Professional Documents
Culture Documents
ACS1000
Medium Voltage Drives
Table of Contents
Table of Contents ................................................................................................................ 3
1 ACTUAL SIGNALS
Measured and calculated values
2 ACTUAL SIGNALS
Measured or calculated water cooling values
3 ACTUAL SIGNALS
Measured or calculated values in the speed and torque reference chain.
4 ACTUAL SIGNALS
Measured or calculated values from basic IOEC 1 2.
DI6 DI1
Figure
DI13 DI8
Figure
DI6 DI1
Figure
DI13 DI8
Figure
5 ACTUAL SIGNALS
Data values
DO6 DO2
Figure
DO6 DO2
Figure
Group 6 INFORMATION
6 INFORMATION
Information on the actual software version on the AMC board.
7 CONTROL WORDS
ABB drive profile control word.
8 STATUS WORDS
Status signals of the drive according to the ABB Drive Profile.
n ref
AT SETPOINT
MARGIN
n act
0
t
8.01 MSW Bit 8 - AT SETPOINT
Figure
Group 11 START/STOP/DIR
11 START/STOP/DIR
These parameter values can only be altered when the ACS1000 is stopped.
11.01 Ext1Strt/Stop/Dir
This parameter defines the connections and the source of Start, Stop, and Direction commands for
external control location 1 (EXT1).
VALUE NAME MEANING
1 NOT SEL external control location is not selected
2 DI1 (two-wire Start/Stop is connected to DI1 – IOEC2. Direction is fixed to
connection for forward.(0V DC on DI1 – IOEC2 = Stop; 24V DC on DI1 –
Start/Stop) IOEC2 = Start)
3 DI1,2 (two-wire Start/Stop is connected to digital input DI1 – IOEC2 as above.
connection for Direction is connected to digital input DI2 – IOEC2.(0V DC on
Start/Stop and Direction) DI2 – IOEC2 = Forward; 24V DC on DI2 – IOEC2 = Reverse)
4 DI1P,2P (three-wire Start/Stop commands are given by means of momentary
connection for push-buttons (P stands for „pulse“). The start push-button is
Start/Stop) normally open and connected to digital input DI1 – IOEC2.
The Stop button is normally closed and connected to digital
input DI2 – IOEC2. Multiple start push-buttons are connected
in parallel; stop-push buttons are connected in series.
5 DI1P,2P,3 (three-wire Start / Stop connected as with DI1P,2P. Direction is
connection for connected to digital input DI3 – IOEC2.(0V DC on DI3 =
Start/Stop and Direction) Forward; 24V DC on DI3 = Reverse)
6 DI1P,2P,3P (three-wire Start and Direction commands are given simultaneously with
connection for Start two separate momentary push-buttons (P stands for „pulse“).
Forward, Start Reverse, The stop push-button is normally closed and connected to
and Stop) digital input DI3 – IOEC2. Start-Forward and Start-Reverse
push-buttons are normally open and connected to digital
inputs DI1 – IOEC2 and DI2 – IOEC2 respectively. Multiple
start push-buttons are connected in parallel and multiple Stop
push-buttons are connected in series.
7 DI 6 (two wire Start/Stop connected to DI6 – IOEC2. Direction is fixed
connection for according to parameter 11.3 DIRECTION.(0V DC on DI6 =
Start/Stop) Stop; 24V DC on DI6 = Start)
8 DI6,5 (two-wire Start/Stop is connected to digital input DI6 – IOEC2 as above.
connection for Direction is connected to digital input DI5 – IOEC2.(0V DC on
Start/Stop, and DI5 – IOEC2 = Forward; 24V DC on DI5 – IOEC2 = Reverse)
Direction)
9 KEYPAD The Start/Stop and Direction commands are given from the
Control Panel keypad when external control location 1 is
active.
10 COMM.MODULE The Start/Stop and Direction commands are given from
COMMON MODULE when 75.04 is set to 2 or 3.
11 COMM.CH4 The Start/Stop and Direction commands are given from
COMMON MODULE CH4 when 75.05 is set to 2 or 3.
Unit: Type: I Min: 1 Max: 11 Def: 3 Int. scaling:1 == 1
11.03 Direction
This parameter allows you to fix the rotation of the motor to FORWARD or REVERSE. If you select
REQUEST the direction is selected by digital inputs as defined by parameters 11.1 EXT1
STRT/STOP/DIR and 11.2 EXT2 STRT/STOP/DIR or by keypad push-buttons.
VALUE NAME MEANING
1 FORWARD
2 REVERSE
3 REQUEST
Unit: Type: I Min: 1 Max: 3 Def: 1 Int. scaling:1 == 1
CDP 312
CONTROL PANEL
LO
C
R EM
12.02
EXT1 / EXT2
SELECT
10
REMOT E FO RW ARD
DIRECTION
C OM M.M OD ULE
EX T2
RE VERSE
DI 1.. .6 2.. .8
K EYPAD 9
AMC3-bo ar d CH 0
C OM M.M OD ULE 10
Comm. Modul e
REM
pu sh bu tto ns o n
contro l secti on door
IOEC2 - DI9
DI 6 Feedback MCB Status open
IO EC 1: OffLin
DI 7
e
OnL ine
IOEC2 - DI10
Feedback MCB Status closed
IOEC2 - DI11
MCB MCB COMMAND
rem ote con tr ol location
E xt1 / E xt2
Feedback MCB Status Available LOGIC
IO EC 2: DI 1...6 N OT SE LEC TE D 1 Open / Close
LO C AL
DI 7, 13
Def au l t: DI7,13 2...9 EXT1
N OT SE LE CTE D 1 REMO TE
C OM M.M OD ULE 10
12 REFERENCE SELECT
The following parameters (except those marked with “O”) can be altered while the ACS1000 is
running.
E XT RE F1 S ELE CT (12.03)
12.01
S PE E D M AX
(2 0.02) Ma x
KE YPAD S cal ing: 1
mi n .. . ma x speed
Min 2 .. .11 RE F
RE F1 IN T ERN AL 2 S PE E D M IN = S PE E D M IN .. . S PE E D M AX
see 1 2 .. .13
3 (2 0.01)
Fi gure 13 -2 RE F2 IN T ERN AL
4
+
5
-
6
x E XT RE F1 M AX
7 (1 2.05) Ma x
M IN S cal ing:
mi n .. . ma x speed
8 Min
M AX E XT RE F1 M IN = E XT RE F1 M IN .. . E XT RE F1 M AX
(1 2.04)
ACC TIM E 2
(2 2.04)
OCOM
verr.M. RE F -
S ystem 12 E XT RE F1 M AX
Da taS e t 1 Va l. 2
(1 2.05) Ma x
(03.24) 13 S cal ing:
+ 0 .. . 20000
14 0 = 0 .. . E XT RE F1 M AX
x
Figure
Figure
E XT RE F2 S ELE CT (12.06)
12.01
S PE E D M AX
(2 0.02) Ma x
KE YPAD S cal ing: 1
mi n .. . ma x speed
Min 2 .. .11 RE F
RE F1 IN T ERN AL 2 S PE E D M IN = S PE E D M IN .. . S PE E D M AX
see 1 2 .. .13
3 (2 0.01)
Fi gure 13 -2 RE F2 IN T ERN AL
4
+
5
-
6
x E XT RE F2 M AX
7 (1 2.08) Ma x
M IN S cal ing:
mi n .. . ma x speed
8 Min
M AX E XT RE F2 M IN = E XT RE F2 M IN .. . E XT RE F2 M AX
(1 2.07)
ACC TIM E 2
(22.04)
OCOM
verr.M. RE F -
S ystem 12 E XT RE F2 M AX
Da taS e t 1 Va l. 3
(1 2.08) Ma x
(03.25) 13 S cal ing:
+ 0 .. . 20000 resp. 0 .. . 10000
14 0 = 0 .. . E XT RE F2 M AX
x
The range of the analogue input signal is set by parameter 13.03 and 13.08. EXT REF2 is a speed or torque reference
of the motor, or a process reference depending on the selected Application Macro. In the SCALAR control mode EXT
REF2 is a frequency reference given in %.
The ACS1000 can be controlled (i.e. reference, Start/Stop and Direction commands can be given) from two External
control locations or from the Local control location, Control Panel Keypad. The selection between Local control and
External control can be done with the LOC REM key on the Control Panel Keypad.
External Control
When the ACS1000 is in External control, the commands are given primarily through the control terminal blocks on the
IOEC 1 and 2 board (digital and analogue inputs). Commands can also be given through the control panel or a fieldbus
adapter module.
12.09 MotPotTracking
With this parameter it is possible to activate a so-called “tracking function”.
The motor potentiometer will be initialised with the actual speed reference value after changing from “Externa
Control Location” 2 to 1 and vice versa.
VALUE NAME MEANING
0 NO Tracking function is not active
1 YES Tracking function is active
S oftwa re
MOT O R-POT E NT IO MET ER
RE F 1 (REF2)
DI3,4 - IOEC2
2 2.0 4
Accel Time 2
13 ANALOGUE INPUTS
The analogue input value can be selected in milliamps or volts by means of a HW-switch.
13.01 AutoOffsetCalib
Automatic offset calibration for the analogue inputs of IOEC 1 & 2. Offset value will be stored into the
appropriate AIx OFFSET Iox parameter.
Note: Even if 0s as the minimum value is selected, the signal is still filtered with a time constant of
20ms due the signal interface hardware. This cannot be changed by any parameter.
Figure
13.12HIGH VALUE: 20 mA (10V)= 200°CÞ Setting = 2000 (max value multiplied by 10)
13.13LOW VALUE:4 mA ( 2V)= 0°CÞSetting = 0 (min value multiplied by 10)
13.14MIN VALUE:4 mA ( 2V)= ÞSetting = 4mA (2V)
Þ MOTOR WDG TMP PHASE U:4 ... 20mA (2 ... 10V) = 0 ... 180°C
The actual motor winding temperature in phase U is shown in parameter 04.06 MotorWdgTmpPhaseU (in °C).
Figure
14.01 DO2Group+IndexIO1
A binary signal (i.e. from a status word) is assigned to digital output DO2 by setting this parameter to the
parameter group and index from which the signal is to be taken from. Additionally the bit number that
identifies the signal within the status word has to be selected with the next parameter. The format is
(x)xyy, where (x)x the group and yy is the index of the desired signal.
Example:
If Par. 14.01 is set to “801” and 14.02 is set to “1” , digital output DO2 is active when 8.01 MAIN
STATUS WORD / BIT 1 is “1”. If Par. 14.01 is set to “702” and 14.02 is set to “12,13 or14” , digital
output DO1 is controlled from the overriding system by 7.02 AUX CONTROL WORD 2.
By default, DO2 is the TrafoProtReset signal (Par. 8.04 / Bit 12)
NOTE!
With an ACS 1000i (par. 112.05 ‘’ = ‘Air&Trafo’) DO2 is fixed to the ‘TrafoProtReset’ command.
Unit: Type: I Min: 0 Max: 30000 Def: 804 Int. scaling:1 == 1
14.04 DO1Group+IndexIO2
A binary signal (i.e. from a status word) is assigned to digital output DO1 by setting this parameter to the
parameter group and index from which the signal is to be taken from. Additionally the bit number that
identifies the signal within the status word has to be selected with the next parameter. The format is
(x)xyy, where (x)x the group and yy is the index of the desired signal.
Example:
If Par. 14.04 is set to “801” and 14.05 is set to “1” , digital output DO1 is active when 8.01 MAIN
STATUS WORD / BIT 1 is “1”. If Par. 14.04 is set to “702” and 14.05 is set to “12,13 or14” , digital
output DO1 is controlled from the overriding system by 7.02 AUX CONTROL WORD 2.
Example:
If Par. 14.07 is set to “801” and 14.08 is set to “2”, digital output DO2 is active when 8.01 MAIN
STATUS WORD / BIT 2 is “1”. If Par. 14.07 is set to “702” and 14.08 is set to “12,13 or14”, digital output
DO1 is controlled from the overriding system by 7.02 AUX CONTROL WORD 2.
14.10 DO3Group+IndexIO2
A binary signal (i.e. from a status word) is assigned to digital output DO3 by setting this parameter to the
parameter group and index from which the signal is to be taken from. Additionally the bit number that
identifies the signal within the status word has to be selected with the next parameter. The format is
(x)xyy, where (x)x the group and yy is the index of the desired signal.
Example:
If Par. 14.10 is set to “801” and 14.11 is set to “7”, digital output DO3 is active when 8.01 MAIN
STATUS WORD / BIT 7 is “1”. If Par. 14.10 is set to “702” and 14.11 is set to “12,13 or14”, digital output
DO3 is controlled from the overriding system by 7.02 AUX CONTROL WORD 2.
Example:
If Par. 14.13 is set to “801” and 14.14 is set to “3”, digital output DO4 is active when 8.01 MAIN
STATUS WORD / BIT 3 is “1”. If Par. 14.13 is set to “702” and 14.14 is set to “12,13 or14”, digital output
DO4 is controlled from the overriding system by 7.02 AUX CONTROL WORD 2.
Example
Programming of the digital output signal IOEC2 – D01: The digital output should be closed if the drive is running.
15.01 AO1Group+IndexIO1
A numerical value of the AMC-table is assigned to analogue output by setting parameter 15.01 to the
parameter group and index the value is to taken from. The format is (x)xyy, where (x)x the group and yy
is the index of the desired signal.
Example:
When the actual value of the MOTOR FREQUENCY is to be read out at AO1 - IOEC1, parameter 15.01
is set to 106 with 1 representing the group and 06 representing the index.
A numerical value from a higher-level control system can also transferred to the analogue output. The
data set where the value is transmitted into the AMC-table is directed to one of the DATA parameters
(19.01…19.08) by means of either parameters 90.01...90.12 or 92.01…93.12 (see Figure 19-1). The
value is then assigned to the analogue output by setting 15.01 to the group and index of the desired
DATA parameter (for example: 1901 Þ 19 = group , 01 = index)
Note!
In case of EC fans this analog output cannot be used as free programmable, since it's used for fan
speed reference.
Unit: Type: I Min: 0 Max: 30000 Def: 106 Int. scaling:1 == 1
Example:
When the actual value of the MOTOR TORQUE is to be read out at AO2 – IOEC1, parameter 15.06 is
set to 109 with 1 representing the group and 09 representing the index.
A numerical value from a higher-level control system can also transferred to the analogue output. The
data set where the value is transmitted into the AMC-table is directed to one of the DATA parameters
(19.01…19.08) by means of either parameters 90.01...90.12 or 92.01…93.12 (see Figure 19-1). The
value is then assigned to the analogue output by setting 15.06 to the group and index of the desired
DATA parameter (for example: 1901 Þ 19 = group , 01 = index)
NOTE!
With ACS 1000i the output IOEC1 - AO2 is fix set to 4mA to provide a current source for temperature
measurements and the settings of 15.06…10 are irrelevant.
Unit: Type: I Min: 0 Max: 30000 Def: 109 Int. scaling:1 == 1
Example:
When the actual value of the MOTOR SPEED is to be read out at AO1 – IOEC2, parameter 15.11 is set
to 102 with 1 representing the group and 02 representing the index.
A numerical value from a higher-level control system can also transferred to the analogue output. The
data set where the value is transmitted into the AMC-table is directed to one of the DATA parameters
(19.01…19.08) by means of either parameters 90.01...90.12 or 92.01…93.12 (see Figure 19-1). The
value is then assigned to the analogue output by setting 15.11 to the group and index of the desired
DATA parameter (for example: 1901 Þ 19 = group , 01 = index)
15.16 AO2Group+IndexIO2
A numerical value of the AMC-table is assigned to analogue output by setting parameter 15.16 to the
parameter group and index the value is to taken from.The format is (x)xyy, where (x)x the group and yy
is the index of the desired signal.
Example:
When the actual value of the MOTOR TORQUE FILT is to be read out at AO2 – IOEC2, parameter
15.16 is set to 108 with 1 representing the group and 08 representing the index.
A numerical value from a higher-level control system can also transferred to the analogue output. The
data set where the value is transmitted into the AMC-table is directed to one of the DATA parameters
(19.01…19.08) by means of either parameters 90.01...90.12 or 92.01…93.12 (see Figure 19-1). The
value is then assigned to the analogue output by setting 15.16 to the group and index of the desired
DATA parameter (for example: 1901 Þ 19 = group , 01 = index)
After a process stop command is given, the drive is stopping according to the following steps:
D=1 SCALAR
Process Stop
Mode
21.03 Process Stop MCB Ctrl
DTC if "SCALAR" - mode is selected,
21.04
stop mode is fix ed to
Process Stop "RAMP STOP"
0 Trip 1b
16.01 n =0 MCB Opening
Process Stop
NOT USED RAMP STOP
& "Fault"
1 1
1 Trip 1a
DI8 - IOEC2 2 2 TORQ STOP MCB Stay Closed
-1 >
Process Stop
COMM.MOD ULE 3 3 COAST STOP & "Alarm"
(7.06 - Bit12)
Process Stop Ramp RAMP STOP MODE TORQ STOP MODE COAST STOP MODE
n n n
22.06 (rpm) (rpm) (rpm)
RAMP FUNCTION
t (s)
Note!
The selection comm. module may not be used at a follower drive, because the process stop bit is never
set in the follower control word par. 7.07.
NAME VALUE MEANING
NOT USED 1
DI8-IO2 2
COMM.MODULE 3
COMM.CH4 4
Unit: Type: I Min: 1 Max: 4 Def: 2 Int. scaling:1 == 1
16.03 Passcode
This parameter selects the pass code for the Parameter Lock. The default value of this parameter is 0.
In order to open the Parameter Lock changes the value to 358. After the Parameter Lock is opened the
value is automatically changed back to 0.
Unit: Type: I Min: 0 Max: 9999 Def: 0 Int. scaling:1 == 1
16.04 FaultResetSel
Selects the source for the fault reset signal. The signal resets the drive after a fault trip if the cause of
the fault is no longer exists.
VALUE NAME MEANING
1 KEYPAD Fault reset is executed from the control panel keypad only (RESET -
Key).
2 DI12 – IO2 Control Panel in REMOTE – Mode:Reset is activated by a rising
(positive) edge of the digital input signal DI12 - IOEC2.Control Panel
in LOCAL – Mode:Reset is activated by control panel keypad (RESET
- Key)
3 ON STOP Control Panel in REMOTE – Mode:Fault reset is executed along with
the stop signal. Control Panel in LOCAL – Mode:Fault reset is
executed along with the stop signal or from control panel keypad
(RESET - Key)
4 COMM.MODULE Control Panel in REMOTE – Mode:
5 COMM.CH4 Control Panel in REMOTE - MODE: Fault reset is executed by ACDA
(CH4)
Unit: Type: I Min: 1 Max: 5 Def: 1 Int. scaling:1 == 1
When the state of the specified digital input changes from high to low User Macro 1 is loaded. When the
state of the specified digital input changes from low to high User Macro 2 is loaded.
NOTE!
The user macro can be changed via a digital input only when the MCB is switched Off. During the
change of the macro the drive will not start.
The value of this parameter is not included in the User Macro. A setting once made remains despite the
User Macro change.
Always save the user macro by parameter 99.13 after changing any parameter settings. The last
settings saved by the user are loaded into use whenever the power is switched off and on again (see
also Par. 99.13 APPLICATION MACRO)
VALUE NAME MEANING
1 NOT SEL User macro change is not possible via digital input or field bus.
2 DI1 – IO2 Falling edge of digital input: User macro 1 is loaded.Rising edge of
digital input: User macro 2 is loaded.
3 DI2 – IO2 Falling edge of digital input: User macro 1 is loaded.Rising edge of
digital input: User macro 2 is loaded.
4 DI3 – IO2 Falling edge of digital input: User macro 1 is loaded.Rising edge of
digital input: User macro 2 is loaded.
5 DI4 – IO2 Falling edge of digital input: User macro 1 is loaded.Rising edge of
digital input: User macro 2 is loaded.
6 DI5 – IO2 Falling edge of digital input: User macro 1 is loaded.Rising edge of
digital input: User macro 2 is loaded.
7 DI6 – IO2 Falling edge of digital input: User macro 1 is loaded.Rising edge of
digital input: User macro 2 is loaded.
8 COMM.MODULE Falling edge of ACW1 – Bit 04: User macro 1 is loaded into use.
Rising edge of ACW1 – Bit 04: User macro 2 is loaded into use.
16.06 OldUserPasscode
This parameter authorises the setting of a new pass code for the Parameter Lock. After the
OldUserPasscode is opened the value is automatically changed back to 0.
Unit: Type: I Min: 0 Max: 999 Def: 358 Int. scaling:1 == 1
16.07 NewUserPasscode
This parameter selects the new pass code for the Parameter Lock and stores it into the flash. After the
NewUserPasscode is set, the value is automatically changed back to 0.
Unit: Type: I Min: 0 Max: 999 Def: 0 Int. scaling:1 == 1
This parameter is used to activate (or de-activate) bit number B01 & B02 of FBA Control Word (CH0)
if selected. If the parameter is set to DISABLED, the signals are set internally to constant 1.
NOTE! This parameter is only active if FBA communication module is used (parameter 75.04 FBA
CommModule is set to DSET1 R/W or DSET10 R/W).
Group 17 UTILITIES
17 UTILITIES
Group 17 allows the monitoring of several internal values.
17.01 ProbeVariable
(161.26) Parameter 17.01 is used to choose one of the available entities.
Parameter 17.02, 17.03, 17.04 change their meaning depending on what is chosen in parameter 17.01.
For DriveWindow users, this means that after changing parameter 17.01 the complete parameter list
should be uploaded again. Otherwise, the name of parameters 17.02 - 17.04 and possibly the Unit
name will not be correct, even though the displayed numbers are correct.
