

By operator’s
“continue command

25. START cooling supply to (A) and MAINTAIN temp. at 105 deg. C (A) YES
Start pump P-29 ,(Close Open XV-0606/0609) (Open XV-0607)
rol temperature inside vessel. TIC-0601 which adjusts the position of the control valve TCV-0601B)

NO
Temp. reach 120 deg. C

YES

ALERT operator to
a) ALERT for H2O Adding Acknowledgement (A)
b) Add H2O ______ Kg. (A)

Add H2O ______ Kg. (A)


(30 min. duration pre-set flow rate by adjusting a globe valve VGL-0376)
(FIQ-0610 monitor the mass)

NO
mass reach "set point"

YES

Close XV-0610 (A)

NO
Temp. reach 105 deg. C

YES

ALERT (A) operator to check "water evaporation complete"

NO
Water evaporation "complete"

YES

27. By operator’s NO
“continue command”

YES

ALERT (A) operator to STOP agitator A/B (M)


(STOP agitator AG-TG-8 A/B via HS-8 A/B)

28. Operator to STOP agitator A/B (M)


(STOP agitator AG-TG-8 A/B via HS-8 A/B)
)

NO
Operator checks "complete"
NO
Operator checks "complete"

YES

By operator’s NO
“continue command”

YES

ALERT (A) operator for "QC sampling."

29. QC sampling (M)

NO
30. QC sampling "complete"

YES

31. By operator’s NO
“continue command”

YES

ALERT operator to START Agitator A/B (M)


(START Agitator AG-TG-8 A/B via HS-8 A/B)

32. Operator to START Agitator A/B (M)


(START Agitator AG-TG-8 A/B via HS-8 A/B)
Set speed 8A = 32 RPM
NO
33. Admin. Room QC Signal

YES
ALERT operator to Close upper and lower jacket (M)

Operator's Monitor displays the Acid and Base value


QC (Quality ) : Pass or No Pass
QC (Appearance) : Pass or No Pass

By Operator's Close upper and lower jacket (M)

QC (Quality)
"PASS"
NO

34. By operator’s NO
“continue command”

YES

35. I. START heating to and MAINTAIN temp. at 150 deg. C (A)


(open XV-0606/0609) (close XV-0607)
trol temperature inside vessel. TIC-0601 which adjusts the position of the control valve TCV-0601A)

NO
Temp. reach 150 deg. C

YES

36. QC (Appearance) YES


"PASS"

NO

By operator’s NO
“continue command”

YES

ALERT operator to
I. Add H2O______Kg. from flexible hose (M)

37. Operator to Add H2O ______Kg. from flexible hose (M)


(FIQ-0610 monitor the mass)

NO
mass reach "set point"

YES

38. By operator’s NO
“continue command”

YES
55. Acquire devices
-FQI-0601

YES Owned by other?

Interupt feeding?

YES
ALERT operator to open upper and lower jacket (M)

By Operator's open upper and lower jacket (M)


By Operator's open upper and lower jacket (M)

By operator’s NO
“continue command”
Replete Step 6-8
By operator’s NO
“continue command”

YES

40. START cooling supply to (A) and MAINTAIN temp. at 70 deg. C (A)
Start pump P-29, (Close XV-0606/ 0609) (Open XV-0607)
(TT-0601 control temperature inside vessel. TIC-0601 which adjusts the position of the control valve TCV-0601B)

NO
Temp. reach 99 deg. C

YES

ALERT operator to
a) ALERT for TBO-2 Adding Acknowledgement (A)
b) Add TBO-2 (111001-10T)____kg. (A)

NO
41. By operator’s
“continue command”

YES

Feed TBO-2 (111001-10T)_________kg. (A)


(Start Pump P-2),(Open XV-0602,0603)(Close XV-0601,0604,0605,0635,0636,0629) NO
(FT-0701 monitor the mass flow, FQI-0701 measure the mass ) Owned by

NO Interupt feeding?

NO
mass reach "set point"

YES

Stop Pump P-2, (A)


(Close XV-0602,0603)

ALERT operator to check "complete".