VALUE NAME MEANING
0 InvCurrent U
1 InvCurrent V
2 InvCurrent W
3 FilCurrent U
4 FilCurrent V
5 FilCurrent W
6 MotCurrent U
7 MotCurrent V
8 MotCurrent W
9 GndCurrent
10 StaCurrent X
11 StaCurrent Y
12 InvVoltage X
13 InvVoltage Y
14 FilVoltage X
15 FilVoltage Y
16 DCVoltage 1
17 DCVoltage 2
18 DCVoltageTot
19 DCVoltageDif
Unit: Type: I Min: 0 Max: 19 Def: 0 Int. scaling:
18 PROCESS SPEED
This parameter can be altered while the ACS1000 running.
18.01 Scale
This parameter matches the process speed to the motor speed. The value of this parameter
corresponds to the greater one of the absolute value defined by parameter 20.01 and 20.02, maximum
speed and minimum speed. The process speed is displayed with one decimal. When the value of this
parameter is set to 1, the possible values of the process speed display are 0.1, 0.2, 0.3…0.9, 1.0. The
value 1.0 corresponds to, for example, 1500rpm, if it is set at the maximum speed, and the absolute
value of the minimum speed is smaller.
Unit: Type: R Min: 1 Max: 100000 Def: 100 Int. scaling:1 == 1
18.02 Unit
Selection of the Unit of the process speed.
NAME VALUE MEANING
NO 1
rpm 2
% 3
m/s 4
Unit: Type: R Min: 1 Max: 4 Def: 3 Int. scaling:1 == 1 xx
19.01 Data 1
Parameter setting or reading from the overriding system. Example:Signal from the Dataset 18 Index 3 is
required for the trending measurement in the DriveWindow tool. Set parameter 90.15 DATASET 18 VAL
3 to the value 1901 (group19 + index 01). Assign parameter 19.01 DATA 1 to the selected trending
channel in DriveWindow.
Unit: Type: R Min: -32768 Max: 32767 Def: Int. scaling:1 == 1
19.02 Data 2
See 19.01 DATA 1
Unit: Type: R Min: -32768 Max: 32767 Def: Int. scaling:1 == 1
19.03 Data 3
See 19.01 DATA 1
Unit: Type: R Min: -32768 Max: 32767 Def: Int. scaling:1 == 1
19.04 Data 4
See 19.01 DATA 1
Unit: Type: R Min: -32768 Max: 32767 Def: Int. scaling:1 == 1
19.05 Data 5
See 19.01 DATA 1
Unit: Type: R Min: -32768 Max: 32767 Def: Int. scaling:1 == 1
19.06 Data 6
See 19.01 DATA 1
Unit: Type: R Min: -32768 Max: 32767 Def: Int. scaling:1 == 1
19.07 Data 7
See 19.01 DATA 1
Unit: Type: R Min: -32768 Max: 32767 Def: Int. scaling:1 == 1
19.08 Data 8
See 19.01 DATA 1
Unit: Type: R Min: -32768 Max: 32767 Def: Int. scaling:1 == 1
ParAssign1
Read Parameter
ParAssign1ReadPar NOT USED
19.21 Group & Index
ParAssign1 Read Value (PA1RV) DIRECT ParAssign1Wr iteValue
Output ParAssign1 Sc aled Value (PA1SV)
MULT 19.23
R1 DIV
MUL
(R1*R2)
ParAssign1 Scale ParAssign1
19.22 R2 Wr ite Parameter
Input
ParAssign1WritePar
R1 19.24 Group & Index
DIV
(R1:R2)
R2
Example:If Par. 19.21 is set to “412” the analog input signal 1 of IOEC 1 is copied to signal
PA1RV.
Unit: Type: I Min: 0 Max: 30000 Def: 0 Int. scaling:
19.24 ParAssign1WritePar
Parameter selects the group and the index to where the value of PA1WV is sent. The format
is (x)xyy, where (x)x is the group and yy is the index of the desired signal.
Example:If Par. 19.24 is set to “2202” the value of PA1WV is sent to parameter 22.02
ACCEL TIME 1.
Unit: Type: I Min: 0 Max: 30000 Def: 0 Int. scaling:
Example:
If Par. 19.26 is set to “412” the analog input signal 1 of IOEC 1 is copied to signal PA2RV.
Unit: Type: I Min: 0 Max: 30000 Def: 0 Int. scaling:
19.29 ParAssign2WritePar
Parameter selects the group and the index to where the value of PA2WV is sent. The format
is (x)xyy, where (x)x is the group and yy is the index of the desired signal.
Example:If Par. 19.29 is set to “2202” the value of PA2WV is sent to parameter 22.02
ACCEL TIME 1.
Unit: Type: I Min: 0 Max: 30000 Def: 0 Int. scaling:
Example:If Par. 19.31 is set to “412” the analog input signal 1 of IOEC 1 is copied to signal
PA3RV.
Unit: Type: I Min: 0 Max: 30000 Def: 0 Int. scaling:
19.34 ParAssign3WritePar
Parameter selects the group and the index to where the value of PA3WV is sent. The format
is (x)xyy, where (x)x is the group and yy is the index of the desired signal.
Example:If Par. 19.34 is set to “2202” the value of PA3WV is sent to parameter 22.02
ACCEL TIME 1.
Unit: Type: I Min: 0 Max: 30000 Def: 0 Int. scaling:
Example:If Par. 19.36 is set to “412” the analog input signal 1 of IOEC 1 is copied to signal
PA4RV.
Unit: Type: I Min: 0 Max: 30000 Def: 0 Int. scaling:
19.39 ParAssign4WritePar
Parameter selects the group and the index to where the value of PA4WV is sent. The format
is (x)xyy, where (x)x is the group and yy is the index of the desired signal.
Example:If Par. 19.39 is set to “2202” the value of PA4WV is sent to parameter 22.02
ACCEL TIME 1.
Unit: Type: I Min: 0 Max: 30000 Def: 0 Int. scaling:
Example:If Par. 19.41 is set to “416” the analog input signal 1 of IOEC 1 is copied to signal
PA5RV.
Unit: Type: I Min: 0 Max: 30000 Def: 0 Int. scaling:
19.44 ParAssign5WritePar
Parameter selects the group and the index to where the value of PA5WV is sent. The format
is (x)xyy, where (x)x is the group and yy is the index of the desired signal.
Example:If Par. 19.44 is set to “2202” the value of PA5WV is sent to parameter 22.02
ACCEL TIME 1.
Unit: Type: I Min: 0 Max: 30000 Def: 0 Int. scaling:
Example:If Par. 19.46 is set to “416” the analog input signal 1 of IOEC 1 is copied to signal
PA6RV.
Unit: Type: I Min: 0 Max: 30000 Def: 0 Int. scaling:
19.49 ParAssign6WritePar
Parameter selects the group and the index to where the value of PA6WV is sent. The format
is (x)xyy, where (x)x is the group and yy is the index of the desired signal.
Example:If Par. 19.49 is set to “2202” the value of PA6WV is sent to parameter 22.02
ACCEL TIME 1.
Unit: Type: I Min: 0 Max: 30000 Def: 0 Int. scaling:
Example:If Par. 19.51 is set to “412” the analog input signal 1 of IOEC 1 is copied to signal
PA7RV.
Unit: Type: I Min: 0 Max: 30000 Def: 0 Int. scaling:
19.54 ParAssign7WritePar
Parameter selects the group and the index to where the value of PA7WV is sent. The format
is (x)xyy, where (x)x is the group and yy is the index of the desired signal.
Example:If Par. 19.54 is set to “2202” the value of PA7WV is sent to parameter 22.02
ACCEL TIME 1.
Unit: Type: I Min: 0 Max: 30000 Def: 0 Int. scaling:
Example:If Par. 19.56 is set to “416” the analog input signal 1 of IOEC 1 is copied to signal
PA8RV.
Unit: Type: I Min: 0 Max: 30000 Def: 0 Int. scaling:
19.59 ParAssign8WritePar
Parameter selects the group and the index to where the value of PA8WV is sent. The format
is (x)xyy, where (x)x is the group and yy is the index of the desired signal.
Example:If Par. 19.59 is set to “2202” the value of PA8WV is sent to parameter 22.02
ACCEL TIME 1.
Unit: Type: I Min: 0 Max: 30000 Def: 0 Int. scaling:
Group 20 LIMITS
20 LIMITS
This parameter group defines the maximum and minimum limits for speed, frequency, current and
torque algorithms.
Figure
For a speed supervision with a smaller margin use Group 32 Limit Supervision (slip already taken into
account in actual value and actual value stronger filtered).
This parameter defines together with parameters SPEEDMAX and SPEEDMIN (FREQ MAX and FREQ MIN in
the scalar control mode) the maximum allowed frequency of the drive. If this frequency is reached, the trip
OVER SPEED FAULT is activated.
20.16 FreqLimInit
After setting the motor nominal values the frequency and speed limits are calculated and preset.This
parameter indicate whether the initialization of these limits has been done.To automatically recalulate
the limits after changing the nomimal motor parameters, this parameter can be set to NO
NAME VALUE MEANING
NO 0
YES 1
Unit: % Type: B Min: 0 Max: 1 Def: 0 Int. scaling:1==1
20.17 ZeroSpeedDetect
Selection of zero speed detection function.
VALUE NAME MEANING
0 ENCODER Zero speed detection is activated if actual speed is below parameter
20.03 ZEROSPEED LIMIT.
-1 MODULATING Zero speed detection is activated by COAST STOP or EMERGENCY
OFF as soon as inverter stops modulating (independently of actual
speed).
Unit: Type: NoType Min: Max: Def: Int. scaling:
Group 21 START/STOP/MCB
21 START/STOP/MCB
Selection of Start / Stop and MCB functions. The parameters marked with (O) can only be altered
while the ACS1000 is stopped.
STOP FUNCTION
After a stop command is given, the drive is stopping according to the following steps:
3 COAST STOP
Comm. Module
RAMP STOP MODE TORQ STOP MODE RAMP FUNCTION COAST STOP MODE
n n n
(rpm) (rpm) (rpm)
D=1 SCALAR
Process Stop
Mode
21.03 Process Stop MCB Ctrl
DTC if "SCALAR" - mode is selected,
21.04
stop mode is fix ed to
Process Stop "RAMP STOP"
0 Trip 1 b
16.01 n =0 MCB Opening
Process Stop
NOT USED RAMP STOP
& "Fault"
1 1
1 Trip 1 a
DI8 - IOEC2 2 2 TORQ STOP MCB Stay Closed
-1 >
Process Stop
COMM.MOD ULE 3 3 COAST STOP & "Alarm"
(7.06 - Bit12)
Process Stop Ramp RAMP STOP MODE TORQ STOP MODE COAST STOP MODE
n n n
22.06 (rpm) (rpm) (rpm)
RAMP FUNCTION
t (s)
21.04 ProcessStopMCBCtrl
Selection of MCB reaction if the “Process Stop” is activated (see figure 16-1).
VALUE NAME MEANING
0 OPENING after drive has stopped, the MCB will be opened
1 STAY CLOSED after drive has stopped, the MCB will not be opened
Unit: Type: B Min: 0 Max: 1 Def: 0 Int. scaling:1 == 1
500
250
Calcu late d
Motor Speed (Act)
t s
22.06 PROCC ES STOP RAMP
Unit: rpm/s Type: R Min: 0 rpm/s Max: 18000 Def: 10 rpm/s Int. scaling:1 = 1 rpm/s
rpm/s
If ONE signal for opening and closing is needed than this parameter has to be set to ONE SIGNAL
(dig. Output IOEC2 - DO6 is “ON” = closing command or “OFF” = opening command; dig. Output
IOEC2-DO5 is always de-energized).
If TWO separate signals, one for opening and one for closing, are needed than this parameter has to
be set to TWO SIGNALS (dig. Output IOEC2 - D05 “OFF” = opening command, dig. Output IOEC2 -
D06 “ON” = closing command; in normal operation digital Output of IOEC2 - DO5 is “ON” and dig.
Output IOEC2 - DO6 is “OFF”).
NAME VALUE MEANING
ONE SIGNAL 0
TWO SIGNALS 1
Unit: Type: B Min: 0 Max: 1 Def: 1 Int. scaling:1 == 1
When using the feedback signal the earth isolator can only be operated when the MCB is not available
to make sure that with closed earth isolator also the input terminals are without voltage.
Note!
If this parameter is selected to LOW ACTIV, the earth isolatar can only be operated if dig. Input IOEC2 –
DI11 is ON (MCB is not available).
If this parameter is selected to HIGH ACTIV, the earth isolatar can only be operated if dig. Input IOEC2
– DI11 is OFF (MCB is not available).
NAME VALUE MEANING
NO 1
LOW ACTIV 2
HIGH ACTIV 3
Unit: Type: I Min: 1 Max: 3 Def: 1 Int. scaling:1 == 1
no light =
INT - RELAIS
IOEC1 & IOEC2 -
Board DO5 / DO6
OFF
LWL "MCB Off"
(light on = no trip)
PPCS-Lin k
no light =
Signal = " 0 "
D06
Par.: 5.01
DO1-6 Status IOEC1 IOEC1
LWL
Converter
MCB
D05
Control
& / MCB Open
D06
Par.: 5.02
DO1-6 Status IOEC2
IOEC2
Figure 21-4 LWL “MCB OFF” – Signal of IOEC1 2 - Overview
Par.: 21.12
Backspin Lockout Time
Start inhibited
0 t s
21.11 BackspinLockFunc
This parameter activates the backspin lockout function. If lockout is active, a start command will be
ignored (Start inhibition is active). ASW1 – Bit08 (Backspin Lockout Act) will be set during a pending
lockout and drive status shows “Lockout Act”
Note!
This parameter can not be changed during an active lockout.
VALUE NAME MEANING
0 OFF No action, backspin lockout function is not used.
1 ON Backspin lockout function is active.
Unit: Type: B Min: 0 Max: 1 Def: 0 Int. scaling:1 == 1
21.13 BackspinLockReset
With this parameter an active lockout can be reset.
Note!
This parameter can only be set from service.
VALUE NAME MEANING
0 OFF Backspin lockout, reset is not active
1 ON Backspin lockout, lockout (time) will be reset
Unit: Type: B Min: 0 Max: 1 Def: 0 Int. scaling:1 == 1
21.16 CoastStopMaxTrq
Maximum allowed torque to which the torque limiters is ramped during coast stop
Unit: % Type: R Min: -100% Max: 100% Def: 3% Int. scaling:1 == 1 %
21.17 CoastStopMinTrq
Minimum allowed torque to which the torque limiters is ramped during coast stop
Unit: % Type: R Min: -100% Max: 100% Def: -3% Int. scaling:1 == 1 %
22 RAMP FUNCTIONS
Speed reference ramp functions.
22.10 EStopRampTime
Deceleration time for speed ramp function if MCW-B2 (OFF_3_N) is set to "0" (emergency stop function
active).
Unit: s Type: R Min: 0 Max: 1800 Def: 20 Int. scaling:100 == 1
22.11 EStopSpeedDiff
Monitors the deceleration of drive speed after an EMERGENCY STOP command has been given. This monitoring starts few
seconds after the drive has received the emergency stop signal. If the drive is not able to decelerate within specified rate,
drive will be tripped and an EMERGENCY OFF will be initiated
23 SPEED REFERENCE
Speed reference functions.
LOCAL / REMOTE
ACCELER ATION
LI MITER COMPENSATION
SETPOINT
LIMITER W EIGHTING
SPEED REF
23.01
+
SPEED SH ARE x _
23.05
24.06 SET P W EIGHTING
20.01 MINIMUM SPEED
24.07 SET POINT WEIGHT
20.02 MAXIMUM SPEED
WINDOW CONTROL
When window control is used, normally parameter 26.01 TORQUE SELECTOR = ADD. Window control mode can be
selected by a signal from the fieldbus via AUX CTRL WORD 1 (7.02 – Bit7) or by parameter 23.07 WINDOW SEL ON.
The size of the window (in window control mode) is determined by parameters 23.09 WINDOW WIDTH POS or 23.10
WINDOW WIDTH NEG (rpm).
When running with window control, the speed controller output is zero if speed error is less than number in WINDOW
WITH parameters. If speed error is larger than the number in WINDOW WIDTH, the speed controller output, TORQ
REF2 (3.09) is added to the torque reference. In AUX STATUS WORD 1 (8.02-Bit1) it is shown when speed error is
greater than or less than the WINDOW WIDTH value. Pay attention to the speed controller output limits, 20.07 SPC
TORQMAX and 20.08 SPC TORQMIN and to how much it has adapted to correct the torque reference.
When the window control is enabled, the integrator of the speed controller can be released or blocked by parameter
23.08 WINDOW INTG ON. When 23.08 = OFF, the window control works only as a P-controller.
Figure 23-2 Window Control, Effect of Load Change on a Torque Controlled Drive - Diagram
Note: If the drive needs very fast response times a sample interval time shorter than 5ms are required. Use Data
Logger tool instead of Monitoring tool.
The parameter 23.11 SPEED STEP is used in step response tests. Steps of 1% or 2% of the nominal speed are set.
Bigger steps can also be used depending on the dynamic demands of the application. The value 20 corresponds to 20
rpm. Since a step given from DriveWindow is an absolute value, it must be proportional to the maximum speed of drive.
Increase the integral time constant parameter, 24.08 TIS, to a high value so that its effect is small. First, a step up is
given, e.g. 23.11 SPEED STEP = 20rpm. Then, when the speed is stabilised, a step down, e.g. 23.11 SPEED STEP = -
20rpm, is given.
The relative gain 24.03 KPS is increased until the response is sufficient.
The integral time constant 24.08 TIS is reduced until overshoot is observed in the response. The integral time constant
is then adjusted such that there is no overshoot or only a slight overshoot (depending on the drive application). The
function of the integral part is to remove as quickly as possible the difference between reference and the actual value
caused by the proportional control.
If the drive is stable and allows a high proportional gain, the integral time constant can be set short and an
overcompensated step response is obtained. If the drive goes to torque limit during a step, a further compensation of
the response should be attempted.
24 SPEED CONTROL
INERTIA COMPENSATION
Inertia compensation torque can be calculated in the inverter when the time for derivative function is given. The
acceleration compensator gives an additional torque reference (3.07) relative to parameter 24.15 ACC COMP DER
TIME. If inertia changes during the process, the calculation of the inertia can be done with the overriding system, and
then the compensation torque is transmitted directly as a torque reference to address 25.04 TORQ REF B.
When an internal speed actual value is used, parameter 24.17 SLIP GAIN is also valid. Value 100 corresponds to the
rated slip of the motor. Value 0 means no slip compensation and calculated speed equals motor frequency.
Make sure that overcompensation does not occur, for example, the value of speed controller output 3.09 TORQ REF2
should not become more negative (positive) during acceleration (deceleration) than when the speed reference was
constant.
25 TORQUE REFERENCE
LIMITER
TORQ REF SEL
TORQ REF A
APPL BLOCK 0 25.01
OU TPUT
03.18
1 25.02 TORQ REF A FTC
x +
TORQ REF SELECT LOAD SHARE LI MITER
25.07
25.03 TORQ REF1
3.08
RAMPING
t__sta_ref_vdcosc
t__sta_ref_pullout
t__sta_ref_slow
t__sta_ref_user
t__sta_ref_curr
t__sta_ref_nrot
t__sta_ref_spd
t__sta_ref_bc
Braking
Rotor User Pull-out V_dc
Current Chopper
speed torque torque oscillation
limitation duty cycle
limitation limitation limitation damping
limitation
Figure 25 2 Details of the Torque Limiting Chain
The TORQUE REF A are limited by the torque limit 20.09 TREF TORQMAX and 20.10 TREF TORQMIN (see Figure
25 1).
26 TORQREF HANDLING
The torque reference can be given from the speed reference chain (TORQ REF2) or from the
torque reference chain (TORQ REF1) depending on the control mode. This group defines how
to handle the reference after the torque selector block.
TORQUE STEP
26.03
LOAD COMPENSATION
26.02 TORQUE REFERENCE
LIMITING
TORQ REF5 TORQ USED REF
OSCILLATION DAMPING
3.12 3.13
OS C_COMP_ON
126.01
OS C_COMP_FREQ
126.02
OS C_COMP_PHASE LIMITAT IO NS
126.03
OS C_COMP_GAIN TORQ REF4
126.04
3.11
TORQUE REFERENCE
TORQUE S ELECTOR SELECTOR
26.01
0
TORQ REF1
3.08 2 1 TORQ REF3
3
(EX TERNA L TORQUE REFERENCE) 3.10
4
MIN
5 6
MAX
TORQ REF2
3.09 +
Note!
The torque selector can be modified only when the following conditions are true:
• Ref2 selected via 12.01 (local) resp. 12.02 (remote),
• torque control selected (99.14 = Torque Ctrl) and/or follower selected (70.08 = Follower).
With the other control modes that can be selected in 99.14 the torque selector is fixed to ‘SPEED’.
When running with pure torque control (26.01 = 3), the drive follows the external torque reference
(TORQUE REF A / B) and the actual speed is not controlled or limited. Then it is not possible to prevent
the drive section from overspeeding.
If a safety margin of the actual speed is needed, then 26.01 TORQUE SELECTOR is set to 4 (or 5).
Then the speed controller of the drive has to receive a speed reference value from the overriding
system which is slightly higher (lower if 26.01 = 5) than the actual speed. The actual speed then
remains below (above) the reference and the logic selects the smaller torque reference. A negative
(positive) speed difference causes changeover to speed control. A changeover from speed control to
torque control reference takes place when reference is lower (higher) than the controller output. This
function enables a smooth changeover from speed control to torque control and back.
NAME VALUE MEANING
ZERO 1
SPEED 2
TORQUE 3
MINIMUM 4
MAXIMUM 5
ADD 6
Unit: Type: I Min: 0 Max: 5 Def: 1 Int. scaling:1 == 1
28 DC LINK CONTROL
Parameters for charging, discharging and neutral point voltage supervision.
All parameter in this group are inverter type specific and set during the commissioning according
the drive type code.
They are only visible after entering the service passcode.
28.10 HV ChrgRelaySupv
Not applicable for ACS1000.
Unit: Type: B Min: 0 Max: -1 Def: 0 Int. scaling:1 == 1
28.15 PassiveDischDelay
Parameter defines the waiting time until the grounding switch can be operated, if the TC Stałe Machine
still stays in the INIT sequence (6.42 TC STATE- Stałe 0, 1 or 2) or a communication fault is active after
the software initilization time has elapsed.
With this delay, it can be guaranteed that the DC-Link voltage is really zero also without communication
link between the measurement device and the AMC board not working.
During this sequence an additional alarm message is shown: „ PassiveDischarge”
Note!
Parameter change is only allowed by ABB service. If parameter is set to zero (0), the monitoring
function is disabled.
Unit: s Type: R Min: 0 Max: 3600 Def: 900 Int. scaling:1==1s
28.16 NpVoltDevIncTime
NP voltage deviation increase time after modulation stop. The NP voltage threshold will be increased
after stopping modulation for the time set in this parameter.
Unit: Type: R Min: 0 Max: 3600 Def: 300 Int. scaling:1 == 1s
29 SCALAR CONTROL
NOT AVAILABLE
When parameter 99.09 CONTROL MODE is set to SCALAR the scalar control mode is activated.
This parameter group is only visible if SCALAR - control mode is selected.
NOTE! All scalar control parameters above Group 99 have to be checked during commissioning.
UDC2
Local
DC-VO LTAGE
LIMITER CURRENT
Freq Ref LIMITATION
29.01 LIMITER ACC/DEC/SHAPE UDC
SCALAR CONTROL
Inverter Current
Accel Ti me1 29.03 FREQUENCY MIN DECEL TIME 1/2
22.02
Accel Ti me2 22.06 PR STOP RAMP Max Motor Current
22.03 20.04
22.07 SHAPE TIME
Decel Ti me1 MIN
22.04 MaxInverterCurrent
22.05 Decel Ti me2
Flux X Act
Motor Torque
1.09 Flux Y Act
IR COMP
COMPENSATION
CALCULATION
Flux Y Act
30 MOTOR PROTECTION
The motor can be protected against overheating by:
• temperature measurement of the motor using PT100 or PTC sensors by using analogue inputs
(with a separate transducer)
• a thermal switch inside the motor connected to digital input DI14-IOEC1
EXTERNAL: The motor over temperature detection is based on the measured values of the
motor temperature by means of PT100.
Motor Thermal Protection
30.01 EXT MOTOR THERM PROT
AI2 - IOEC2
(4.17) MotTempPhase U1
SCALING (4.09)
13.12 Ext ernal Alarm Motor Temp Alarm
: 30.05 M OT T EM P AL M L
MotTempAlarm U1
AI3 - IOEC2
(4.18) MotTempPhase V1
SCALING (4.10)
13.18
: 30.05 M OT T EM P AL M L
MotTempAlar m V1
enable
AI3-IOEC2 < 2mA
AI3-IOEC2
MeasLostAlarm V1
30.03 M OT TEM P M EA S V MeasLost Trip U1
AI4 - IOEC2
(4.19) MotTempPhase W1
SCALING (4.11)
13.24
: 30.05 M OT T EM P AL M L
MotTempAlar m W1
13.28 :
M OT T EM P T RIP L MotTempTrip W1
30.06
enable
AI4-IOEC2 < 2mA
AI4-IOEC2
MeasLostAlarm W1
30.04 M OT TEM P M EA S W MeasLostTrip W1
30.02 MotWdgUTempMeas1
This parameter activates the first motor winding temperature measurement of phase U by using
analogue input AI2-IOEC2 connected to an external sensor (PT100 or PTC is connected to a transducer
which provides a 0(4)...20mA signal for the AI). The supervision for measurement loss is only active, if
Par. 13.14 AI2 MINIMUM IO2 is set to 4mA/2V .
Note:
If more than one motor winding measurement is active (Par.: 30.02, 30.03, 30.04) a Soft Stop will only
be generated when all off the selected AI signals are lost.
VALUE NAME MEANING
1 SOFT Motor temperature measurement is used. In case of measurement loss the
STOP drive will be stopped with SOFT STOP and a fault signal will be generated.
2 ALARM Motor temperature measurement is used. In case of measurement loss the
drive will not be stopped – only an alarm signal will be generated
3 NO No action, motor temperature measurement is not used
Unit: Type: I Min: 1 Max: 3 Def: 3 Int. scaling:1 == 1
30.03 MotWdgVTempMeas1
This parameter activates the first motor winding temperature measurement of phase V by using
analogue input AI3-IOEC2 connected to an external sensor (PT100 or PTC is connected to a transducer
which provides a 0(4)...20mA signal for the AI). The supervision for measurement loss is only active, if
Par. 13.20 AI3 MINIMUM IO2 is set to 4mA/2V .
Note:
If more than one motor winding measurement is active (Par.: 30.02, 30.03, 30.04) a Soft Stop will only
be generated when all off the selected AI signals are lost.
VALUE NAME MEANING
1 SOFT Motor temperature measurement is used. In case of measurement loss the
STOP drive will be stopped with SOFT STOP and a fault signal will be generated.
2 ALARM Motor temperature measurement is used. In case of measurement loss the
drive will not be stopped – only an alarm signal will be generated
3 NO No action, motor temperature measurement is not used
Unit: Type: I Min: 1 Max: 3 Def: 3 Int. scaling:1 == 1
Note:
If more than one motor winding measurement is active (Par.: 30.02, 30.03, 30.04) a Soft Stop will only
be generated when all off the selected AI signals are lost.
VALUE NAME MEANING
1 SOFT Motor temperature measurement is used. In case of measurement loss the
STOP drive will be stopped with SOFT STOP and a fault signal will be generated.
2 ALARM Motor temperature measurement is used. In case of measurement loss the
drive will not be stopped – only an alarm signal will be generated
3 NO No action, motor temperature measurement is not used
Unit: Type: I Min: 1 Max: 3 Def: 3 Int. scaling:1 == 1
i / in
OVERLOAD
20 480 t/s
1200
Par.: 30.10 Par.: 30.11
MotorProtTime1 MotorProtTime2 Par.: 30.12
MotorProtTime3
Figure 30 2 Motor Overload Protection - Diagram
Figure
30.13 StallFunction
This parameter defines the reaction of the stall protection once it gets active.
30.14 StallFreqLLim
Defines the motor stall frequency low level. If motor frequency is below this level, the first condition to
supervize the motor for stall conditions is fulfilled.
Unit: Hz Type: R Min: 0 Max: 100 Def: 1 Int. scaling:1 == 1Hz
30.15 StallCurrHLim
Defines the motor current high level. If motor RMS current is above this level, the second condition to
supervize the motor for stall conditions is fulfilled.
Unit: % Type: R Min: 0 Max: 500 Def: 150 Int. scaling:1 == 1%
Stall area
Operation area
30.15 StallCurHighLim
The protection function assumes that the drive is equipped with a motor of the rated power.
VALUE NAME MEANING
1 NO No action, motor underload protection is not active.
2 WARNING Motor underload protection is active; if motor is underloaded, an alarm
signal will be generated.
3 FAULT Motor underload protection is active; if motor is underloaded, a trip signal
will be generated and the drive will be stopped.
Further settings for the motor overload protection must be set in paramters 30.07 to 30.12.
NAME VALUE MEANING
PROT 0 Function disabled
DISABLE
PROT 1 Function enabled, only alarm appears if in motor overload protection
W/ALARM area
PROT W/TRIP 2 Function enabled, drive trips with FC2 fault reaction if in motor
overload protection area
Unit: Type: Enum Min: 0 Max: 2 Def: 2 Int. scaling:1 == 1
31.03 AI<MinFuncExtRef1
Operation in cases the reference value 1 (analogue input signal AI1-IOEC2) drops below the minimum
limit. The function is only activated if the parameter 13.08 AI1 MINIMUM IOEC2 is set to 4mA/2V.
VALUE NAME MEANING
1 NO No action
2 FAULT Drive trips in case of analogue signal loss
3 CNST Alarm will be set and drive runs continuously with constant speed15
SPD15 (Par.34.16)
4 LAST Alarm will be set and drive runs continuously with the last speed
SPEED reference
Unit: Type: I Min: 1 Max: 4 Def: 1 Int. scaling:1 == 1
31.04 AI<MinFuncExtRef2
Operation in cases the reference value 2 (analogue input signal AI1-IOEC1) drops below the minimum
limit. The function is only activated if the Parameter 13.03 AI1 MINIMUM IOEC1 is set to 4mA/2V.
VALUE NAME MEANING
1 NO No action
2 FAULT Drive trips in case of analogue signal loss
3 CNST Alarm will be set and drive runs continuously with constant speed15
SPD15 (Par.34.16)
4 LAST Alarm will be set and drive runs continuously with the last speed
SPEED reference
Unit: Type: I Min: 1 Max: 4 Def: 1 Int. scaling:1 == 1
31.06 PanelLossSuperv
Defines the operation of the drive if the control panel stops communicating, when it is selected as the
control location for the drive (e.g. local mode).
NOTE!
If you select CNST SPD 15 or LAST SPEED, make sure that it is safe to continue operation in case
communication with the Control Panel fails.
VALUE NAME MEANING
1 NO No panel link supervision
2 FAULT Fault indication is displayed, fault bit is set (FW5 – Bit 09) and drive stops
according to the setting of Parameter 21.02 STOP FUNCTION
3 CNST Warning indication is displayed, alarm bit is set (AW5 – Bit 03) and drive
SPD15 runs continuously with constant speed15 (Par.34.16).
4 LAST Warning indication is displayed, alarm bit is set (AW5 – Bit 03) and drive
SPEED runs continuously with the last actual speed
Unit: Type: I Min: 1 Max: 4 Def: 1 Int. scaling:1 == 1
31.07 AUTORESTART CW
As long as motor frequency is in the range of 0Hz to 5Hz (adaptable by parameter 133.05 FREQ HYST 70%)
and inverter RMS current is bigger than the linear approximation from 133.30 70% LIM I LIMIT (0Hz) to 100%
(5Hz), the overload protection is active and drive will trip after a delay time.
The delay time can be set in parameter 133.10 70%LIM DELAY TIME or 33.12 Overl@LowFreq, depending on
the selection in this parameter.
If 133.10 is selected as source for the time delay, the delay is depending on how much the inverter is
overloaded (e.g. if inverter is 120% overloaded, the delay time is 133.10 divided by 2). If 33.11 is set to 33.12,
the delay time is indepent of overload condition.
NAME VALUE MEANING
31.12 0 Overload protection delay time is set with parameter 31.12 and not dependent on
overload condition.
133.10 1 Overload protection delay time is set with parameter 133.10, but trip delay is dependent
on overload condition (e.g. trip delay at 110% overload = 133.10; trip delay at 120%
overload = 133.10 / 2; ...)
I_inv_rms [%]
100%
70%
(133.30)
5Hz n [Hz]
(133.05)
Figure
Group 32 SUPERVISION
32 SUPERVISION
These parameter values can be altered while the ACS1000 is running. Free programmable relay
output can be used to indicate a supervision limit. The limit bit from each supervision function is
set in Limit Word 2 (Par. 8.07).
32.01 LimSupervAction
This parameter defines the operation in case one of the supervision functions below is activated. If one
of the supervision functions is active the delay time will be started. The status of each limit supervision
function will be shown in Par. 8.07 LIMIT WORD2.
VALUE NAME MEANING
1 SOFT If one of the supervision functions below is active, a trip signal will be
STOP generated and the drive will be stopped
2 ALARM If one of the supervision functions below is active, only an alarm signal will
be generated
3 NO No alarm/fault will be set if one of the supervision functions below is active
Unit: Type: I Min: 1 Max: 3 Def: 3 Int. scaling:1 == 1
32.03 SpeedRefFunction
This parameter activate the speed reference supervision function.
VALUE NAME MEANING
1 NO Supervision not used
2 LOW LIMIT Supervision will be activated if value is below the set limit.
3 HIGH LIMIT Supervision will be activated if value is above the set limit.
Unit: Type: I Min: 1 Max: 3 Def: 1 Int. scaling:1 == 1
32.07 MotCurrentFunction
This parameter activates the motor current supervision function.
VALUE NAME MEANING
1 NO Supervision not used
2 LOW LIMIT Supervision will be activated if value is below the set limit.
3 HIGH LIMIT Supervision will be activated if value is above the set limit.
Unit: Type: I Min: 1 Max: 3 Def: 1 Int. scaling:1 == 1
32.09 MotTorqueFunction
This parameter activates the motor torque supervision function.
VALUE NAME MEANING
1 NO Supervision not used
2 LOW LIMIT Supervision will be activated if value is below the set limit.
3 HIGH LIMIT Supervision will be activated if value is above the set limit.
Unit: Type: I Min: 1 Max: 3 Def: 1 Int. scaling:1 == 1
Example:
When the actual value of INVERTER AIR TEMPERATURE should be supervised, parameter 32.12 is
set to 216 with 2 representing the group and 16 representing the index.
32.15 SupSig2Group+Indx
A numerical value of the AMC-table is assigned to “supervision signal 2” by setting parameter 32.15 to
the parameter group and index the value is to taken from. The format is (x)xyy, where (x)x the group
and yy is the index of the desired signal.
Example:
When the actual value of INVERTER AIR TEMPERATURE should be supervised, parameter 32.15 is
set to 216 with 2 representing the group and 16 representing the index.
33 CONSTANT SPEED
The following parameters (except those marked with “O”) can be altered while the ACS1000 is
running. The ACS1000 has 15 programmable constant speeds, ranging from 0 to 18000rpm.
Negative speed values cannot be given directly; this has to be done with the digital input
SIGNAL DIRECTION. If constant speed is activated, the absolute value of the speed is read
from parameter group 33. The sign of constant speed 15 is considered when used as a Fault
Speed (sees parameter 30.18 and 30.19 and figure 12-3).
In External, when External Control Location EXT1 is selected, constant speed override any other
references.
Constant speed selections are ignored if the torque reference or process PID reference is
followed (see Torque Control and PID Control Macros).
34 CRITICAL SPEED
In some mechanical systems, certain speed ranges can cause resonance problems. With this
parameter group it is possible to select up to five different speed ranges that the ACS 1000 will
avoid. It is not required that Parameter 34.04 CRITICAL SPEED 2 LOW is higher than
Parameter 34.03 CRITICAL SPEED 1 HIGH, as long as the LOW parameter of one set is lower
than the HIGH parameter of the same set. Sets may overlap, but the skip will be from the lower
LOW value to the higher HIGH value.
Figure 34-1 Critical Speed, Function of High and Low Limit - Diagram
35.01 BearingTmpProtDE
Motor bearing temperature protection for Driven End. Reaction in case of bearing over temperature and
measurement loss.
VALUE NAME MEANING
1 SOFT Bearing temperature protection is used. In case of measurement loss the
STOP drive will be stopped with SOFT STOP and a fault signal will be generated,
bearing temperature supervision (35.02 and 35.03) is active.
2 ALARM Bearing temperature protection is used. In case of measurement loss the
drive will not be stopped – only an alarm signal will be generated, bearing
temperature supervision (35.02 and 35.03) is active.
3 NO No action, bearing temperature protection is not used.
Unit: Type: I Min: 1 Max: 3 Def: 3 Int. scaling:1 == 1
35.04 BearingTmpProtNDE
Motor bearing temperature protection for Non Driven End. Reaction in case of bearing over temperature
and measurement loss.
NAME VALUE MEANING
SOFT STOP 1
ALARM 2
NO 3
Unit: Type: I Min: 1 Max: 3 Def: 3 Int. scaling:1 == 1
35.08 MotorCoolingProt
Selection of external motor cooling protection. This parameter activates the binary inputs ‘Motor Cooling
Alarm’ (IOEC3-DI6) and ‘Motor Cooling Trip’ (IOEC3-DI7). With parameter 82.04 DI6 INVERT IO3
it is possible to select if the digital input for the alarm signal is high or low active.
IOEC3-DI6 = “1“ (high signal) : only an alarm message will be generated IOEC3-DI7 = “0” (low signal) :
drive will be stopped by and a fault message will be generated
VALUE NAME MEANING
0 OFF External motor cooling protection function is disabled
1 ON External motor cooling protection function is active
Unit: Type: B Min: 0 Max: 1 Def: 0 Int. scaling:1 == 1
35.09 VibrationProtDI
External vibration protection function: This parameter activates the binary inputs ‘Vibration Supervision
Alarm’ (IOEC3-DI8) and ‘Vibration Supervision Trip’ IOEC3-DI9’. With parameter 82.05 DI8 INVERT
IO3 it is possible to select if the digital input for the alarm signal is high or low active. IOEC3-DI8 = “1“
(high signal) : only an alarm message will be generated IOEC3-DI9 = “0” (low signal) : drive will be
stopped by and a fault message will be generated.
VALUE NAME MEANING
0 OFF External vibration protection function is disabled
1 ON External vibration protection function is active
Unit: Type: B Min: 0 Max: 1 Def: 0 Int. scaling:1 == 1
35.10 VibrationProtAI1
Vibration signal 1 supervision. Reaction in case of too high vibrations and measurement loss.
NOTE!
If this function is enabled par. 81.26 AI1 Select IO3 is set = 3 ‘VibraSens1’. Enabling is only possible
when the supervision functions of the load bearing temperature 1 (35.14) and the transformer
temperature ext/3 (36.02 and 36.07) are disabled.
VALUE NAME MEANING
1 SOFT Vibration protection is used. In case of measurement loss the drive will be
STOP stopped with SOFT STOP and a fault signal will be generated, Vibration
supervision (35.12 and 35.13) is active.
2 ALARM Vibration protection is used. In case of measurement loss the drive will not be
stopped – only an alarm signal will be generated, Vibration supervision (35.12
and 35.13) is active.
3 NO No action, bearing temperature protection is not used.
Unit: Type: I Min: 1 Max: 3 Def: 3 Int. scaling:1 == 1
NOTE!
If this function is enabled par. 81.27 AI4 Select IO3 is set = 3 ‘VibraSens2’. Enabling is only possible
when the supervision functions of the load bearing temp. 2 (35.17), the outside air temp. (37.04), the
second cooling water pressure (190.44) and the output trafo temp. (36.12) are disabled.
VALUE NAME MEANING
1 SOFT Vibration protection is used. In case of measurement loss the drive will be
STOP stopped with SOFT STOP and a fault signal will be generated, Vibration
supervision (35.12 and 35.13) is active.
2 ALARM Vibration protection is used. In case of measurement loss the drive will not be
stopped – only an alarm signal will be generated, Vibration supervision (35.12
and 35.13) is active.
3 NO No action, bearing temperature protection is not used.
Unit: Type: I Min: 1 Max: 3 Def: 3 Int. scaling:1 == 1
35.14 LoadBrgTmpProt1
Motor bearing temperature protection 1. Reaction in case of bearing over temperature and
measurement loss.
NOTE!
If this function is enabled par. 81.26 AI1 Select IO3 is set = 2 ‘LoadBearTemp1’. Enabling is only
possible when the supervision functions of the vibration sensor 1 (35.10) and the transformer
temperature ext/3 (36.02 and 36.07) are disabled.
VALUE NAME MEANING
1 SOFT Bearing temperature protection is used. In case of measurement loss the
STOP drive will be stopped with SOFT STOP and a fault signal will be generated,
bearing temperature supervision (35.13 and 35.14) is active.
2 ALARM Bearing temperature protection is used. In case of measurement loss the
drive will not be stopped – only an alarm signal will be generated, bearing
temperature supervision (35.13 and 35.14) is active.
3 NO No action, bearing temperature protection is not used.
Unit: Type: I Min: 1 Max: 3 Def: 3 Int. scaling:1 == 1
AI3 - IOEC4
(85.08) MotTempPhase V2
SCALING (85.04)
86.14
: 30.05 M OT T EM P AL M L
MotTempAlar m V2
enable
AI3-IOEC4 < 2mA
AI3-IOEC4
MeasLostAlarm V2
35.21 M OT TEM P M EA S V
MeasLost Trip V2
AI4 - IOEC4
(85.09) MotTempPhase W2
SCALING (85.05)
86.20
: 30.05 M OT T EM P AL M L
MotTempAlar m W2
86.24 :
M OT T EM P T RIP L MotTempTrip W2
30.06
enable
AI4-IOEC4 < 2mA
AI4-IOEC4
MeasLostAlarm W2
35.22 M OT TEM P M EA S W MeasLostTrip W2
35.20 MotWdgUTempMeas2
This parameter activates the second motor winding temperature measurement of phase U by using
analogue input AI2-IOEC4 connected to an external sensor (PT100 or PTC is connected to a transducer
which provides a 0(4)...20mA signal for the AI). The supervision for measurement loss is only active, if
Par. 86.10 AI2 MINIMUM IO4 is set to 4mA/2V .
Note!
If more than one motor winding measurement is active (Par.: 35.20, 35.21, 35.22) a Soft Stop will only
be generated when all off the selected AI signals are lost. If this function is enabled par. 86.26 ‘AI2
Select IO4’ is set = 2 ‘MotWgTmpPhU2’
VALUE NAME MEANING
1 SOFT Motor temperature measurement is used. In case of measurement loss the
STOP drive will be stopped with SOFT STOP and a fault signal will be generated.
2 ALARM Motor temperature measurement is used. In case of measurement loss the
drive will not be stopped – only an alarm signal will be generated
3 NO No action, motor temperature measurement is not used
Unit: Type: I Min: 1 Max: 3 Def: 3 Int. scaling:1 == 1
Note!
If more than one motor winding measurement is active (Par.: 35.20, 35.21, 35.22) a Soft Stop will only
be generated when all off the selected AI signals are lost.
VALUE NAME MEANING
1 SOFT Motor temperature measurement is used. In case of measurement loss the
STOP drive will be stopped with SOFT STOP and a fault signal will be generated.