NO
43. Operator check "complete"

YES

44. By operator’s NO
“continue command”

YES
Adjust speed AG-TG-8A = 15 RPM

ALERT operator to Circulation (M)

ALERT operator to
a) Open Tank Bottom Valve (XV-0630) via HS-0630A (M)
b) 3 way Valve (XV-0632) direct to TG-8 via HS-0632 (M)
c) START grease pump (Start Pump P-13 via HS-0630A) (M)

45. Operator to Open Tank Bottom valve (XV-0630) (M)


(Open via via HS-0630)
)

Tank bottom valve NO


is opened
(HS-0630A)

YES

By operator’s NO
“continue command”

YES

Operator to Open 3way valve (XV-0632) to TG-8 (M)


Select "Circulation" via HS-0632 (CYCLE)
)

3 way valve NO
(XV-0632)directs to TG-8 via
HS-0632 (CYCLE)

YES

46. By operator’s NO
“continue command”

YES

47. Operator to start grease pump (XV-0633)


(Start Pump P-13 via HS-0630 (A)

NO
Grease pump is started
via HS-0630 A

YES

II. Run for 45 min.

ALERT (A) operator to STOP agitator A/B (M)


(STOP agitator AG-TG-8 A/B via HS-8 A/B

48. Operator to STOP agitator A/B (M)


(STOP agitator AG-TG-8 A/B via HS-8 A/B
)
ALERT (A) operator for "QC sampling".

49. QC sampling (M)

NO
50. QC sampling "complete"

YES

51. By operator’s NO
“continue command”

YES

ALERT operator to START Agitator A/B (M)


(START Agitator AG-TG-8 A/B via HS-8 A/B)

52. Operator to START Agitator A/B (M)


(START Agitator AG-TG-8 A/B via HS-8 A/B)
Set speed 8A = 15 RPM

NO
53. Admin. Room QC Signal

YES

Operator's Monitor displays the Acid and Base value.

YES
"QC PASS"

NO

54. By operator’s NO
“continue command”

YES

I. By operator’s NO
“Command”

YES
cquire devices
0601

Feed TBO-2 (111001-10T)__________Kg. (A)


NO (Start Pump P-2),(Open XV-0602,0603)(Close XV-0601,0604,0605,0635,0636,0629)
ned by other? (FT-0701 monitor the mass flow, FQI-0701 measure the mass )

NO
?

NO
mass reach "set point"
mass reach "set point"

YES

Stop Pump P-2,


(Close XV-0602,0603)

ALERT operator to check “complete”.

NO
56. Operator checks "complete"

YES

57. By operator’s NO
“continue command”

YES

ALERT operator to START Agitator A/B (M)


(START Agitator AG-TG-8 A/B via HS-8 A/B)

Operator to START Agitator A/B (M)


(START Agitator AG-TG-8 A/B via HS-8 A/B)

NO
Operator checks "complete"

YES

Temp reach
70 deg. C

YES

59. By operator’s
“continue command”

YES

ALERT (A) operator to STOP agitator A/B (M)


(STOP agitator AG-TG-8 A/B via HS-8 A/B)

60. I. Operator to STOP agitator A/B (M)


(STOP agitator AG-TG-8 A/B via HS-8 A/B)

ALERT operator to pour


Additive I ,II,III,IV,V
ALERT operator to pour
Additive I ,II,III,IV,V

Monitor displays the amounts

II. Add Additive I (212053-0400 )_________ Kg. (M)

III. Add Additive II (212053-0200)_________ Kg. (M)

IV. Add Additive III (212026-0000)_________ Kg. (M)

V. Add Additive IV(212028-0000) _________ Kg. (M)

VI. Add Additive V (212028-0200)_________ Kg. (M)

61. Operator checks "complete"

YES

62. By operator’s
“continue command”

YES

ALERT operator to START Agitator A/B (M)


(START Agitator AG-TG-8 A/B via HS-8 A/B)

63. VI. Operator to START Agitator A/B (M)


(START Agitator AG-TG-8 A/B via HS-8 A/B)
Set speed 8A = 15 RPM

64. Run for 45 min.

ALERT operator to check “complete”.

65. Operator checks "complete"

YES

ALERT operator to Flush line (M) (2 Drums)

66. operator to Flush line (M) (2 Drums)


66. operator to Flush line (M) (2 Drums)

67. By operator’s
“Continued command”

YES

ALERT (A) operator to STOP agitator A/B (M)


(STOP agitator AG-TG-8 A/B via HS-8A/B)

Operator to STOP agitator A/B (M)


(STOP agitator AG-TG-8 A/B via HS-8A/B)
)

ALERT (A) operator for "QC sampling."

68. QC sampling for final inspection (M)

69. QC sampling "complete"

YES

70. By operator’s
“continue command”

YES

ALERT operator to START Agitator A/B (M)


(START Agitator AG-TG-8 A/B via HS-10A/B)

Operator to START Agitator A/B (M)


(START Agitator AG-TG-8 A/B via HS-10A/B
)

71. Admin. Room QC Signal

YES

Operator's Monitor displays the Acid and Base value.