2 ALARM Motor temperature measurement is used. In case of measurement loss the
drive will not be stopped – only an alarm signal will be generated
3 NO No action, motor temperature measurement is not used
Unit: Type: I Min: 1 Max: 3 Def: 3 Int. scaling:1 == 1
35.22 MotWdgWTempMeas2
This parameter activates the second motor winding temperature measurement of phase W by using
analogue input AI4-IOEC4 connected to an external sensor (PT100 or PTC is connected to a transducer
which provides a 0(4)...20mA signal for the AI). The supervision for measurement loss is only active, if
Par. 86.22 AI4 MINIMUM IO4 is set to 4mA/2V.
Note!
If more than one motor winding measurement is active (Par.: 35.20, 35.21, 35.22) a Soft Stop will only
be generated when all off the selected AI signals are lost.
VALUE NAME MEANING
1 SOFT Motor temperature measurement is used. In case of measurement loss the
STOP drive will be stopped with SOFT STOP and a fault signal will be generated.
2 ALARM Motor temperature measurement is used. In case of measurement loss the
drive will not be stopped – only an alarm signal will be generated
3 NO No action, motor temperature measurement is not used
Unit: Type: I Min: 1 Max: 3 Def: 3 Int. scaling:1 == 1
36 TRANSFORMER PROT
Only available with IOEC3-Board (see Parameter 75.01) or ACS 1000i
36.01 TrafoTmpProtectDI
Selection of binary trafo temperature protection (oil or winding). This parameter activates the binary
inputs ‘Trafo Temperature Alarm’ (IOEC3-DI2) and ‘Trafo Temperature Trip’ IOEC3-DI3’. With Par.
82.02 DI2 INVERT IO3 it is possible to select, if the digital input for alarm signal is high or low active.
IOEC3-DI2 = “1“ (high signal) : only an alarm message will be generated
IOEC3-DI3 = “0” (low signal) : drive will be stopped and a fault message will be generated
VALUE NAME MEANING
0 OFF External transformer protection function is disabled
1 ON External transformer protection function is active
Unit: Type: B Min: 0 Max: 1 Def: 0 Int. scaling:1 == 1
36.02 TrafoTmpProtectAI
Selection of analogue trafo temperature protection (oil or winding). Operation in case of trafo
temperature to high and measurement loss.
NOTE!
This parameter will be fixed set to “SOFT STOP” to prevent overheating of the transformer, if
“Integrated Transformer Fan” option is used (Par.: 41.07 INTEGRATED TRAFO FAN INST) or with ACS
1000i.
With ACS 1000: If this function is enabled, par. 81.26 AI1 Select IO3 is set = 1 ‘TrafoTmpExt/3’.
Enabling is only possible when the supervision functions of the vibration sensor 1 (35.10) and the load
bearing temperature 1 (35.14) are disabled.
VALUE NAME MEANING
1 SOFT Trafo temperature protection is used. In case of measurement loss the drive
STOP will be stopped with SOFT STOP and a fault signal will be generated. Trafo
temperature supervision is active.
2 ALARM Trafo temperature protection is used. In case of measurement loss the drive
will not be stopped - only an alarm signal will be generated.
Trafo temperature supervision is active.
3 NO No action, analogue trafo protection is not used.
Unit: Type: I Min: 1 Max: 3 Def: 3 Int. scaling:1 == 1
NOTE!
This function is only available if the “Integrated Transformer Fan” option is not used ((Par.: 41.07
INTEGRATED TRAFO FAN INST is set to “NO”) and this function is not available with ACS 1000i.
VALUE NAME MEANING
0 OFF Transformer buchholz protection function is disabled
1 ON Transformer buchholz protection function is active
Unit: Type: B Min: 0 Max: 1 Def: 0 Int. scaling:1 == 1
36.06 TrafoOilLevProtec
Selection of trafo oil level protection. This parameter activates the binary input ‘Trafo Oil Level Alarm’
(IOEC3-DI1). With parameter 82.01 DI1 INVERT IO3 it’s possible to select, if the digital input for alarm
signal is high or low active. I IOEC3-DI3 = “1“ (high signal) : only an alarm message will be generated.
NOTE!
This function is not available with ACS 1000i.
VALUE NAME MEANING
0 OFF Transformer oil level protection function is disabled
1 ON Transformer oil level protection function is active
Unit: Type: B Min: Max: Def: 0 Int. scaling:1 == 1
36.07 TrafoTmpSelect
Only ACS 1000i:
Selection of the transformer temperature sensors that are used for the supervision function (36.02).
VALUE NAME MEANING
1 1 only temperature sensor 1 used,
2 12 temperature sensor 1 and 2 used,
3 123 temperature sensor 1, 2 and 3 used;
Unit: Type: I Min: 1 Max: 3 Def: 2 Int. scaling:1 == 1
36.12 OutpTrafoTmpProt
Selection of analogue trafo temperature protection (oil or winding). Operation in case of trafo
temperature to high and measurement loss.
NOTE!
If this function is enabled, par. 81.27 AI4 Select IO3 is set = 5 ‘OutpTrafoTmp’. Enabling is only possible
when the supervision functions of the vibration sensor 2 (35.11), the load bearing temp. 2 (35.17), the
outside air temp. (37.04) and the second cooling water pressure (190.44) are disabled.
VALUE NAME MEANING
1 SOFT Output trafo temperature protection is used. In case of measurement loss the
STOP drive will be stopped with SOFT STOP and a fault signal will be generated.
Trafo temperature supervision is active.
2 ALARM Output trafo temperature protection is used. In case of measurement loss the
drive will not be stopped - only an alarm signal will be generated. Trafo
temperature supervision is active.
3 NO No action, analogue output trafo protection is not used.
Unit: Type: I Min: 1 Max: 3 Def: 3 Int. scaling:1 == 1
37.01 ExtWtrCoolingProt
Selection of external water cooling operation. This parameter activates the binary output 'External Water
Cooling Unit Start' (IOEC4-DO5) as well as the binary inputs ‘External Water Cooling Alarm’ (IOEC4-
DI1) and ‘External Water Cooling Trip’ IOEC4-DI2’. With parameter 87.01 DI1 INVERT IO4 it is possible
to select if the digital input for alarm signal is high or low active.
IOEC4-DI1 - an alarm message will be generated
IOEC4-DI2 - drive will be stopped by a low signal value and a fault message will be generated
VALUE NAME MEANING
0 OFF External water cooling function is disabled
1 ON External water cooling function is active
Unit: Type: B Min: 0 Max: 1 Def: 0 Int. scaling:1 == 1
This parameter is used to select the type of the OUTPUT SWITCH, which is installed
between the INU output and the motor. The output side switch is used for drive operation
prevention purposes, ensuring safe motor side maintenance operations.
NOTE!
Parameter has to be set according to installed output switch type
VALUE NAME MEANING
1 NOT USED Inverter output side switch is not used or not existing.
2 ISOLATOR Inverter output side switch is an isolator.
3 GND SW Inverter output side switch is a grounding switch.
Unit: Type: Enum Min: 1 Max: 3 Def: 1 Int. scaling:1 == 1
NOTE!
Parameter has to be set according to installed input switch type.
VALUE NAME MEANING
1 NOT USED Inverter input side switch is not used or not existing.
2 ISOLATOR Inverter input side switch is an isolator.
3 GND SW Inverter input side switch is a grounding switch.
Unit: Type: Enum Min: 1 Max: 3 Def: 1 Int. scaling:1 == 1
NOTE!
If 1 or 2 is selected, par 81.27 AI4 Select IO3 is set = 1 ‘OutsideAirTemp’. Enabling is only possible
when the supervision functions of the vibration sensor 2 (35.11), the load bearing temp. 2 (35.17), the
second cooling water pressure (190.44) and the output trafo temp. (36.12) are disabled.
VALUE NAME MEANING
1 SOFT Outside air temperature protection is used. In case of measurement loss the
STOP drive will be stopped with SOFT STOP and a fault signal will be generated,
outside air temperature supervision (37.05 and 37.06) is active.
2 ALARM Outside air temperature protection is used. In case of measurement loss the
drive will not be stopped - only an alarm signal will be generated, outside air
temperature supervision (37.05 and 37.06) is active.
3 NO No action, outside air temperature protection is not used.
Unit: Type: I Min: 1 Max: 3 Def: 3 Int. scaling:1 == 1
38 OPTIONAL FUNC
Optional function used by the customer.
The parameters marked with (O) can only be altered while the ACS1000 is stopped.
38.01 MotorHeater
This parameter activates the motor heater function. Normally the digital output DO5-IOEC1 (NO
MOTOR HEATER ON) is energized, even if parameter 38.01 is set to “NO”. If the function is activated,
the motor heater order on command is controlled from digital output DO5-IOEC1. The digital output
IOEC1-DO3 will be de-energized, if parameter 38.01 is set to “YES”, the drive is not in “RUNNING” –
state, no HEATER ALARM signal is active (DI12 – IOEC1) and digital output MOTOR COOLER
ORDER ON (IOEC3 – DO1) is not activated. The motor heater trip signal is connected to IOEC1-DI12
(in series with cabinet heater). If the ORDER ON command is set and the trip signal has a low value, an
alarm message will be generated.
VALUE NAME MEANING
0 NO Motor heater function is not active
1 YES Motor heater is installed, function is active
Unit: Type: B Min: 0 Max: 1 Def: 0 Int. scaling:1 == 1
38.02 MotorCooler
This parameter activates the motor cooler function. If the function is activated, the motor cooler order on
command is controlled from output IOEC3-DO1; the motor cooler trip signal is connected to IOEC3-
DI12.
VALUE NAME MEANING
1 SOFT Motor cooler is used. If motor cooler trip signal is active the drive will be
STOP stopped with SOFT STOP and a fault signal will be generated.
2 ALARM Motor cooler is used. If motor cooler trip signal is active the drive will not be
stopped - only an alarm signal will be generated.
3 NO No action, motor cooler is not used.
Unit: Type: I Min: 1 Max: 3 Def: 3 Int. scaling:1 == 1
38.04 CabinetHeater
This parameter activates the cabinet heater function. The cabinet heater trip signal is connected to
IOEC1-DI12 (in series with motor heater). If the cabinet heater function is selected and the trip signal
has a low value, an alarm message will be generated.
VALUE NAME MEANING
0 NO Cabinet heater function is not active
1 YES Cabinet heater is installed, function is active
Unit: Type: B Min: 0 Max: 1 Def: 0 Int. scaling:1 == 1
38.07 SynBypassFunction
This parameter activates the Synchronized Bypass function for starter. If the parameter is set to:
NAME VALUE MEANING
SBYP 2-4 MTR 1
SBYP FOR 1 MTR 2
NO 3
Unit: Type: I Min: 1 Max: 3 Def: 3 Int. scaling:1 == 1
FUNCTION:
Parameter Setting: LOW ACTIVE / HIGH ACTIVE. If Safe Torque Off monitoring
function is used this parameter is normally set to LOW ACTIVE.
38.15 SafeTrqOffStopM
This parameter defines the drive reaction when the ACS 1000 is in "Ready REF" – State and
the Safe Torque Off function became active.
NAME VALUE MEANING
NO REACTION 1
STOP RAMP 2
STOP TORQ 3
STOP COAST 4
Unit: Type: Enum Min: 1 Max: 4 Def: 1 Int. scaling:
38.16 EmergeStopCtrl
This parameter activates the Emergency Stop function (connected to digital input selected in
parameter group 72). Emergency Stop is a category 1 stop which finally ends by hardwired
timer relays in an emergency off (category 0 stop).
FUNCTION:
Parameter Setting: LOW ACTIVE / HIGH ACTIVE. If Emergency Stop monitoring
function is used this parameter is normally set to LOW ACTIVE.
NAME VALUE MEANING
NOT USED 1
LOW ACTIVE 2
HIGH ACTIVE 3
Unit: Type: Enum Min: 1 Max: 3 Def: 1 Int. scaling:
FUNCTION:
Parameter Setting: LOW ACTIVE / HIGH ACTIVE. If Arc Fault monitoring function is
used this parameter is normally set to LOW ACTIVE.
NAME VALUE MEANING
NOT USED 1
LOW ACTIVE 2
HIGH ACTIVE 3
Unit: Type: Enum Min: 1 Max: 3 Def: 1 Int. scaling:
38.18 GndCurrent1Prot
Selection of analogue ground current protection reaction.
NAME VALUE MEANING
SOFT 1 Ground current supervision 1 is used and if trip level is reached reaction is
STOP SOFT STOP
ALARM 2 Ground current supervision 1 is used and if alarm level is reached reaction
is an ALARM
NO 3 No action, analogue ground current protection is not used.
Unit: Type: Enum Min: 1 Max: 3 Def: 3 Int. scaling:
38.21 GndCurrent2Prot
Selection of analogue ground current protection 2 reaction.
NAME VALUE MEANING
SOFT 1 Ground current supervision 2 is used and if trip level is reached reaction is
STOP SOFT STOP
ALARM 2 Ground current supervision 2 is used and if alarm level is reached reaction
is an ALARM
NO 3 No action, analogue ground current protection 2 is not used.
Unit: Type: Enum Min: 1 Max: 3 Def: 3 Int. scaling:
39 RIDE THROUGH
The ride through function prevents an under voltage fault when short voltage dips in the DC
intermediate circuit occur.
The ride-through function of the ACS 1000 is expected to keep the drive in operation and
prevent a trip when the main (input) power fails. During ride-through operation, the voltage of
the DC bus is kept at a specified level. For this purpose, energy from the rotating mass of the
motor and load is taken through the inverter to compensate for losses and maintain the DC bus
voltage. In the process, the motor speed drops. The ride-through mode can be maintained as
long as the rotating mass has sufficient energy that can be extracted to keep the DC bus
voltage up. The ACS 1000 ride-through function provides adjustable limits for the minimum
speed permitted during ride-through, and the maximum time allowed for ride-through to be
active. If the input power is restored, within the permitted time and speed, the mode
automatically changes from ride-through to normal operation. After the transition to normal
operation, the motor is accelerated to the speed setting that was active before the input power
failure. If the input power is not restored before the set time and speed limits are reached, then
the drive is tripped.
It is also possible to disable ride-through operation completely. If it is disabled, then the drive
trips immediately if the input power is lost.
[%] DC Bus Voltage The ride-through voltage levels are
explained on the basis of Figure 39-1.
D
100
C A Undervoltage Trip Level 65%
B B Undervoltage Alarm Level 71%
A
C Ride-Through Level 80%
D Overvoltage Trip Level 129%
time
t1 t2 t3
39.07 BattFaultReact
This parameter activates the back-up supply battery supervision (DI4 - IOEC1).
VALUE NAME MEANING
1 Fault A fault message will be generated.
2 Alarm Only an alarm message will be generated.
Unit: Type: I Min: 1 Max: 2 Def: 2 Int. scaling:1==1
Group 40 PID-CONTROL
40 PID-CONTROL
Intended for use with different closed loop control systems such as pressure control, level control
and flow control.
The PID Control Macro allows the ACS 1000 to take a reference signal (setpoint) and an actual
signal (feedback), and automatically adjust the speed of the drive to match the actual signal to
the reference. The minimum and maximum values of the PID Controller output are the same as
Parameter 20.01 MINIMUM SPEED and 20.02 MAXIMUM SPEED.
NOTE!
These parameters can only be seen when the PID Control Macro is selected.
Process Error Value
Gain
Figure 40-1 PID Controller Gain Settings (MAXIMUM SPEED is 1500 rpm)
Figure
40.05 ErrorValueInvers
PID Controller error value inversion. This parameter allows inverting the Error Value (and thus the
operation of the PID Controller). Normally, a decrease in Actual Signal (feedback) causes an increase in
drive speed. If a decrease in actual is desired to cause a decrease in speed, set Error Value Invert to
YES.
VALUE NAME MEANING
0 NO PID Controller error value inversion is not active
1 YES PID Controller error value inversion is active
Unit: Type: B Min: 0 Max: 1 Def: 0 Int. scaling:1 == 1
40.06 ActualValueSel
Actual signal source for the PID Process Controller is selected by this parameter. Analogue input AI1-
IOEC4 is fix connected to actual signal 1 (ACT1) and analogue input AI2- IOEC4 is fix connected to
actual signal 2 (ACT2) for the PID controller.
In the list of parameter values choices AI denotes ACT1 and A2 denotes ACT2. ACT1 and ACT2 are
combined by subtraction, addition, multiplication or other function as listed below:
• MIN (A1,A2) sets the parameter value either ACT1 or ACT2, depending which one has the smallest
value
• MAX (A1,A2) sets the parameter value either ACT1 or ACT2, depending which one has the biggest
value
• sqrt (A1–A2) sets the parameter value to square root of (ACT1 – ACT2)
• sqA1 + sqA2 sets the parameter value to square root of ACT1 plus square root of ACT2
Note!
Use the sqrt (A1-A2) or sqA1+sqA2 function if the PID-Controller controls flow with a pressure
transducer measuring the pressure difference over a flow meter.
NAME VALUE MEANING
ACT1 1
ACT1 - ACT2 2
ACT1 + ACT2 3
ACT1 * ACT2 4
ACT1 / ACT2 5
MIN (A1,A2) 6
MAX (A1,A2) 7
sqrt (A1 - A2) 8
sqA1 + sqA2 9
Unit: Type: I Min: 1 Max: 9 Def: 1 Int. scaling:1 == 1
Figure
Figure
40.11 Act1UnitScale
This parameter matches the actual value displayed in the Control Panel (Parameter 03.19) to the Unit
defined by Parameter 40.12.
Unit: Type: R Min: -1000 Max: 1000 Def: 1 Int. scaling:1 == 1
40.12 Act1Unit
Selection of the Unit of the actual 1 value displayed in the Control Panel (Parameter 03.19).
1 = rpm actual value 1 will be displayed in rpm
2 =bar actual value 1 will be displayed in bar
3 = % actual value 1 will be displayed in %
4 =C actual value 1 will be displayed in °C
5 =mg/l actual value 1 will be displayed in milligram / litre
6 =kPa actual value 1 will be displayed in kilo Pascal
Unit: Type: R Min: 1 Max: 6 Def: 3 Int. scaling:1 == 1
40.14 Act2Unit
Selection of the Unit of the Actual 2 value displayed in the Control Panel (Parameter 03.20).
VALUE NAME MEANING
1 rmp actual value 1 will be displayed in rpm
2 bar actual value 1 will be displayed in bar
3 % actual value 1 will be displayed in %
4 C actual value 1 will be displayed in °C
5 mg/l actual value 1 will be displayed in milligram / litter
6 kPa actual value 1 will be displayed in kilo Pascal
Unit: Type: R Min: 1 Max: 6 Def: 3 Int. scaling:1 == 1
40.15 AI<MinFuncExtAct1
Operations in case of actual value 1 (analogue input signal AI1-IOEC4) drops below the minimum limit.
The function is only activated if the parameter 86.04 AI1 MINIMUM IO4 is set to 4mA/2V.
VALUE NAME MEANING
1 NO No action
2 FAULT Drive trips in case of analogue signal loss
3 CNST Alarm will be set and drive runs continuously with constant speed15
SPD15 (Par.34.16)
4 LAST Alarm will be set and drive runs continuously with the last speed
SPEED reference
Unit: Type: I Min: 1 Max: 4 Def: 1 Int. scaling:1 == 1
40.16 AI<MinFuncExtAct2
Operations in case of actual value 2 (analogue input signal AI2-IOEC4) drops below the minimum limit.
The function is only activated if the Parameter 86.10 AI2 MINIMUM IO4 is set to 4mA/2V.
VALUE NAME MEANING
1 NO No action
2 FAULT Drive trips in case of analogue signal loss
3 CNST Alarm will be set and drive runs continuously with constant speed15
SPD15 (Par.34.16)
4 LAST Alarm will be set and drive runs continuously with the last speed
SPEED reference
Unit: Type: I Min: 1 Max: 4 Def: 1 Int. scaling:1 == 1
8V (75%) 8V (80%)
60%
4V (25%) 4V (40%)
2V (0%) 20%
0V 0% 0V 0% 0% 0%
Actual Scaled Actual Actual Scaled Actual Actual Scaled Actual
41 COOLING SYSTEM
Cooling system parameter of ACS1000.
With “Redundant Cooling System” (two fans or pumps are selected) the continuous operation of
the drive is guaranteed if a fan (air) or pump (water) failure occures. Switch-over from the faulty
to the stand-by device will take place automatically.
With the “Automatic change over” - function the cycle time and running time for both fans/pumps
can be set. If for example a cycle time of 10h and a Fan1/Pump1 run time of 6h is selected,
Fan1/Pump1 will run for 6 hours. Then they will be stopped and Fan2/Pump2 will run for 4h.
After 4h Fan1/Pump1 are swiched on again.
With water cooling the supervision of the conductivity is disabled for the time defined by par.
41.15 WtrPmpChangeMask after a change-over.
1st cycle start 1st cycle finished
Fan1/Pump 1 2nd cycle start
ON
OFF
Fan2/Pump 2
ON
OFF
6h 4h t
10h 10h
Figure 41-1 Redundant Cooling System, Automatic Fan / Pump Change - Diagram
With “Redundant Cooling System” (two fans or pumps are selected) the continuous operation of the
drive is guaranteed if a fan (air) or pump (water) failure occures. Switch-over from the faulty to the
stand-by device will take place automatically.
With the “Automatic change over” - function the cycle time and running time for both fans/pumps can be
set. If for example a cycle time of 10h and a Fan1/Pump1 run time of 6h is selected, Fan1/Pump1 will
run for 6 hours. Then they will be stopped and Fan2/Pump2 will run for 4h. After 4h Fan1/Pump1 are
swiched on again.
With water cooling the supervision of the conductivity is disabled for the time defined by par. 41.15
WtrPmpChangeMask after a change-over.
This parameter defines the cycle time of the redundant cooling system.
Unit: h Type: R Min: 2 Max: 24 Def: 10 Int. scaling:1 == 1
41.02 Fan1/Pump1RunTime
Parameter defines the switch over time between Fan1 / Pump1 and Fan2 / Pump2.
Unit: h Type: R Min: 1 Max: 41.01 – Def: 6 Int. scaling:100 == 1h
1h
On
41.03 AirCoolFanSel
This parameter activates the selected cooling fan in an air cooled drive. If parameter selection is set to
TWO (FAN1&2) the redundant cooling fan function is active. In case one of the fan is disturbed, the
other fan is switched on automatically.
VALUE NAME MEANING
1 ONE (FAN 1) Cooling fan 1 is installed
2 ONE (FAN 2) Cooling fan 2 is installed (only with IOEC 3)
3 TWO (FAN12) Redundant cooling fans 1 2 are installed (only with IOEC 3)
Unit: Type: I Min: 1 Max: 3 Def: 1 Int. scaling:1 == 1
41.04 FanAlarmReset
Resetting of an active fan ALARM.
Note!
Parameter will be set back automatically to OFF.
VALUE NAME MEANING
0 OFF Fan alarm reset not active
1 RESET Reset command will be set
Unit: Type: B Min: 0 Max: 1 Def: 0 Int. scaling:1 == 1
41.05 InvAirFilterSupvi
Parameter activates monitoring of air filter in an air cooled drive. If function is activated and digital input
signal is high, an ALARM will be generated. IOEC1 - DI09
VALUE NAME MEANING
0 OFF Air filter supervision function is disabled
1 ON Air filter supervision function is active
Unit: Type: B Min: 0 Max: 1 Def: 0 Int. scaling:1 == 1
3 3 -K11 -K12
Pump 1 Pump 2
-Q13 -Q14
Aux.Fan 1 Aux.Fan 2
3 IOEC1
3 IOEC4
-DI3 -DI9
-K13 -K14 -Q13 -Q14
Aux.Fan 1 Aux.Fan 2 Aux.Fan 1 Aux.Fan 2
3 3
-K13 -K14
M M Aux.Fan 1 Aux.Fan 2
IntTrafFan1 Alarm
9.55
> AW2 / Bit 05
Automatic Change
Over Function / IntTrafoFan1Trip Fan1
Supervision 8.01
AirCoolingFanSel (DI4 - IOEC3)
41.03 MSW / Bit 07
(TWO(FAN1&2) IntTrafoFanReset
41.08
IntegTrafoFanInst Auto Chg Active
41.07 >
(TWO(FAN1&2)
WtrCoolingP umpSel IntTrafFan2 Alarm
41.09 9.55
(TWO(PUMP1&2)
ActRunTimeFan1/Pump1
> AW2 / Bit 06
Fan1/Pump1
5.15
Fan/PumpCycleTime ActRunTimeFan2/Pump2 / IntTrafoFan2Trip Fan2
41.01 5.16 Supervision 8.01
(DI5 - IOEC3)
Fan1/Pump1RunTime Fan 2/Pump2 Fan1/Pump1OrderOn MSW / Bit 07
41.02 IntTrafoFanReset
Fan2/Pump2OrderOn 41.08
IntTrafFan1Order On
DO5 - IOEC3
IntTrafFan1 &
& > Alarm
5.14
IntTrafFan2Order On
DO6 - IOEC3
IntTrafFan2 &
&
> Alarm
5.14
41.07 IntegTrafoFanInst
This parameter activates the integrated transformer function. Depending on the installed fans the
parameter has to be set to the correct value; not available with ACS 1000i.
VALUE NAME MEANING
1 NO Integrated transformer fan is not installed, function is not active
2 ONE (FAN 1) Integrated transformer cooling fan 1 is installed, function is active
3 ONE (FAN 2) Integrated transformer cooling fan 2 is installed, function is active
4 TWO Integrated transformer cooling fans 12 are installed, redundant function is
(FAN12) active
Unit: Type: I Min: 1 Max: 4 Def: 1 Int. scaling:1 == 1
41.08 TrafoFanAlmReset
Resetting of an active integrated transformer fan ALARM; not available with ACS 1000i.
Note!
Parameter will be set back automatically to OFF.
VALUE NAME MEANING
0 OFF Fan alarm reset not active
1 RESET Reset command will be set
Unit: Type: B Min: 0 Max: 1 Def: 0 Int. scaling:1 == 1
Hysteresis (1°C)
Air Temperature Low Trip 0
(fixed = -0.5°C)
Time
Trip "Inverter Air Temperature"; ACS1000 switch on prevented s
Pressure transducers –B5261 and in case of ACS1000i –B5262 monitor the air pressure (connected to DI3 on IOEC1).
The following figure shows only the difference pressure for ACS 1000 (ACS 1000i not shown).
AIR PRESSURE
SUPERVISION
Trip Delay
Digital Input
DI3 - IOEC1 Note!
Default: 5s AIR PRESSURE FAIL Supervision signal during
41.21 ON DELAY fan start, change over
fans (Redundant Cooling
System) and normal run!
B1
ControlBox
WR
P
p < - 250 Pa
Pa
DI3 - IOEC
Cooling Air Pressure
Pa 0
DI3 - IOEC
Air differential -
Air differential- pressure sensor
pressure sensor
41.09 WtrCoolPumpSel
This parameter activates the selected water cooling pump in a water cooled drive. If parameter is
selected to TWO (PUMP 1 and 2) the redundant water cooling pump function is active. In case one of
the pump is disturbed, the other pump is switched on automatically.
VALUE NAME MEANING
1 ONE (PUMP 1) Water cooling pump 1 is installed
2 ONE (PUMP 2) Water cooling pump 2 is installed
3 TWO (PUMP 1 and 2) Redundant water cooling pump is installed (Pump 1 2)
Unit: Type: I Min: 1 Max: 3 Def: 1 Int. scaling:1 == 1
41.10 PumpAlarmReset
Resetting of an active pump ALARM.
Note!
Parameter will be set back automatically to OFF.
VALUE NAME MEANING
0 OFF Pump alarm reset not active
1 RESET Reset command will be set
Unit: Type: B Min: 0 Max: 1 Def: 0 Int. scaling:1 == 1
Function!
If water conductivity is above the value of par. 41.17 WtrAutoCoolStCond the “Auto Cooling On Delay”- time (par. 41.11
AutoCoolOnDelay) is started. The waiting time before the auto cooling sequence will be started can be seen on the
panel at Par. 5.17 AutoCoolWaitTime (counting down to zero!). After cooling on delay time has been exceeded cooling
pump 1 will start automatically. On the Panel the drive status “AutoCoolOn” will be shown (Par.: 8.10 DriveStatusWord).
Water conductivity starts to decrease and if conductivity is below alarm limit the auto cooling sequence will stop (drive
status “AutoCoolOn” disappears) and the pump off delay time (Par.: 41.20 Pump Off Delay) starts. During this time the
status “CoolOffDely” will be shown on panel status (Par.: 8.10 DriveStatus). After exceeding cooling off delay time
pump 1 will stop. Water conductivity starts to increase again. If water conductivity is above alarm limit the auto cooling
sequence starts again but this time with starting of pump 2.
Note!
The auto cooling system is always alternating between cooling pump 1 and pump 2, if parameter 41.09 Water
CoolingPumpSelection is set to “TWO(Pump12) otherwise only selected pump (Pump1 or Pump2) will start. The “Auto
cooling start sequence” will not be started if parameter 41.11 AutoCoolOnDelay is set to ZERO.
Water
Cooling On Delay "Start"
Conductivity
us Cooling Pump 1 "ON"
Cooling Pump Off delay "ON"
Cooling Pump 1 "OFF"
Pump 1
ON
OFF
t
OFF
t
Function!
If water conductivity is above alarm limit after initialisation, pump 2 will be started immediately to bring down the water
conductivity. On the Panel the drive status “StartSeqOn” will be shown (Par.: 8.10 DriveStatusWord). After water
conductivity is below alarm limit the 1st delay time of 15s is started and if time is over without reaching the alarm limit
again the cooling system will be switched over to pump1. After pump1 has started it could be that the water conductivity
is bad again (from pump1 system, pipe …) and the alarm level will be exceeded. After water conductivity is below
alarm limit the 2nd delay time of 15s is started and if time is over without reaching the alarm limit again, the drive status
changes to “RdyForMCB On” and the “Start Sequence” is swiched off.
Note!
The “Start Sequence” will not be started if water conductivity is below alarm limit after switching on the auxiliary power.
Therefore Pump1 will start immediately.
Aux. Power On
Water
Start of 15s delay time
Cond uctivity Init Done
us
Pump change over
Trip Level
Alarm Level
Pump 1
ON
OFF
Pump 2
ON
OFF
Note!
If start sequence is active the drive is not ready for closing the MCB.
VALUE NAME MEANING
0 OFF Redundant water cooling system start sequence is not active
1 ON Redundant water cooling system start sequence is active
Unit: Type: B Min: 0 Max: 1 Def: 0 Int. scaling:1 == 1
0.05bar HHyst
Default: 6bar
13.35 AI3 HighValue IO1
Default:
Default: 0bar 5.5 bar INV WTR PRESS URE
13.36 AI3 LowValue IO1 41.35 ALARM LEVE L HIGH
Default: 4mA
13.37 AI3 Minimum IO1
WATER PRESSURE 1 WATER PRESSURE 1
Default: 0.1s SUPERVISI ON SUPERVISION
13.38 AI3 Filter IO1 Trip High Trip High Delay Fix
Default: 0mA Water Outp. Press. Water Outp. Press.
13.39 AI3 Offset IO1
High Trip High Trip Delayed
AI I
WATER PRESSURE I > = H2
SUPERVISI ON Limit H2
Measuremen t Lost
0.05bar HHyst
Water Press. 1
MeasLost Default:
AI I 6 bar INV WTR PRESS URE WTR PRESSURE
2s
I < = L1 (AI3 - IOEC1 < 3mA) 41.36 TRIP LEVEL HIGH FAIL ON FIX DELAY
3mA L1
P T Q 0.05bar H1 Hyst
I I I
V5 Default:
TO CO NV ERTER 4.5 bar INV WTR PRESS URE
41.37 ALARM LEVE L HIGH
PART OF
WATER CO OLING SYSTEM
FLOW DIAGRAM WATER PRESS DIFF
(see Figure 41-7) SUPERVISI ON
Alarm L ow
0.05bar L1 Hyst
Default:
2 bar INV WTR PRESS URE
41.38 ALARM LEVE L LOW
WATER PRESSURE 1
SUPERVISION
Trip Delay Fix
Water Diff. Press.
Low Trip Delayed
following supervisions
only active with closed
cooling system:
Note!
41.34 80.19 WATER PRESSURE 2 Supervision signal during
SUPERVISI ON
open cool. system Alarm High 0.5 s
WTR PRESSURE normal run!
FAIL ON FIX DELAY
0 Water Inp. Press.
High Alarm
AI I
closed cool. system I > = H1
Water Pressure 2 Limit H1
0.05bar HHyst
0.05bar LHyst
Default:
0.1 bar INV WTR PRESS URE WTR PRESSURE
41.43 1s
TRIP LEVEL LOW FAIL ON FIX DELAY
41.29 InvAirTempSelect
This parameter selects the input signal for the inverter air temperature supervision.Only air cooled
type!
NAME VALUE MEANING
InvAirTmp1 1
InvAirTmp2 2
InvAirTmp12 3
Unit: Type: I Min: 1 Max: 3 Def: 1 Int. scaling:1==1
41.33 WtrCoolSysLeakage
Liquid leakage sensor selection.
NAME VALUE MEANING
NO 0
YES 1
Unit: - Type: B Min: 0 Max: 1 Def: 0 Int. scaling:1==1
41.34 WtrCoolSysClosed
Selection of the closed water cooling system. This system needs the second water pressure
measurement (input pressure) on IOEC3, AI4.
NOTE!
If Yes is selected, par 81.27 AI4 Select IO3 is set = 4 ‘CoolWtrPres2’.Enabling is only possible for
water cooled types when the supervision functions of the vibration sensor 2 (35.11), the load bearing
temp. 2 (35.17), the outside air temp. (37.04) and the output trafo temp. (36.12) are disabled.
VALUE NAME MEANING
0 NO Open water cooling system
1 YES Closed water cooling system
Unit: - Type: B Min: 0 Max: 1 Def: 0 Int. scaling:1==1
Note!This parameter is only active with closed cooling system (parameter 41.34 = YES).
Unit: bar Type: R Min: 0.1 Max: 5.9 Def: 4.5 Int. scaling:100==1bar
Note!
If water pressure sinks below this limit with redundant cooling pumps, the pump will be changed. In
addition an alarm will be generated, and after resetting the alarm the faulty pump will be selected
again.If parameter 41.34 is set to NO the input pressure is zero (diff. pressure = output pressure).
Unit: bar Type: R Min: 0.1 Max: 5.9 Def: 2 Int. scaling:100==1bar
Note!If parameter 41.34 is set to NO the input pressure is zero (diff. pressure = output pressure).
Unit: bar Type: R Min: 0.1 Max: 5.9 Def: 1.5 Int. scaling:100==1bar
Note!This parameter is only active with closed cooling system (parameter 41.34 = YES).
Unit: bar Type: R Min: 0.1 Max: 5.9 Def: 2.0 Int. scaling:100==1bar
Note!This parameter is only active with closed cooling system (parameter 41.34 = YES).
Unit: bar Type: R Min: 0.1 Max: 5.9 Def: 2.5 Int. scaling:100==1bar
Note!This parameter is only active with closed cooling system (parameter 41.34 = YES).
Unit: bar Type: R Min: 0.1 Max: 5.9 Def: 0.2 Int. scaling:100==1bar
Note!This parameter is only active with closed cooling system (parameter 41.34 = YES).
Unit: bar Type: R Min: 0.1 Max: 5.9 Def: 0.1 Int. scaling:100==1bar
0.05bar HHyst
Default: 6bar
13.35 AI3 HighValue IO1
Default:
Default: 0bar 5.5 bar INV WTR PRESS URE
13.36 AI3 LowValue IO1 41.35 ALARM L EVE L HIG H
Default: 4mA
13.37 AI3 Minimum IO1
WATER PRESSURE 1 WATE R PRESSURE 1
Default: 0.1s SUPERVISION SUPE RVISI ON
13.38 AI3 Filter IO1 Trip High Trip High Delay Fix
Default: 0mA Water Outp. Press. Water Outp. Press.
13.39 AI3 Offset IO1
High Trip High Trip Delayed
AI I
WATE R PRESSURE I > = H2
SUPERVISION Limit H2
Measurement Lost HHyst
0.05bar
Water Press. 1
MeasLost Default:
AI I 6 b ar INV WTR PRESS URE WTR PRESSURE
I < = L1 (AI3 - IOEC1 < 3mA) 41.36 2s
T RIP LEVEL HIGH FAIL O N F IX DELAY
3mA L1
Ana log ue Input
WATER PRESSURE DIFF
AI3 - IOEC1 SUPERVISION
Ala rm High
P T Q 0.05bar H1 Hyst
I I I
V5 Default:
TO CONV ERTER 4.5 bar INV WTR PRESS URE
41.37 ALARM L EVE L HIG H
PART OF
WATE R COOLING SY STEM
FLOW DIAGRAM WATER PRESSURE DIFF
(see Figure 41-7) SUPERVISION
Alarm Low
0.05bar L1 Hyst
Default:
2 b ar INV WTR PRESS URE
41.38 ALARM L EVE L LOW
WATE R PRESSURE 1
SUPE RVISI ON
Trip Delay Fix
Water Diff. Press.
Low Trip Delayed
following supervisions
only active with closed
cooling system:
Note!
41.34 80.19 WATER PRESSURE 2 Supervision signal during
SUPERVISION
open cool. system Ala rm High 0.5 s
WTR PRESSURE normal run!
FAIL O N F IX DELAY
0 Water Inp. Press.
High Alarm
AI I
closed cool. system I > = H1
Water Pressure 2 Limit H1
0.05bar HHyst
0.05bar LHyst
Default:
0.1 bar INV WTR PRESS URE WTR PRESSURE
41.43 1s
T RIP LEVEL LOW FAIL O N F IX DELAY
bar
Time
s
Warning -> Difference pressure too low Warning disappears -> Difference pressure too high
Trip -> Difference pressure too low (0.5s / 190.05 delayed) Warning disappears -> Output pressure too high
Trip reset possible -> Difference pressure too low Trip reset possible -> Output pressure too high
Warning disappears -> Difference pressure too low Trip -> Output pressure too high (2s delayed)
Warning -> Output pressure too high
Figure 41-14 Water Cooling System, Ouput / Difference Pressure Supervision - Diagram
Time
s
Warning -> Input pressure too low Warning disappears -> Input pressure too high
Trip -> Input pressure too low (1s delayed ) Trip reset possible -> Input pressure too high
Trip reset possible -> Input pressure too low Trip -> Input pressure too high (5s delayed )
Warning disappears -> Input pressure too low Warning -> Input pressure too high
WATER TE MPERATURE
AI I Auto. Cooling Pump On
I > = H1
SUPERVISI ON Limit H1
Measurement Lost
1 °C H1 Hyst
P T Q 1°C H3 Hyst
I I I
V5
TO CO NVERTER Default: 41°C
41.24 INV WTR TEMP
PART OF TRIP LEVEL
WATER COOLING SYSTEM
FLOW DIAGRAM WATER TEMPERATURE
(see Figure 41-7) SUPERVISION
Low Trip
WATER TEMPERATURE
SUPERVISION
Low Trip
WATER TEMPERATURE
SUPERVISION
High Trip
Hysteresis (1°C)
Temperature Pump On Level
(Par.: 41.25 = 15°C)
Hysteresis (1°C)
Temperature Pump Off Low Lev.
(Par.: 41.30 = 2°C)
Time
Trip, Pump ON -> Water temperature too low s
Pump OFF
Pump ON
Trip reset possible -> Water temperature too low,
Pump OFF (depends on autocooling setting)
Warning -> Water temperature too high
Trip -> Water temperature too high
Pump OFF
Pump ON
Trip reset possible -> Water temperature too high
WATER CONDUCTIVITY
SUPERVISI ON Water Conductivity Alarm
Measurement Lost AI I
I > = H1
Limit H1
Water Cond MeasLost
0,1us H1 Hyst
AI I (AI4-IOEC1 < 3mA)
I < = L1
3mA L1
Default: 0,5us INV WTR COND
Ana logue Input 41.26 ALARM LEVE L
AI4 - IOEC1
WtrAutoCoolStCond
(Par.: 41.17 = 0.4uS)
Time
Start Autocooling when MCB open and enabled with par. 41.16 s
Drive Alarm
MCB Off
MCB Control
Reset
MCB Open
Drive Trip Feedback
1b
Closed
Autoc ooling
On Delay
Single
Pu mp2
Pu mp Selection
Pump1
Pump1 Pump2
Yes Tripped Yes Tripped
NO NO
Pump1 Pump2
Start Star t
Pump
Running
Trip
Water Pressu re
OK
Delay Time Delay Time
Pump Start Pu mp Run
Trip Trip
OK
Reset
Drive
Ready to Start
Water Coolin g
System
Single
Redundant
Cooling Off
Seq Start
On
On
Pu mp Auto
Ch an ge Off
OK
Alarm Trip
Pump1 Pump2
On Command On Command
Yes Yes
1st Alar m 1st Alar m
No No
Tripped 1st
Alarm
nd
2 Trip
1st Alar m
Tripped
2nd Trip
41.45 InvWtrLevLowProt
Inverter water low level detection selection, which is connected to DI10 on IOEC4.
NAME VALUE MEANING
NOT USED 1 Level sensor is not installed.
ALARM HA 2 Level sensor is installed and the alarm apears with a high active signal.
ALARM LA 3 Level sensor is installed and the alarm apears with a hlow active signal.
Unit: Type: Enum Min: 1 Max: 3 Def: 1 Int. scaling:1 == 1
42 LOAD PROTECTION
Motor over- underload protection parameter of ACS1000.
This function prevents running the motor within unpermitted operating ranges for a longer
period.
42.01 LoadProtFunction
This parameter activates the motor load protection function. If the actual motor frequency is above the
start frequency (Par.: 42.07 LoadProtStartFrequency) the calculation of ideal motor current and
monitoring function will be started.
VALUE NAME MEANING
0 OFF No action, motor load protection is not used.
1 ON Motor load protection is active.
Unit: Type: B Min: 0 Max: 1 Def: 0 Int. scaling:1 == 1
The actual motor current used for the load protection can be filtered.
This is needed for small motors with very low motor current to allow small hysteresis values.
Unit: ms Type: R Min: 0 Max: 5000 Def: 500 Int. scaling:
During operation the ACS 2000 software continuously calculates the maximum difference between the three motor
phases.
If the actual motor unbalance current is inside the operating range (below motor unbalance alarm and trip current) no
alarm/fault is active. If the actual motor unbalance current is outside the operating range an alarm/fault will be
generated.
This function makes it possible to avoid, running the motor within permitted operating ranges for a longer period.
43 ESP PROTECTION
ESP application protection parameter of ACS1000.
43.01 MotPhaseUnbalFunc
This parameter activates the motor phase unbalance protection function.
Note!
This parameter can only be overwritten from service.
VALUE NAME MEANING
0 OFF No action, motor phase unbalance protection is not used.
1 ON Motor phase unbalance protection is active.
Unit: Type: B Min: 0 Max: 1 Def: 0 Int. scaling:1 == 1
This parameter group allows the customer to define an own supervision function. It is possible
to define three different signals (CSS1.1 … CSS1.3) and their logical interconnection (OR or
AND - gate). Additionally is it possible to invert (high or low active) those signals.
If NOT SEL is selected, the function is disabled.
If ONLY STATUS is selected, only the status bit in parameter 8.04 AUX STATUS WORD 3 will
be set, no alarm or fault will be initiated.
If ALARM is selected, only the alarm message “CustSupSig1” will be displayed on the panel. No
trip reaction is active.