72. "QC PASS"


(Admin Room )

NO

ALERT (A) operator to STOP agitator A/B (M)


(STOP agitator AG-TG-8 A/B via HS-8 A/B

I. Operator to STOP agitator A/B (M)


(STOP agitator AG-TG-8 A/B via HS-8 A/B
)

74. II. By operator’s


“continue command”
74. II. By operator’s
“continue command”

YES
75. Acquire devices
-FQI-0601

Feed TBO-2 (111001-10T)__________Kg. (A)


YES (Start Pump P-2),(Open XV-0602,0603)
Owned by other? (Close XV-0601,0604,0605,0635,0636,0629)
(FT-0701 monitor the mass flow, FQI-0701 measure the mass )

NO
Interupt feeding?

mass reach "set point"

YES

Stop Pump P-2 (A)


(Close XV-0602,0603)

ALERT operator to check “complete”.

76. Operator checks "complete"

YES

77. By operator’s
“continue command”

YES

Stop AG-TG-8 A/B

78. ALERT operator to pour


Additive I,II,III,IV,V

Monitor displays the amounts

III. Add Additive I (212053-0400)_________ Kg. (M)

IV. Add Additive II (212053-0200)_________ Kg. (M)

V. Add Additive III (212026-0000)_________ Kg. (M)

VI. Add Additive IV(212028-0000) _________ Kg. (M)


VI. Add Additive IV(212028-0000) _________ Kg. (M)

VII. Add Additive V (212028-0200)_________ Kg. (M)

Start AG-TG-8A/8B
Set speed 8A = 15 RPM

79. Operator checks "complete"

YES

80. By operator’s
“continue command”

YES

ALERT operator to START Agitator A/B (M)


(START Agitator AG-TG-8 A/B via HS-8A/B)

VIII. Operator to START Agitator A/B (M)


(START Agitator AG-TG-8 A/B via HS-8 A/B
)

IX. Run for 45 min.

ALERT (A) operator for "QC sampling."


(Take sample at Filling Line)

QC sampling (M)
(Take sample at Filling Line)
42. Acquire devices
-FQI-0601

YES
Owned by other?

Interupt feeding?

YES
ch NO
C

tor’s NO
mmand”

P agitator A/B (M)


A/B via HS-8 A/B)

agitator A/B (M)


A/B via HS-8 A/B)

to pour
II,IV,V
to pour
II,IV,V

he amounts

00 )_________ Kg. (M)

200)_________ Kg. (M)

000)_________ Kg. (M)

00) _________ Kg. (M)

200)_________ Kg. (M)

NO
s "complete"

tor’s NO
mmand”

Agitator A/B (M)


A/B via HS-8 A/B)

T Agitator A/B (M)


A/B via HS-8 A/B)
15 RPM

ck “complete”.

NO
s "complete"

ine (M) (2 Drums)

ne (M) (2 Drums)
ne (M) (2 Drums)

ator’s NO
mmand”

OP agitator A/B (M)


A/B via HS-8A/B)

itator A/B (M)


A/B via HS-8A/B)

"QC sampling."

al inspection (M)

NO
"complete"

ator’s NO
mmand”

T Agitator A/B (M)


A/B via HS-10A/B)

gitator A/B (M)


8 A/B via HS-10A/B

NO
m QC Signal

e Acid and Base value.

ASS" YES
om )

P agitator A/B (M)


A/B via HS-8 A/B

itator A/B (M)


A/B via HS-8 A/B

ator’s NO
mand”
ator’s NO
mand”

__________Kg. (A)
XV-0602,0603)
,0635,0636,0629)
I-0701 measure the mass )
By operator’s NO
“continue command”

YES

NO
t point" ALERT operator to
START Filling Process (M)

P-2 (A) 82. Operator to


2,0603) START Filling Process (M)

eck “complete”.
NO
Operator checks "Filling completed"

YES
NO
"complete"

83. By operator’s NO
“continue command”

tor’s NO YES
mand”

ALERT operator to
STOP Agitator A/B and END Cooling Supply, Circulation, Filling (M)

-8 A/B

or to pour
II,IV,V 84. Operator to
STOP Agitator A/B (Stop AG-TG-8 A/B via HS-8 A/B)
END Cooling Supply Stop pump P-29 (Close XV-0607)
Circulation Stop pump P-13 , (Close XV-0630), (Close XV-0632)
Filling (M)
he amounts

00)_________ Kg. (M) 85. END

200)_________ Kg. (M)

000)_________ Kg. (M)

000) _________ Kg. (M)