If SOFTSTOP, TRIP 1a or TRIP 1b is chosen, drive stops according selected trip reaction and
the fault message “CustSupSig1” will be displayed on the panel.
CustSig1 Reaction
48.01
CustSig1 TypeSel
48.02
CustSig1.1 Invert
48.05
Signal Selection
CSS1.1 NOT SEL
CustSig1.1 Grp&Idx
48.03 Group & Index
CustSig1.1 BitNum ONLY STATUS
48.04 Bit Number -1
OR ALARM
Output 9.17
CSS1.1 Act
> CSS1 (AW7 - B07
CustSig1.2 Invert Act SO FTSTOP
48.08 7.03
(ACW2 - B06
Signal Selection
TRIP 1a
CSS1.2 7.03
CustSig1.2 Grp&Idx (ACW2 - B01
48.06 Group & Index
TRIP 1b
A ND 7.03
CustSig1.2 BitNum
48.07 Bit Number -1
(ACW2 - B02
Output
&
OR
CSS1.2 Act
CustSig1.3 Invert
48.11 CustSupSig1 Active
Signal Selection > 8.04
Output OR
CustSupSig1 Fault
CSS1.3 Act
> 9.09
(FW9 - B07
48.01 CustSig1Reaction
This parameter activates the customer supervision signal 1.
VALUE NAME MEANING
1 NOT SEL Function is not active
2 ONLY Only status indication is active
STATUS
3 ALARM If supervision signal is active, an alarm will be generated
4 SOFT STOP If supervision signal is active, a fault will be generated and the drive trips
according to “Softstop” trip reaction
5 TRIP 1A If supervision signal is active, a fault will be generated and the drive trips
according to “Trip 1a” trip reaction
6 TRIP 1B If supervision signal is active, a fault will be generated and the drive trips
according to “Trip 1b” trip reaction
Unit: Type: I Min: 1 Max: 6 Def: 1 Int. scaling:1 == 1
If AND is selected, customer supervision signal 1 will only be set if all three signals (CSS1.1 …
CSS1.3) are active.
If OR is selected, customer supervision signal 1 will be set if one of three signals (CSS1.1 … CSS1.3)
is active.
Note!
Only if CSS1.1 … 1.3 INVERT is set to DIRECT.
VALUE NAME MEANING
0 AND gate is active
1 OR gate is active
Unit: Type: B Min: 0 Max: 1 Def: 0 Int. scaling:1 == 1
48.03 CustSig1.1Grp+Idx
A binary signal (i.e. from a status word) is assigned to Customer Supervision Signal 1.1 (CSS 1.1) by
setting parameter 48.03 to the parameter group and index from which the signal is to be taken from.
Additionally the bit number, which identifies the signal within the status word, has to be selected with
parameter 48.04.
The format is (x)xyy, where (x)x is the group and yy is the index of the desired signal.
Example:
If Par. 48.03 is set to “809” and 48.04 is set to “0”, customer supervision signal 1.1 is active when 8.09
DI1-14 STAUS WORD IOEC2 / BIT 0 is “1” (digital input 1 of IOEC2 is active).
48.04 CustSig1.1BitNum
This parameter specifies the bit number (0...15) of the selected parameter group and index in 48.03.
Unit: Type: I Min: 0 Max: 15 Def: 13 Int. scaling:1 == 1
48.05 CustSig1.1Invert
Inversion selection for selected Customer Supervision Signal 1.1 (CSS 1.1).
VALUE NAME MEANING
0 DIRECT selected signal sent directly to AND / OR - gate
1 INVERTED selected signal sent inverted to AND / OR - gate
Unit: Type: B Min: 0 Max: 1 Def: 0 Int. scaling:1 == 1
48.06 CustSig1.2Grp+Idx
Selection of Group and Index of Customer Supervision Signal 1.2 (CSS 1.2).
Description see parameter 48.03
By default CS1.2 is set to “0”.
Unit: Type: I Min: 0 Max: 30000 Def: 804 Int. scaling:1 == 1
48.07 CustSig1.2BitNum
This parameter specifies the bit number (0...15) of the selected parameter group and index in 48.06
Unit: Type: I Min: 0 Max: 15 Def: 13 Int. scaling:1 == 1
48.08 CustSig1.2Invert
Inversion selection for selected Customer Supervision Signal 1.2 (CSS 1.2).
VALUE NAME MEANING
0 DIRECT selected signal sent directly to AND / OR - gate
1 INVERTED selected signal sent inverted to AND / OR – gate
Unit: Type: B Min: 0 Max: 1 Def: 0 Int. scaling:1 == 1
48.10 CustSig1.3BitNum
This parameter specifies the bit number (0...15) of the selected parameter group and index in 48.09
Unit: Type: I Min: 0 Max: 15 Def: 13 Int. scaling:1 == 1
48.11 CustSig1.3Invert
Inversion selection for selected Customer Supervision Signal 1.3 (CSS 1.3).
VALUE NAME MEANING
0 DIRECT selected signal sent directly to AND / OR - gate
1 INVERTED selected signal sent inverted to AND / OR – gate
Unit: Type: B Min: 0 Max: 1 Def: 0 Int. scaling:1 == 1
CustSig2 TypeSel
48.13
CustSig2.1 Invert
48.16
Signal S election
CSS2.1 NOT SEL
CustSig2.1 Grp&Idx
48.14 Group & Index
CustSig2.1 BitN um ONLY STATUS
48.15 Bit Number -1
OR ALARM
Output 9.17
CSS2.1 Act
> CSS2 (AW7 - B08
CustSig2.2 Invert Act SOFTSTOP
48.19 7.03
(ACW2 - B06
Signal S election
TRIP 1a
CSS2.2 7.03
CustSig2.2 Grp&Idx (ACW2 - B01
48.17 Group & Index
TRIP 1b
AN D 7.03
CustSig2.2 BitN um
48.18 Bit Number -1
(ACW2 - B02
Output
&
CSS2.2 Act OR
CustSig2.3 Invert
48.22
CustSupSig2 Active
Signal S election
CSS2.3
> 8.04
(ASW3 - B03
CustSig2.3 Grp&Idx
48.20 Group & Index
CustSig2.3 BitN um
48.21 Bit Number -1
Output OR
CustSupSig2 Fault
CSS2.3 Act
> 9.09
(FW9 - B08
48.13 CustSig2TypeSel
With this parameter the logical interconnection (AND or OR) of customer supervision signal 2 is
selected.
If AND is selected, the customer supervision signal 2 will only be set if all three signals (CSS2.1 …
CS2.3) are active.
If OR is selected, the customer supervision signal 2 will be set if one of three signals (CSS2.1 … CS2.3)
is active.
Note!
Only if CSS1.1 … 1.3 INVERT is set to DIRECT.
VALUE NAME MEANING
0 AND gate is active
1 OR gate is active
Unit: Type: B Min: 0 Max: 1 Def: 0 Int. scaling:1 == 1
48.14 CustSig2.1Grp+Idx
A binary signal (i.e. from a status word) is assigned to Customer Supervision Signal 2.1 (CSS 2.1) by
setting parameter 48.14 to the parameter group and index from which the signal is to be taken from.
Additionally the bit number, which identifies the signal within the status word, has to be selected with
parameter 48.15.
The format is (x)xyy, where (x)x is the group and yy is the index of the desired signal.
Example:
If Par. 48.14 is set to “809” and 48.15 is set to “0”, customer supervision signal 2.1 is active when 8.09
DI1-14 STAUS WORD IOEC2 / BIT 0 is “1” (digital input 1 of IOEC2 is active).
By default CS2.1 is set to “0”.
Unit: Type: I Min: 0 Max: 30000 Def: 804 Int. scaling:1 == 1
48.15 CustSig2.1BitNum
This parameter specifies the bit number (0...15) of the selected parameter group and index in 48.14
Unit: Type: I Min: 0 Max: 15 Def: 13 Int. scaling:1 == 1
48.16 CustSig2.1Invert
Inversion selection for selected Customer Supervision Signal 2.1 (CSS 2.1).
VALUE NAME MEANING
0 DIRECT selected signal sent directly to AND / OR - gate
1 INVERTED selected signal sent inverted to AND / OR - gate
Unit: Type: B Min: 0 Max: 1 Def: 0 Int. scaling:1 == 1
48.17 CustSig2.2Grp+Idx
Selection of Group and Index of Customer Supervision Signal 2.2 (CSS 2.2).
Description see parameter 48.14
By default CS2.2 is set to “0”.
Unit: Type: I Min: 0 Max: 30000 Def: 804 Int. scaling:1 == 1
48.19 CustSig2.2Invert
Inversion selection for selected Customer Supervision Signal 2.2 (CSS 2.2).
VALUE NAME MEANING
0 DIRECT selected signal sent directly to AND / OR - gate
1 INVERTED selected signal sent inverted to AND / OR - gate
Unit: Type: B Min: 0 Max: 1 Def: 0 Int. scaling:1 == 1
48.20 CustSig2.3Grp+Idx
Selection of Group and Index of Customer Supervision Signal 2.3 (CSS 2.3).
Description see parameter 48.14 By default CS2.3 is set to “0”.
Unit: Type: I Min: 0 Max: 30000 Def: 804 Int. scaling:1 == 1
48.21 CustSig2.3BitNum
This parameter specifies the bit number (0...15) of the selected parameter group and index in 48.10
Unit: Type: I Min: 0 Max: 15 Def: 13 Int. scaling:1 == 1
48.22 CustSig2.3Invert
Inversion selection for selected Customer Supervision Signal 2.3 (CSS 2.3).
VALUE NAME MEANING
0 DIRECT selected signal sent directly to AND / OR - gate
1 INVERTED selected signal sent inverted to AND / OR - gate
Unit: Type: B Min: 0 Max: 1 Def: 0 Int. scaling:1 == 1
EXAMPLE 1:
A special customer ALARM is generated if ACS1000 is running and digital input DI11 - IOEC4 is not set (OFF)
ACS1000 Running
AN D
(8.01 - B2)
ALARM
DI11 - IOEC4
(85.11 - B10)
& 9.17
(AW7 - B08)
CustSup1SigAct
1 Consta nt "1"
(8.04 - B14) 8.04
(ASW3 - B02)
Figure 48-3 Customer Supervision - Example 1 (Alarm)
(8.01 - B8 AT SETPOINT)
CustSup2SigAct
REMOTE - Mode
(8.01 - B9 REMOTE)
& 8.04
(ASW3 - B03)
Inv Air Temp > 40°C
(8.07 - B7 SUP SIG1)
Digital Output Selection
EXAMPLE 3
It is also possible to combine the customer supervision signal 1 2 :
Drive trips with trip reaction TRIP 1a if ACS1000 is running in LOCAL – Mode or digital Input DI6 – IOEC2 is set to ON
ACS1000 Running
AN D
(8.01 - B2)
CustSup1SigAct
REMOTE - Mode
(8.01 - B9 REMOTE) & 8.04 OR
(ASW3 - B02) CustSup2SigAct
DI6 - IOEC2
1
Constant 1
(8.09 - B5)
> 8.04
(8.04 - B14)
(ASW3 - B03
Constant 0
0
(8.04 - B13)
Trip 1a
8.04
(ACW2 - B01)
Figure 48 5 Customer Supervision - Example 3 (Trip)
50 SPEED MEASUREMENT
If measurement from ENCODER is faulty during magnetizing, running or stopping the speed
feedback selection will be switched to INTERNAL and an alarm / fault message will be displayed.
SPE ED
MEASURE MT
Mot or Model
Motor Speed
1.02
ENCODER
Speed Measured
1.04
FILTER
50.03 SPEED FB SEL
Motor Speed Filt
50.01 SP EED SCALING 1.03
50.02 SPEED MEAS MO DE
50.04 ENCODER PULS NUMBER
50.06 SD ACT FILT TIME
50.05 ENCODER ALM/FLT
Figure 50-1 Speed Measurement - Overview
Figure
Unit: rpm Type: R Min: 0rpm Max: 18000rpm Def: 1500rpm Int. scaling:15000 ==
1500 rpm
50.03 SpeedFeedbackSel
Source of the speed feedback to the speed controller.
VALUE NAME MEANING
1 INTERNAL internal actual speed
2 ENCODER pulse encoder module is used (see also Par. 75.03 ENCODER MODULE)
Unit: Type: I Min: 1 Max: 2 Def: 1 Int. scaling:1 == 1
51 MASTER ADAPTER
This parameter group defines the communication parameters when FBA (Field Bus Adapter) is
used. Parameter names depend on the selected FBA type.
This group name identifies which communication hardware module is connected to the ACS 1000
drive. Some option modules support multiple protocols, which can be selected with a parameter.
The setup parameters can be modified either by using the drive panel or by PC software, e.g.
DriveWindow.
Note!
The changes to the parameters in group 51 do not come into effect immediately but only when the
power of the fieldbus adapters was switched off and then switched on again.
Group 52 EC FAN
52 EC FAN
ACS1000 EC (electronically commutated) fan parameter group.
To enable the EC fan functionality first set parameter 75.06 to EC FAN, otherwise the whole
parameter group is read protected.
Refer to the graphic below for a better understanding of the inverter fan speed calculation.
Refer to the graphic below for a better understanding of the transformer fan speed calculation.
52.06(52.01,52.02) = (52.34/[max(52.15,52.25)]^2)*max(52.01,52.02)^2
Unit: Pa Type: R Int. scaling: 1 == 1
Note!
In order to ensure the measurements which are taken during the calibration process, the final result
must be in a certain range (define by parameters 210.26 AirPress MinExpect & 210.27 AirPress
MaxExpect). If the range is exceeded the “old” value from 52.34 is not changed and a calibration fault is
active.
NAME VALUE MEANING
DISABLED 0 Calibration not active.
CALIBRATION 1 Calibration is active.
Unit: Type: B Min: 0 Max: 1 Def: 0 Int. scaling:1 == 1
52.11 FanRedundancy
Selection of EC fan redundancy configuration.
NAME VALUE MEANING
NO 0 No EC fan redundancy configuration.
YES 1 EC fan redundancy configuration.
Unit: Type: B Min: 0 Max: 1 Def: 0 Int. scaling:1 == 1
52.13 FanRdyRunStopDel
After the set time in this parameter, the fans are stopped if the drive is in RdyRun state (MCB closed,
but not modulating)
Unit: s Type: R Min: 30 Max: 300 Def: 60 Int. scaling:1 == 1
52.15 InvFanNomSpd
Inverter fan nominal speed. Fan speed at nominal inverter operation.
Unit: rpm Type: R Min: 0 Max: 2500 Def: 1700 Int. scaling:1 == 1
52.16 InvRedFanNomSpd
Inverter fan nominal speed in redundant configuration. Fan speed of both inverter fans at nominal
inverter operation.
Unit: rpm Type: R Min: 0 Max: 2500 Def: 1350 Int. scaling:1 == 1
52.17 InvFanMinSpd
Minimum fan speed of inverter fan, for both, single and redundant configuration.
Unit: rpm Type: R Min: 0 Max: 52.18 Def: 900 Int. scaling:1 == 1
52.19 InvFanRefFiltTime
Inverter fan reference filter time. The reference given to the fan is filtered using this time.
Unit: s Type: R Min: 0 Max: 30 Def: 5 Int. scaling:1 == 1
52.20 InvFanRefWaveForm
Inverter fan reference waveform.
The speed reference to the fan can be quadratic or linear depending on inverter rms current (=160.81).
NAME VALUE MEANING
LINEAR 0 The fan reference is linear dependent on the inverter rms current
(160.81).
QUADRATIC 1 The fan reference is quadratic dependent on the inverter rms current
(160.81).
Unit: Type: B Min: 0 Max: 1 Def: 1 Int. scaling:1 == 1
52.21 MaxCurAtMinSpd
Maximum allowed inverter RMS current, where the fan is still allowed to run with minimum fan speed
(Parameter 52.17) for single configuration. The input must be given in percentage of the maximum
allowed current of the inverter.
Unit: % Type: R Min: 0 Max: 99 Def: 75 Int. scaling:1 == 1
52.22 MaxCurAtRedMinSpd
Maximum allowed inverter RMS current, where the fan is still allowed to run with minimum fan speed
(Parameter 52.17) for redundant configuration. The input must be given in percentage of the maximum
allowed current of the inverter.
Unit: % Type: R Min: 0 Max: 99 Def: 85 Int. scaling:1 == 1
52.25 TraFanNomSpd
Transformer fan nominal speed. Fan speed at nominal transformer power.
Note!
There is no measurement of the transformer power. Therefore it is calculated as follows:
TransfPower = 1.05 x 161.16 FILTERED POWER
Unit: rpm Type: R Min: 0 Max: 2500 Def: 1680 Int. scaling:1 == 1
52.26 TraRedFanNomSpd
Transformer fan nominal speed in redundant configuration. Fan speed of both transformer fans at
nominal transformer power.
Note!
There is no measurement of the transformer power. Therefore it is calculated as follows:
TransfPower = 1.05 x 161.16 FILTERED POWER
Unit: rpm Type: R Min: 0 Max: 2500 Def: 1200 Int. scaling:1 == 1
52.27 TraFanMinSpd
Minimum fan speed of transformer fan for both, single and redundant configuration.
Unit: rpm Type: R Min: 0 Max: 52.28 Def: 900 Int. scaling:1 == 1
52.28 TraFanMaxSpd
Maximum fan speed of transformer fan for both, single and redundant configuration.
Unit: rpm Type: R Min: 52.27 Max: 2500 Def: 1770 Int. scaling:1 == 1
52.30 TraFanRefWaveForm
Transformer fan reference waveform.
The speed reference to the fan can be quadratic or linear depending on inverter transformer power
(=1.05 x 161.16 FILTERED POWER).
NAME VALUE MEANING
LINEAR 0 The fan reference is linear dependent on the calculated (1.05 x 161.16)
transformer power.
QUADRATIC 1 The fan reference is quadratic dependent on the calculated (1.05 x
161.16) transformer power
Unit: Type: B Min: 0 Max: 1 Def: 1 Int. scaling:1 == 1
52.31 MaxPowAtMinSpd
Maximum allowed transformer power (=1.05 x 161.16 FILTERED POWER), where the fan is still
allowed to run with minimum speed (52.27) for single configuration. The input must be given in
percentage of the maximum allowed power of the transformer.
Unit: % Type: R Min: 0 Max: 99 Def: 75 Int. scaling:1 == 1
52.32 MaxPowAtRedMinSpd
Maximum allowed transformer power (=1.05 x 161.16 FILTERED POWER), where the fan is still
allowed to run with minimum fan speed (52.27) for redundant configuration. The input must be given in
percentage of the maximum allowed power of the transformer.
Unit: % Type: R Min: 0 Max: 99 Def: 85 Int. scaling:1 == 1
52.33 TraNominalPower
Integrated transformer nominal power in kVA.
Note!
The data must be taken from the transformer name plate!
Unit: kVA Type: R Min: 0 Max: 10000 Def: 500 Int. scaling:1 == 1
52.34 ExpPressAtNomSpd
Expected pressure at nominal fan speed (maximum of inverter and transformer fan). This parameter is
dependent on drive type.
Note!In case of cooling fan redundancy it takes the redundant fan nominal speed. If the air pressure
calibration is used, this value is automatically written at the end of the calibration.
Unit: Pa Type: R Min: 0 Max: 10000 Def: 120 Int. scaling:1 == 1
Note!
Only relevant in redundant configuration.
Unit: s Type: R Min: 0 Max: 30 Def: 10 Int. scaling:1 == 1
If not operational fan recovers at least for the time set in this parameter, the fan control automatically
changes back to redundant operation with all fan running with less fan speed.
Note!
Only relevant in redundant configurations.
Unit: s Type: R Min: 0 Max: 30 Def: 10 Int. scaling:1 == 1
If not operational fan recovers at least for the time set in this parameter, the fan control automatically
changes back to redundant operation with all fan running with less fan speed.
Note!
Only relevant in redundant configurations.
Unit: s Type: R Min: 0 Max: 30 Def: 10 Int. scaling:1 == 1
52.50 FanAuxSupplyType
Parameter selection whether the fans are internally or externally supplied.
The parameter is set by manufacturing key, respectively software download.
NAME VALUE MEANING
EXTERNAL 0 The fans are supplied from externally.
INTERNAL 1 The fans are supplied internally (only supplied if MCB is closed)
Unit: Type: B Min: 0 Max: 1 Def: 0 Int. scaling:1 == 1
55 Motor Data 1
These group can be used to define 4 different sets of motor parameters.
Each of these motors can be selected by parameter 99.15.
The values are then copied to the standard parameter groups (20, 99 ,150).
When setting the first parameter e.g. 55.01 MOTOR NOM VOLTAGE to 0 all values from the
standard groups are copied to group 51.
55.11 Ls [mH]
Stator main inductance.
Unit: mH Type: R Min: Max: Def: Int. scaling:
55.41 IRCompensationENA
Switch for Ir-compensation function
NAME VALUE MEANING
FALSE 0 IR compenstation is disabled
TRUE 1 IR compensation is enabled
Unit: Type: B Min: 0 Max: 1 Def: 1 Int. scaling:1 == 1
Figure Overview of CH4 DDDCS communication between MVD (Medium Voltage Drive) and AC80
(ABB Advant Controller 80)
Figure Overview of CH4 data exchange between MVD (Medium Voltage Drive) and AC80 (ABB
Advant Controller 80)
NOTE!
If the parameter(s) DS(n) ENABLE is set to ENABLED, corresponding dataset must be set in master system (AC80) as
well, otherwise a transmit error will be generated.
Figure Overview of data exchange between MVD (Medium Voltage Drive) and AC80 (ABB Advant
Controller 80) via CH4
NOTE!
If the parameter(s) DS(n) ENABLE is set to ENABLED, corresponding dataset must be set in master system (AC80) as
well, otherwise a receive error will be generated.
Figure Figure Overview of data exchange between and AC80 (ABB Advant Controller 80) and MVD –
AMC3 via CH4
Figure Overview of CH4 DataSet communication between MVD (Medium Voltage Drive) and ACDA
(ABB Aux. Control Device Adapter)
Figure Overview of CH4 data exchange between MVD (Medium Voltage Drive) and ACDA – AMC3
(Aux. Control Device Adapter)
NOTE!
If the parameter(s) DS(n) ENABLE is set to ENABLED, corresponding dataset must be set in master system (ACDA) as
well, otherwise a transmit error will be generated.
Figure Overview of data exchange between MVD (Medium Voltage Drive) and ACDA – AMC3 (Aux.
Control Device Adapter)
NOTE!
If the parameter(s) DS(n) ENABLE is set to ENABLED, corresponding dataset must be set in master system (ACDA) as
well, otherwise a receive error will be generated.
Figure Overview of data exchange between ACDA – AMC3 (Aux. Control Device Adapter) and MVD
(Medium Voltage Drive)
Figure 60-1 Overview of data exchange between ACDA – AMC3 (APU - Auxiliary Pumping Unit) and
MVD – AMC3 via CH4
Unit: Type: I Min: 6001 Max: 6001 Def: 6001 Int. scaling:1 == 1
Unit: Type: I Min: 6002 Max: 6002 Def: 6002 Int. scaling:1 == 1
Unit: Type: NoType Min: 6003 Max: 6003 Def: 6003 Int. scaling:1 == 1
Unit: conn Type: I Min: 0 Max: 25599 Def: 802 Int. scaling:1 == 1
Unit: conn Type: I Min: 0 Max: 25599 Def: 803 Int. scaling:1 == 1
NOTE!
· writing to AMC-table index is controlled by parameter 62.08 DSET 102&103 ENABLE
NOTE!
· writing to AMC-table index is controlled by parameter 62.08 DSET 102&103 ENABLE
Unit: Type: I Min: 0 Max: 25599 Def: 0 Int. scaling:1 == 1
NOTE!
· writing to AMC-table index is controlled by parameter 62.08 DSET 103&103 ENABLE
Unit: conn Type: I Min: 0 Max: 25599 Def: 0 Int. scaling:1 == 1
NOTE!
· writing to AMC-table index is controlled by parameter 62.08 DSET 103&104 ENABLE
Unit: conn Type: I Min: 0 Max: 25599 Def: 0 Int. scaling:1 == 1
NOTE!
· writing to AMC-table index is controlled by parameter 62.08 DSET 103&104 ENABLE
Unit: conn Type: I Min: 0 Max: 25599 Def: 0 Int. scaling:1 == 1
NOTE!
• writing to AMC-table index is controlled by parameter 62.15 DSET 104&105 ENABLE
Unit: Type: I Min: 0 Max: 25599 Def: 0 Int. scaling:1 == 1
NOTE!
• writing to AMC-table index is controlled by parameter 62.15 DSET 104&105 ENABLE
Unit: Type: I Min: 0 Max: 25599 Def: 0 Int. scaling:1 == 1
NOTE!
• writing to AMC-table index is controlled by parameter 62.15 DSET 104&105 ENABLE
Unit: Type: I Min: 0 Max: 25599 Def: 0 Int. scaling:1 == 1
NOTE!
• writing to AMC-table index is controlled by parameter 62.15 DSET 105&105 ENABLE
Unit: conn Type: I Min: 0 Max: 25599 Def: 0 Int. scaling:1 == 1
NOTE!
• writing to AMC-table index is controlled by parameter 62.15 DSET 105&105 ENABLE
Unit: conn Type: I Min: 0 Max: 25599 Def: 0 Int. scaling:1 == 1
NOTE!
• writing to AMC-table index is controlled by parameter 62.15 DSET 105&105 ENABLE
Unit: conn Type: I Min: 0 Max: 25599 Def: 0 Int. scaling:1 == 1
NOTE!
• writing to AMC-table index is controlled by parameter 62.22 DSET 106&106 ENABLE
Unit: Type: I Min: 0 Max: 25599 Def: 0 Int. scaling:1 == 1
NOTE!
• writing to AMC-table index is controlled by parameter 62.22 DSET 106&107 ENABLE
Unit: Type: I Min: 0 Max: 25599 Def: 0 Int. scaling:1 == 1
NOTE!
• writing to AMC-table index is controlled by parameter 62.22 DSET 106&107 ENABLE
Unit: Type: I Min: 0 Max: 25599 Def: 6012 Int. scaling:1 == 1
NOTE!
• writing to AMC-table index is controlled by parameter 62.22 DSET 106&107 ENABLE
Unit: conn Type: I Min: 0 Max: 25599 Def: 0 Int. scaling:1 == 1
NOTE!
• writing to AMC-table index is controlled by parameter 62.22 DSET 106&107 ENABLE
Unit: conn Type: I Min: 0 Max: 25599 Def: 0 Int. scaling:1 == 1
NOTE!
• writing to AMC-table index is controlled by parameter 62.22 DSET 107&107 ENABLE
Unit: conn Type: I Min: 0 Max: 25599 Def: 0 Int. scaling:1 == 1
NOTE!
• writing to AMC-table index is controlled by parameter 62.29 DSET 108&109 ENABLE
Unit: Type: I Min: 0 Max: 25599 Def: 0 Int. scaling:1 == 1
NOTE!
• writing to AMC-table index is controlled by parameter 62.29 DSET 108&109 ENABLE
Unit: Type: I Min: 0 Max: 25599 Def: 0 Int. scaling:1 == 1
NOTE! • writing to AMC-table index is controlled by parameter 62.29 DSET 108&109 ENABLE
Unit: Type: I Min: 0 Max: 25599 Def: 0 Int. scaling:1 == 1
NOTE!
• writing to AMC-table index is controlled by parameter 62.29 DSET 109&109 ENABLE
Unit: conn Type: I Min: 0 Max: 25599 Def: 0 Int. scaling:1 == 1
Note!
Please check also parameter settings in GROUP 18 – UTILITYS and GROUP 97 DIRECT
DATASET WRITE.
64 ACTUAL SIGNALS
Measured or calculated values
DI 6 DI 1
Figure
DI 13 DI 8
Figure
DO6 DO2
Figure
DI 6 DI 1
Figure
DI 13 DI 8
Figure
DO6 DO2
Figure
65 SYNCHRON BYPASS
Synchronized Bypass function for starter. Group is activated by parameter 38.07
65.07 BrkOpenTimeLimit
Maximum operating time for opening the motor breakers. If the motor breaker has not opened within this
time a trip will be initiated.
Unit: s Type: R Min: 1 s Max: 30 s Def: 3 s Int. scaling:100 == 1 s
65.08 MaxMtrCurForSwiSmx
DTC: Maximum (relative) motor current for opening motor breaker. After the line breaker (Sbpx) has
been closed the motor breaker still remains closed for a while until the load of the converter is
commutated smoothly to the line. If the rel. motor current is < this parameter the motor breaker is
opened. Scalar Control: The motor breaker is opened directly after receiving the line breaker (Sbpx)
closed signal. The setting of this parameter has no influence during scalar control.
Unit: % Type: R Min: 0 Max: 1 Def: 0,15 Int. scaling:1 == 1 %
To set the new motor parameters, first select the motor by digital inputs 6-8 of IOEC5. Type in the
parameter in the usual groups (like if you had only one motor parameter set). Typing in new parameters
is only possible in state “Rdy MCB On”.
65.10 FluxChange / s
DTC: Parameter for adjusting how fast the flux reference (par 27.03) is changed per second.
After the line breaker (Sbpx) has been closed the motor breaker still remains closed for a while until the
load of the converter is commutated smoothly to the line:
For this the torque is ramped to zero and then the flux reference is changed to have a minimum motor
current. This parameter has to be adjusted to achieve a stable control of the flux because optimal flux
reference is depending on ACS1000-, motor- and line properties.
Hints:
0 %/s is used for tuning. Par 27.03 can be adjusted directly to find out optimal flux reference.
If motor current is smaller than 40% of rated current change of flux will be automatically reduced.
Scalar Control: The motor breaker is opened directly after receiving the line breaker (Sbpx) closed
signal. The setting of this parameter has no influence during scalar control.
Group 66 UTILITY
66 UTILITY
MULTIPLE - DATA – TRANSMIT FUNCTION
The multiple-data-transmit function can be used for cyclically transmitting a selected number
(array) of parameter values to an overriding system by using only two data sets.
The multiple-data-transmit function is active as soon a valid data set number is set to parameter
66.01 DSWRITE NO4 or 66.09 DSWRITE NO5. If the function is activated the data set
DSWRITE NO4:I1 resp. DSWRITE NO5:I1 transmits the actual selected parameter and the data
set DSWRITE NO4:I2 resp. DSWRITE NO5:I2 transmits the corresponding actual value of actual
selected parameter. In addition the actual value of the selected parameter in parameter 66.07
DS4 PARRD NO4:I3 resp. parameter 66.15 DS4 PARRD NO4:I3 is cyclically transmitted to
DSWRITE NO4:I3 resp. DSWRITE NO5:I3. The interval time of the multiple data transmit
function has to be set depending on the cycle time of the overriding system.
Note!
The update time in the overriding control system (PLC) must be shorter than the total
transmission time. The selected DataSet Number can be used only once in the drive system.
Therefore the selected data set number is disabled in Group 63, Group 91 or Group 94.
CycleTime =
66.02
DS4 TIME INTERVAL
Interval Time x
AMC3 PLC
e.g.: 50 Nr Of Indexes
SELECT
DS4 START ADDRESS
66.03 9 Selected Group COUNTER
Group
e.g.: 901
1 Start Index n1
In dex
1 COMP
SW (R)
I1
I1 = I2
DS4 NR OF INDEXES nx 901 I2
66.04
8 9.01 Comb Fault Word 1
e.g.: 8
Actual se lected
"Parame ter"
Parameter
Write COMPARE
ADD SW (R)
I1
+ DS4 TRANSM PAR I1 = I2
OUT IN Out 66.05 908 I2
+
9.08 Comb Alarm Word 4
Actual "Value of
se le cted P arameter"
Parameter
Read Parameter
Group
Write
Index
DS4 PAR ACT VAL
Va lue IN Out 66.06
Actual "Value of
selected DSx Val3"
Parameter
Read
Figure
Example: Parameter 66.03 is set to 901, with 9 representing the group no. and 01 representing the
start index of the transmitted (displayed) parameter. Parameter 66.05 set to 5, with 5 representing the
number of indices
--> Parameter 66.05 displays: 1st cycle 901, 902…….905, 2nd cycle 901, 902…….905 a.s.o.
Unit: Type: I Int. scaling: 1 == 1
Example: Parameter 66.11 is set to 901, with 9 representing the group no. and 01 representing the
start index of the transmitted (displayed) parameter. Parameter 66.12 set to 5, with 5 representing the
number of indices
--> Parameter 66.13 displays: 1st cycle 901, 902…….905, 2nd cycle 901, 902…….905 a.s.o.
Unit: Type: I Int. scaling: 1 == 1
DS100
:
DS119
Figure DATA SET - RECEIVE / TRANSMIT VALUE DISPLAY
Example:
If parameter is set to 100:
• the parameter 66.18 DSVALUE DEBUG:I1 shows the value of DataSet 100 Value1
• the parameter 66.19 DSVALUE DEBUG:I2 shows the value of DataSet 100 Value2
• the parameter 66.20 DSVALUE DEBUG:I3 shows the value of DataSet 100 Value3
Unit: Type: I Min: -32768 Max: 32767 Def: 0 Int. scaling:1 == 1
70 DDCS CONTROL
Parameter settings of the DDCS (Distributed Drives Communication System) communication
channels.
CAUTION!
Handle the fibre optic cable with care. Do not touch the ends with bare hands, as fibre optic
cables are extremely sensitive to dirt.
AC70, AC80 & FCI Module - Bus The Position can be calculated as follow:
Position Par. 70.01 16 x hundred number in position
101 17 number + rest of position number
: :
112 28 For example:
201 33 DRIENG / Position = 711
: :
212 44 711 Þ 7 x 16 + 11 = 123
701 113
: : Þ 70.01 = 123
712 124
Figure
In some applications both speed control and torque control of the Followers are required. In those cases a flying
change between speed and torque control can be performed via digital input of the follower (see Chapter 3 – Operation,
at the Master/Follower Application Macro Manual).
Please pay attention to the description of parameters 21.09 and 21.10: MCB closing and opening time limits for master
drive!
ACS1000 ACS1000
Mains 3 3 Mains 3 3
External n External n
Control Signals Control Signals
MASTER MASTER
ACS1000 ACS1000
2 2 2 2
Mains 3 3 Mains 3 3
FOLLOWER FOLLOWER
Follower Fault Follower Fault
Master/Follower Link Master/Follower Link
Supervision Supervision
Figure 70-3 MasterFollower Applications, Schematic Representation
Figure
(Process Stop)
(Process Stop)
IOEC 2
IOEC 2
IOEC 2
Fault (-1)
Fault (-1)
Fault (-1)
X12 5 6 X24 3 2 1 X12 5 6 X24 3 2 1 X12 5 6 X24 3 2 1
MASTER FOLLOW ER
(FIXED)
Value DDCS Link Value
7.07 CH2 M ASTE R SI GN AL1 DS FCW
Follower Control Word 70.09 1 CH 2 1 3.21
23.01 CH2 M ASTE R SI GN AL 2 DS SPEED REF
Speed Reference 70.10 2 2 3.22
3.13 CH2 M ASTE R SI GN AL 3 DS TORQ REF A
70.11 3 3 3.23
Torque Used Ref
P ar.70.17 - FO LL SPEED RE F
"MASTER"
nr
Data Set
1 or 10 122.19
FBA CH 0 1 "MASTER"
*
2
torq_ref_a
3 122.21
Par .75.0 6 - DA TA SE T CO MM
OCW
"RE AD / WRIT E" Figure 11 - 1
& 7.06 &
Par .70.0 8 - CH2 M/F MO DE
"FO LL OWER" Figure 11 - 2
Figure 12 - 1
&
Par .70.18 - FOLL TORQ REF & Figure 12 - 2
"FO LL OW ER"
REF2 OVE RR SYST
3.25
* NOTE!
If Par. 70.17 resp. 70.18 is selected to "MASTER" , the direct fast communication link is used to send
the SPEED REF resp. TORQ REF A directly to motor control (parameter 122.19 resp. 122.21), the
reference value from Application (Par. 23.01 SPEED REF resp. 25.01 TORQ REF A) will be ignored!
Figure 70-7 Follower Signal Selection - Overview
ACS1000 ACS1000
Mains 3 3 Mains 3 3
External n External n
Control Signals Control Signals
MASTER MASTER
ACS1000 ACS1000
2 2 2 2
Mains 3 3 Mains 3 3
FOLLOWER FOLLOWER
Follower Fault Master/Follower Follower Fault Master/Follower
Supervision Link Supervision Link
Figure
Figure
Master Follower Follower
(Process Stop)
(Process Stop)
IOEC 2
IOEC 2
IOEC 2
Fault (-1)
Fault (-1)
Fault (-1)
Figure
RING Connection
AMC3 AMC3 AMC3
CH3 CH3 CH3
AMC3
CH3
AMC3
CH3
72.02 STOCommandGrp+Indx
A binary signal (i.e. from digital input) is assigned to parameter 72.01 DI FUNCTION
SELECTION STATUS 1 – b00 by setting parameter 72.02 to the parameter group and
index from which the signal is to be taken from. Additionally, the bit number, which
identifies the signal within the status word, has to be selected with parameter 72.03. The
format is (x)xyy, where (x)x is the group and yy is the index of the desired signal.
Example:
If Par. 72.02 is set to 422 and 72.03 is set to 1, the status of DI STO COMMAN (b00) of parameter
72.01 DI FUNCTION SELECTION STATUS 1 is set to 1 if digital input IOEC2 – DI02 is active.
72.03 STOCommandBitNum
This parameter specifies the bit number (0…15) of the previous selected signal 72.02.
Unit: Type: I Min: 0 Max: 15 Def: 0 Int. scaling:
A binary signal (i.e. from digital input) is assigned to parameter 72.01 DI FUNCTION
SELECTION STATUS 1 – b02 by setting parameter 72.06 to the parameter group and
index from which the signal is to be taken from. Additionally, the bit number, which
identifies the signal within the status word, has to be selected with parameter 72.07. The
format is (x)xyy, where (x)x is the group and yy is the index of the desired signal.
Example:
If Par. 72.06 is set to 422 and 72.07 is set to 2, the status of DI EMERGE STOP COMMAND (b02)
of parameter 72.01 DI FUNCTION SELECTION STATUS 1 is set to 1 if digital input IOEC2 –
DI03 is active.
Unit: Type: I Min: 0 Max: 30000 Def: 0 Int. scaling:
72.07 EmergeStopBitNum
This parameter specifies the bit number (0…15) of the previous selected signal 72.06.
Unit: Type: I Min: 0 Max: 15 Def: 0 Int. scaling:
72.08 ArcFltDetGrp+Indx
A binary signal (i.e. from digital input) is assigned to parameter 72.01 DI FUNCTION
SELECTION STATUS 1 – b03 by setting parameter 72.08 to the parameter group and
index from which the signal is to be taken from. Additionally, the bit number, which
identifies the signal within the status word, has to be selected with parameter 72.09. The
format is (x)xyy, where (x)x is the group and yy is the index of the desired signal.
Example:
If Par. 72.08 is set to 422 and 72.09 is set to 1, the status of DI ARC DETECT (b03) of parameter
72.01 DI FUNCTION SELECTION STATUS 1 is set to 1 if digital input IOEC2 – DI02 is active.
Unit: Type: I Min: 0 Max: 30000 Def: 0 Int. scaling:
72.09 ArcFltDetBitNum
This parameter specifies the bit number (0…15) of the previous selected signal 72.08.
Unit: Type: I Min: 0 Max: 15 Def: 0 Int. scaling:
75 OPTION MODULES
All IOEC - boards are connected in a ring to the AMC3 - board by using DDCS channel 1 (CH1).
Each of these modules is given a unique address using by setting the rotating switch to the
appropriate value. The IOEC1 Standard I/O board has permanent address number 2 (node-
address-switch set to 2) and IOEC2 Standard I/O board has permanent address number 4 (node-
address-switch set to 4).
Fieldbus adapter modules are connected to the AMC3 - board by using DDCS channel 0 (CH0).
The encoder module NTAC-02 is connected to the AMC3 - board by using DDCS channel 5 (CH5).
The parameters marked with (O) can only be altered while the ACS1000 is stopped.
6
Node-
switch
Figure
Node-
switch
Figure
ON
DIP -
switches 1 2 3 4 5 6 7
Figure
75.06 Fan(s)TypeSel
Fan type selection.
NAME VALUE MEANING
AC FAN 0 AC fan type installed.
EC FAN 1 EC fan type installed.
Unit: Type: B Min: 0 Max: 1 Def: 0 Int. scaling:1 == 1
DI 6 DI 1
Figure
DI 13 DI 8
Figure
DO6 DO2
Figure
81 AN INPUT IOEC3
The analogue input value can be selected in milliamps or volts by means of a HW-switch.
81.26 AI1SelIO3
This parameter selects the AI1 signal of IOEC3. The parameter is write-protected; it is set by the loading
package via type code. actual value par.
NAME VALUE MEANING
NONE 0
TrafTmpExt/3 1
LoadBearTmp1 2
VibraSens1 3
GndCurrent1 4
Unit: Type: I Min: 0 Max: 3 Def: 0 Int. scaling:1 == 1
83 AN OUTPUT IOEC3
Parameter group 83 provides the settings to assign any accessible real type numerical value of the
AMC – table (i.e. actual values like motor current, motor speed…) to an analogue output of IOEC3
and make the adjustment for scaling, filtering, inverting of the output signal.
Numerical values from a higher-level control system can also be transferred to the analogue
outputs.
83.01 AO1Group+IndexIO3
A numerical value of the AMC-table is assigned to analogue output by setting parameter 83.01 to the
parameter group and index the value is to taken from. The format is (x)xyy, where (x)x the group and yy
is the index of the desired signal.
Example:
When the actual value of the MOTOR FREQUENCY is to be read out at AO1 – IOEC3, parameter
83.01 is set to 107 with 1 representing the group and 07 representing the index.
A numerical value from a higher-level control system can also transferred to the analogue output. The
data set where the value is transmitted into the AMC-table is directed to one of the DATA parameters
(19.01…19.08) by means of either parameters 90.01...90.12 or 92.01…93.12 (see Figure 19-1). The
value is then assigned to the analogue output by setting 83.01 to the group and index of the desired
DATA parameter (for example: 1901 Þ 19 = group , 01 = index)
The default setting of 83.01 is 2301, SpeedRef.
NOTE!
In case of EC fans this analog output cannot be used, since its used for redundant fan speed reference.
Unit: Type: I Min: 0 Max: 30000 Def: 2301 Int. scaling:1 == 1
Example:
When the actual value of the MOTOR CURRENT is to be read out at AO2 – IOEC3, parameter 83.06 is
set to 107 with 1 representing the group and 07 representing the index.
A numerical value from a higher-level control system can also transferred to the analogue output. The
data set where the value is transmitted into the AMC-table is directed to one of the DATA parameters
(19.01…19.08) by means of either parameters 90.01...90.12 or 92.01…93.12 (see Figure 19-1). The
value is then assigned to the analogue output by setting 83.06 to the group and index of the desired
DATA parameter (for example: 1901 Þ 19 = group , 01 = index)
84.01 DO1Group+IndexIO3
A binary signal (i.e. from a status word) is assigned to digital output DO1 by setting parameter 84.01 to
the parameter group and index from which the signal is to be taken from. Additionally the bit number,
which identifies the signal within the status word, has to be selected with parameter 84.02. The format is
(x)xyy, where (x)x the group and yy is the index of the desired signal.