000) _________ Kg. (M)

200)_________ Kg. (M)

8A/8B
15 RPM

NO
s "complete"

tor’s NO
mmand”

T Agitator A/B (M)


8 A/B via HS-8A/B)

Agitator A/B (M)


8 A/B via HS-8 A/B

"QC sampling."
lling Line)

g (M)
illing Line)
Start

NO
1. By operator’s
“continue command”

YES

Feed TBO 1 __kg. (A)


(Start Pump P-1),(Open XV-0601,0629)(Close XV-0602,0604,0605,0635,0636,0603)
(FT-0601 monitor the mass flow, FQI-0601 measure the mass )

NO
mass reach
"set point"

YES

(Close XV-0601,0629)

ALERT operator to check “complete”.

Operator checks NO
"complete"
YES

NO
2. By operator’s
“continue command”

YES

Feed TBO 2 __kg. (A)


(Start Pump P-2),(Open XV-0602,0629)(Close XV-0601,0604,0605,0635,0636,0603)
(FT-0601 monitor the mass flow, FQI-0601 measure the mass )
NO
mass reach
"set point"

YES

(Close XV-0602,0629)

ALERT operator to check “complete”.

Operator checks NO
"complete"

YES

NO
3. By operator’s
“continue command”

YES

Feed TBO 4 __kg. (A)


(Start Pump P-4),(Open XV-0702,0720)(Close XV-0701,0703,0704,0705,0710,0716)
(FT-0701 monitor the mass flow, FQI-0701 measure the mass )

NO
mass reach
"set point"

YES

(Close XV-0702,0720)

ALERT operator to check “complete”.


ALERT operator to check “complete”.

Operator checks NO
"complete"
YES

4.ALERT operator to Start AG-TC-1

Start AG-TC-1

5.ALERT operator to pour Ca(OH)2 ......kg (M)and mix 20 min

Operator to pour Ca(OH)2 and mix 20 min

20 min.

ALERT operator to check “complete”.

NO
Operator checks “complete”

YES

6.ALERT operator to check all valves TC-1 to


TG-8 or TG-10
operator check all valves TC-1 to TG-8 or TG-10

NO
1. By operator’s
“continue command”

YES

ALERT operator to Feed Ca(OH2) slurry Kg. to TG-8 or TG-10


by Start Pump P-25 and then stop pump P-25

Start Pump P-25

Stop Pump P-25

NO
9. By operator’s
“continue command”

YES

Feed TBO 1 __kg. (A)


(Start Pump P-1),(Open XV-0601,0629)(Close XV-0602,0604,0605,0635,0636,0603)
(FT-0601 monitor the mass flow, FQI-0601 measure the mass )

NO
mass reach
"set point"

YES

(Close XV-0601,0629)
ALERT operator to check “complete”.

Operator checks NO
"complete"

YES

NO
10. By operator’s
“continue command”

YES

Feed TBO 2 __kg. (A)


(Start Pump P-2),(Open XV-0602,0629)(Close XV-0601,0604,0605,0635,0636,0603)
(FT-0601 monitor the mass flow, FQI-0601 measure the mass )

NO
mass reach
"set point"

YES

(Close XV-0602,0629)

ALERT operator to check “complete”.

Operator checks NO
"complete"
YES

NO
11. By operator’s
“continue command”
11. By operator’s
“continue command”

YES

Feed TBO 4 __kg. (A)


(Start Pump P-4),(Open XV-0702,0720)(Close XV-0701,0703,0704,0705,0710,0716)
(FT-0701 monitor the mass flow, FQI-0701 measure the mass )

NO
mass reach
"set point"

YES

(Close XV-0702,0720)

ALERT operator to check “complete”.

NO
Operator checks
"complete"

YES

12.ALERT operator to Feed Ca(OH2) slurry Kg. to TG-8 or TG-10


by Start Pump P-25 and then stop pump P-25

Start Pump P-25

Stop Pump P-25

NO
13.Operator checks
"complete"

YES
End
636,0603)

636,0603)
710,0716)
When Emerson tested seq running. please clarify with Client need to add.
ALERT operator to check “complete”.

NO
Operator checks “complete”

YES

36,0603)
36,0603)
10,0716)
Feed Li-OH solution from TL-1 (212009-0000) 100% %wt (A)
(Start Pump P-7 via HS-0307 or Local Switch)
(FI-0502 monitor the mass)

mass reach "set point"

YES

Stop Pump P-7 via HS-0307 / Local Switch

ALERT operator to check “complete”.


100% %wt (A)
Switch)

NO

e”.