Example:
If Par. 84.01 is set to “807” and 84.02 is set to “0” , digital output DO1 is active when 8.07 LIMIT WORD
2 / BIT 0 is “1”. If Par. 84.01 is set to “702” and 84.02 is set to “12,13 or14”, digital output DO1 is
controlled from the overriding system by 7.02 AUX CONTROL WORD 2.
By default, DO1 indicates Speed Ref Limit signal (Par. 8.07 / Bit 0).
NOTE!
With the motor cooler option (par. 38.02 ‘MotorCooler’ = ‘SOFT STOP’ or ‘ALARM’) DO1 is fixed to the
‘Motor Cooler Order On’ command.
Unit: Type: I Min: 0 Max: 30000 Def: 807 Int. scaling:1 == 1
84.04 DO2Group+IndexIO3
A binary signal (i.e. from a status word) is assigned to digital output DO2 by setting parameter 84.04 to
the parameter group and index from which the signal is to be taken from. Additionally the bit number,
which identifies the signal within the status word, has to be selected with parameter 84.05. The format is
(x)xyy, where (x)x the group and yy is the index of the desired signal.
Example:
If Par. 84.04 is set to “801” and 84.05 is set to “9”, digital output DO2 is active when 8.01 MAIN
STATUS WORD / BIT 9 is “1”. If Par. 84.04 is set to “702” and 84.05 is set to “12,13 or14”, digital output
DO2 is controlled from the overriding system by 7.02 AUX CONTROL WORD 2.
By default, DO2 indicates LOCAL operation signal (Par. 8.01 / Bit 9 – inverted ; parameter 84.06 is set
to INVERTED).
NOTE!
With the new aux. power concept and the redundant cooling fan / pump option (par. 41.03 = ‘TWO
(FAN1&2)’) DO2 is fixed to the following command:
ACS 1000: ‘Cooling Fan/Pump 2 Order On’,
ACS 1000i: ‘Cooling Fan Grp. 2 Order On’ (second inverter and transformer fan in parallel).
Unit: Type: I Min: 0 Max: 30000 Def: 801 Int. scaling:1 == 1
84.07 DO3Group+IndexIO3
A binary signal (i.e. from a status word) is assigned to digital output DO3 by setting parameter 84.07 to
the parameter group and index from which the signal is to be taken from. Additionally the bit number,
which identifies the signal within the status word, has to be selected with parameter 84.08.The format is
(x)xyy, where (x)x the group and yy is the index of the desired signal.
Example:
If Par. 84.07 is set to “807” and 84.08 is set to “1”, digital output DO3 is active when 8.07 LIMIT WORD
2 / BIT 1 is “1”. If Par. 84.07 is set to “702” and 84.08 is set to “12,13 or14”, digital output DO3 is
controlled from the overriding system by 7.02 AUX CONTROL WORD 2.
By default, DO3 indicates SPEED ACT LIMIT signal (Par. 8.07 / Bit 1)
NOTE!
With water cooling DO3 is fixed to the following command:‘Order close raw water regulation valve’
Unit: Type: I Min: 0 Max: 30000 Def: 807 Int. scaling:1 == 1
84.10 DO4Group+IndexIO3
A binary signal (i.e. from a status word) is assigned to digital output DO4 by setting parameter 84.10 to
the parameter group and index from which the signal is to be taken from. Additionally the bit number,
which identifies the signal within the status word, has to be selected with parameter 84.11. The format is
(x)xyy, where (x)x the group and yy is the index of the desired signal.
Example:
If Par. 84.10 is set to “807” and 84.11 is set to “2”, digital output DO4 is active when 8.07 LIMIT WORD
2 / BIT 2 is “1”. If Par. 84.10 is set to “702” and 84.11 is set to “12,13 or14”, digital output DO4 is
controlled from the overriding system by 7.02 AUX CONTROL WORD 2.
NOTE!
With water cooling DO4 is fixed to the following command: ‘Order open raw water regulation valve’
Unit: Type: I Min: 0 Max: 30000 Def: 807 Int. scaling:1 == 1
84.13 DO5Group+IndexIO3
A binary signal (i.e. from a status word) is assigned to digital output DO5 by setting parameter 84.13 to
the parameter group and index from which the signal is to be taken from. Additionally the bit number,
which identifies the signal within the status word, has to be selected with parameter 84.14. The format is
(x)xyy, where (x)x the group and yy is the index of the desired signal.
Example:
If Par. 84.13 is set to “807” and 84.14 is set to “3”, digital output DO5 is active when 8.07 LIMIT WORD
2 / BIT 3 is “1”. If Par. 84.13 is set to “702” and 84.14 is set to “12,13 or14”, digital output DO5 is
controlled from the overriding system by 7.02 AUX CONTROL WORD 2.
Note!
If Par. 38.10 INTEGRATED TRAFO FAN set to an other value than “0”, the digital output D05 is fix
connected to TRAFO FAN1 ORD ON signal. Par. 84.13, 84.14 & 84.15 are not in function.
84.16 DO6Group+IndexIO3
A binary signal (i.e. from a status word) is assigned to digital output DO6 by setting parameter 84.16 to
the parameter group and index from which the signal is to be taken from. Additionally the bit number,
which identifies the signal within the status word, has to be selected with parameter 84.17. The format is
(x)xyy, where (x)x the group and yy is the index of the desired signal.
Example:
If Par. 84.16 is set to “807” and 84.17 is set to “4”, digital output DO6 is active when 8.07 LIMIT WORD
2 / BIT 4 is “1”. If Par. 84.16 is set to “702” and 84.17 is set to “12,13 or14”, digital output DO6 is
controlled from the overriding system by 7.02 AUX CONTROL WORD 2.
Note!
If Par. 41.07 INTEGRATED TRAFO FAN set to an other value than “0”, the digital output D06 is fix
connected to TRAFO FAN2 ORD ON signal. Par. 84.16, 84.17 & 84.18 are not in function.
By default, DO6 indicates SUP SIG 1 LIMIT signal (Par. 8.07 / Bit 4)
Unit: Type: I Min: 0 Max: 30000 Def: 807 Int. scaling:1 == 1
DI 6 DI 1
Figure
DI 13 DI 8
Figure
DO6 DO2
Figure
86 AN INPUT IOEC4
Scaling and selection of Analogue Input’s
88 AN OUTPUT IOEC4
Parameter group 88 provides the settings to assign any accessible real type numerical value of the
AMC – table (i.e. actual values like motor current, motor speed…) to an analogue output of IOEC4
and make the adjustment for scaling, filtering, inverting of the output signal.
Numerical values from a higher-level control system can also be transferred to the analogue
outputs.
88.01 AO1Group+IndexIO4
A numerical value of the AMC-table is assigned to analogue output by setting parameter 88.01 to the
parameter group and index the value is to taken from. The format is (x)xyy, where (x)x the group and yy
is the index of the desired signal.
Example:
When the actual value of the MOTOR SPEED is to be read out at AO1 – IOEC4, parameter 88.01 is set
to 102 with 1 representing the group and 02 representing the index.
A numerical value from a higher-level control system can also transferred to the analogue output. The
data set where the value is transmitted into the AMC-table is directed to one of the DATA parameters
(19.01…19.08) by means of either parameters 90.01...90.12 or 92.01…93.12 (see Figure 19-1). The
value is then assigned to the analogue output by setting 88.01 to the group and index of the desired
DATA parameter (for example: 1901 Þ 19 = group , 01 = index)
Example:
When the actual value of the MOTOR TORQUE FILT is to be read out at AO2 – IOEC4, parameter
88.06 is set to 108 with 1 representing the group and 08 representing the index.
A numerical value from a higher-level control system can also transferred to the analogue output. The
data set where the value is transmitted into the AMC-table is directed to one of the DATA parameters
(19.01…19.08) by means of either parameters 90.01...90.12 or 92.01…93.12 (see Figure 19-1). The
value is then assigned to the analogue output by setting 88.06 to the group and index of the desired
DATA parameter (for example: 1901 Þ 19 = group , 01 = index)
89.01 DO1Group+IndexIO4
A binary signal (i.e. from a status word) is assigned to digital output DO1 by setting parameter 89.01 to
the parameter group and index from which the signal is to be taken from. Additionally the bit number,
which identifies the signal within the status word, has to be selected with parameter 89.02. The format is
(x)xyy, where (x)x the group and yy is the index of the desired signal.
Example:
If Par. 89.01 is set to “801” and 89.02 is set to “1”, digital output DO1 is active when 8.01 MAIN
STATUS WORD / BIT 1 is “1”. If Par. 89.01 is set to “702” and 89.02 is set to “12,13 or14”, digital output
DO1 is controlled from the overriding system by 7.02 AUX CONTROL WORD 2.
By default, DO1 indicates SPEED REF LIMIT signal (Par. 8.07 / Bit 0)
Unit: Type: I Min: 0 Max: 30000 Def: 807 Int. scaling:1 == 1
89.04 DO2Group+IndexIO4
A binary signal (i.e. from a status word) is assigned to digital output DO2 by setting parameter 89.04 to
the parameter group and index from which the signal is to be taken from. Additionally the bit number,
which identifies the signal within the status word, has to be selected with parameter 89.05. The format is
(x)xyy, where (x)x the group and yy is the index of the desired signal.
Example:
If Par. 89.04 is set to “801” and 89.05 is set to “1”, digital output DO2 is active when 8.01 MAIN
STATUS WORD / BIT 1 is “1”. If Par. 89.04 is set to “702” and 89.05 is set to “12,13 or14”, digital output
DO2 is controlled from the overriding system by 7.02 AUX CONTROL WORD 2.
By default, DO2 indicates SPEED ACT LIMIT signal (Par. 8.07 / Bit 1)
Unit: Type: I Min: 0 Max: 30000 Def: 807 Int. scaling:1 == 1
89.07 DO3Group+IndexIO4
A binary signal (i.e. from a status word) is assigned to digital output DO3 by setting parameter 89.07 to
the parameter group and index from which the signal is to be taken from. Additionally the bit number,
which identifies the signal within the status word, has to be selected with parameter 89.08. The format is
(x)xyy, where (x)x the group and yy is the index of the desired signal.
Example:
If Par. 89.07 is set to “801” and 89.08 is set to “1”, digital output DO3 is active when 8.01 MAIN
STATUS WORD / BIT 1 is “1”. If Par. 89.07 is set to “702” and 89.08 is set to “12,13 or14”, digital output
DO3 is controlled from the overriding system by 7.02 AUX CONTROL WORD 2.
89.10 DO4Group+IndexIO4
A binary signal (i.e. from a status word) is assigned to digital output DO4 by setting parameter 89.10 to
the parameter group and index from which the signal is to be taken from. Additionally the bit number,
which identifies the signal within the status word, has to be selected with parameter 89.11. The format is
(x)xyy, where (x)x the group and yy is the index of the desired signal.
Example:
If Par. 89.10 is set to “801” and 89.11 is set to “1”, digital output DO4 is active when 8.01 MAIN
STATUS WORD / BIT 1 is “1”. If Par. 89.10 is set to “702” and 89.11 is set to “12,13 or14”, digital output
DO4 is controlled from the overriding system by 7.02 AUX CONTROL WORD 2.
Example:
If Par. 89.13 is set to “801” and 89.14 is set to “1”, digital output DO5 is active when 8.01 MAIN
STATUS WORD / BIT 1 is “1”. If Par. 89.13 is set to “702” and 89.14 is set to “12,13 or14”, digital output
DO5 is controlled from the overriding system by 7.02 AUX CONTROL WORD 2.
By default, DO5 indicates SUP SIG 1 LIMIT signal (Par. 8.07 / Bit 4)
Unit: Type: I Min: 0 Max: 30000 Def: 807 Int. scaling:1 == 1
89.16 DO6Group+IndexIO4
Digital output 6 is controlled by a selectable bit (see Par. 89.17) of the signal selected with this
parameter. The format is (x)xyy, where (x) the group and yy is the index of the desired signal.
Example:
If Par. 89.16 is set to “807” and 89.17 is set to “6”, digital output DO6 is active when 8.05 LIMIT WORD
2 / BIT 6 is “1”. If Par. 89.16 is set to “702” and 89.17 is set to “12,13 or14”, digital output DO6 is
controlled from the overriding system by 7.02 AUX CONTROL WORD 2.
Note!
If Par. 38.05 BRAKE CHOPPER INSTALLED is set to “1”, the digital output D06 is fix connected to the
BRAKE CHOPPER ORDER ON signal. Par. 89.16 , 89.17 & 89.19 are not in function.
By default, DO6 indicates SUP SIG 2 LIMIT signal (Par. 8.07 / Bit 5)
Unit: Type: I Min: 0 Max: 30000 Def: 807 Int. scaling:1 == 1
Overriding
AMC 3
System
DataSet Table
10
12
14
16
Figure 90-1 Receive Data from Fieldbus (Data Set 1…16) - Overview
91 D SET TR ADDR
Signal addresses for the data transmitted to the overriding system.
The format is x(xyy), where (x)x = Group and yy = Index.
Overriding
AMC 3
System
DataSet Table
11
13
15
17
Overriding
System AMC 3
Address
Assignment of AMC
DataSet Table DataSet Table
Group
DDCS link 18
92.01 ... 92.21
20 93.01 ... 93.12
:
CH0 :
38
NOTE !
This group 93 is visible only if the FBA Dset10 is selected (75.01).
94 D SET TR ADDR
Signal addresses for the data transmitted to the overriding system.
The format is (x)xyy, where (x)x = Parameter Group and yy = Parameter Index.
Overriding
System AMC 3
Address
Assignment of AMC
DataSet Table DataSet Table
Group
DDCS link 19
94.01 ... 94.21
21 95.01 ... 95.12
:
CH0 :
39
95 D SET TR ADDR
Signal addresses for the data transmitted to the overriding system.
The format is x(xyy), where (x)x = Group and yy = Index.
(see Figure 94-1 Overview transmit data to fieldbus)
NOTE !
This group 93 is visible only if the FBA Dset10 is selected (75.01).
97 PSTD BUFFER
Access to diagnostic buffer.
98.01 SetNewRealTime
Selects the source for setting of new clock time (Par. 98.02… 98.07).
VALUE NAME MEANING
1 PANEL SET Set new real time clock by Panel command “PANEL SET ON”. After
OFF new time has been set, the parameter will be automatically set back
to “PANEL SET OFF”.
2 PANEL SET ON Set new real time clock by Panel command “PANEL SET ON”. After
new time has been set, the parameter will be automatically set back
to “PANEL SET OFF”.
3 DI1 – IO2 Set new real time clock by digital Input. The new time will always be
set after a 0 – 1 flag.
4 DI2 – IO2 Set new real time clock by digital Input. The new time will always be
set after a 0 – 1 flag.
5 DI3 – IO2 Set new real time clock by digital Input. The new time will always be
set after a 0 – 1 flag.
6 DI4 – IO2 Set new real time clock by digital Input. The new time will always be
set after a 0 – 1 flag.
7 DI5 – IO2 Set new real time clock by digital Input. The new time will always be
set after a 0 – 1 flag.
8 DI6 – IO2 Set new real time clock by digital Input. The new time will always be
set after a 0 – 1 flag.
9 COMM.MODULE Set new real time clock by fieldbus command (ACW1 – Bit9). The
new time will always be set after a 0 – 1 flag.
Unit: Type: I Min: 1 Max: 9 Def: 1 Int. scaling:1 == 1
99 START-UP DATA
Parameters to set up the motor information.
Running the motor and the equipment being driven with incorrect start-up data can result in improper
operation, reduction in control accuracy and damage to the equipment.
99.01 LANGUAGE
(101.04) The ACS 1000 Drives Macro displays all information in the selected language. The CDP 312 Control
Panel or DrivesWindow show 13 alternative languages.
VALUE NAME MEANING
0 ENGLISH English
1 ENGLISH AM English Am.
2 DEUTSCH Deutsch
3 ITALIANO Italiano
4 ESPANOL Espanol
5 PORTUGUES Portugese
6 NEDERLANDS Netherlands
7 FRANCAIS Francaise
8 DANSK Dansk
9 SUOMI Suomi
10 SVENSKA Svenska
11 CESKY Czech
12 POLSKI /LOC1
13 PO-RUS /LOC2
Unit: Type: I Min: 1 Max: 13 Def: 0 Int. scaling:1 == 1
99.11 ApplicationRestore
Restores either USER MACRO 1, USER MACRO 2 or FACTORY parameter values depending on the
selection in Parameter 99.13 ApplicationMacro (except “USER MACRO x” parameter group 75 and 99)
VALUE NAME MEANING
0 NO Not selected.
-1 YES Values are restored.
Unit: Type: B Min: Max: Def: NO Int. scaling:1 == 1
99.13 ApplicationMacro
Application macros are stored parameter sets. By using the user macros customized parameter sets
can be stored and loaded.
The current parameter settings can be saved as a User Macro: USER 1 SAVE or USER 2 SAVE. These
settings can be recalled using USER 1 LOAD or USER 2 LOAD. If USER MACRO 1 or 2 is in use, the
parameter values are stored to the last saved values. In addition, the last saved results of the motor
identification are restored.
Exception: Settings of Parameters 16.05. During APPLICATION MACRO changes, the alarm message
“MACRO CHANGE” will be shown on the panel (until the new macro is loaded completely). If the MCB
will try to close during the “macro change” – time the drive will change to trip state and a fault message
is coming up.
Note:
The backup function of Drive Window only saves the active User Macro if called: thus both User Macros
must be backed up separately.
The User Macro can be changed from digital inputs or from the overriding system by using AUX CTRL
WORD 1 (7.02) Bit 4 (see also Parameter 16.05). The status of the active macro can be seen in AUX
STATUS WORD 2 (8.03) Bits 8 and 9.
VALUE NAME MEANING
1 FACTORY Factory parameters are recalled and stored to the FLASH.
2 USER 1 LOAD Parameter set1 (USER MACRO 1) is loaded to the RAM memory.
3 USER 1 SAVE Parameter set1 (USER MACRO 1) is saved to the FLASH.
4 USER 2 LOAD Parameter set2 (USER MACRO 2) is loaded to the RAM memory.
5 USER 2 SAVE Parameter set2 (USER MACRO 2) is saved to the FLASH.
6 NONE SEL None selected.
99.14 ControlMode(DTC)
The DTC-control-modes are pre-programmed parameter settings for faster parametrizing. All settings
could be made also manually in the different parameter groups.
Every time the selection is changed, the corresponding parameter settings marked with magenta in
Table 99-1 are applied and stored.
Note!
The unmarked parameters are not overwritten when a different control mode is selected.
VALUE NAME MEANING
1 Speed Ctrl
2 Torque Ctrl
3 PID Ctrl
4 Seq. Ctrl
Unit: Type: I Min: 1 Max: 4 Def: 1 Int. scaling:1 == 1
MODBUS (RS485)
Service Tool
e.g. Drive Window
X3 X1
RS485 AC80
NMBC-01 Drive Bus
(Modbus-Interface)
CDP 80 CDP 80
X2 X4
I/O Interface
DDCS Protocol
Standard
IOEC1 & 2
Transformer
Supervision Option
IOEC3 ... 6
INVERTER
Encoder Module
NTAC-20
Motor
Figure 1.1-1 - Fieldbus / DDCS Communication - Overview
Fieldbus
Master · One fieldbus adapter per drive
· Fieldbus adapter acts as slave
· No direct communication between drives
Fieldbus
........ Fieldbus
Adapter
AC70
Drives Application sw
AF 100
DRIENG
Current
En abled
Status :
Communication OK
Driv e OK
Driv e Al arm
Driv e Warning
Start Drive
events
Stop
PC elements
MMC-ORD MMC-IND
07 MOTOR CURRENT
Index Description Measured motor current absolute value (rms).
:
Unit: A Type: R Min: Max: Int. scaling: 10 == 1A
Each parameter has two different gateways to write the value: integer format or
decimal. Finally, the result is exactly same in the AMC program. This relation is
always shown in the signal and parameter table as shown above
Parameter Setting
Par.: 90. 01 :
Read DataSet values
DSET1 or DSET10 Parameter from Fieldbus
Main Control Word Selection
DSREAD
Par.: 90. 01 : 706 PAR 10 DataSet
DataSet 1/10 Value 1
Value 1
Copy the received
90 Group 1 Value 2
DataSet 1/10 Value 2
value from Fieldbus to
1 Index DataSet 1/10 Value 3 Group 7.06
Value 3
(fixed) 706 InitValue
706 PARWR
DSET 1/10 VAL 1 Name 7 (Group) Group
DIV 6 (Index) Index
Speed Reference 1 100
Value
Par.: 90. 02 : 324 PAR
90 Group Copy the received
value from Fieldbus to
2 Index Group 3.24
(fixed) 324 InitValue
324 PARWR
DSET 1/10 VAL 2 Name 3 (Group)
Group
DIV 24 (Index)
Speed Reference 2
100 Index
Value
Par.: 90. 03 : 325 PAR
90 Group Copy the received
value from Fieldbus to
3 Index Group 3.25
(fixed) 325 InitValue
325 PARWR
DSET 1/10 VAL 3 Name 3 (Group)
Group
DIV 25 (Index)
Index
100
Read DataSet values Value
from Fieldbus
Aux Control Word 1 DSREAD
Par.: 90. 04 : 702 PAR 12 DataSet Value 1
Data Set 3 Value 1
Copy the received
90 Group 3 Data Set 3 Value 2
Value 2 value from Fieldbus to
4 Index Data Set 3 Value 3 Group 7.02
Value 3
(free pro- InitValue
702
grammable) 702 PARWR
D SET 3 VAL 1 Name 7 (Group)
Group
DIV
2 (Index) Index
100
Value
Par.: 75. 04 :
(DataSet 1 or DataSet 10)
Main Status Word
Par.: 91. 01 : 801 PAR
Read selected value
91 Group
(Group 8.01) and transmitt
11
1 Index it to DDCS - Link WriteDataSet values to
InitValue
2 DDCS - Link
(fixed) 801
801 PARRD
DSET 2/11 VAL 1 Name 8 (Group)
DIV Group DSWRITE
100 1 (Index) Index DataSet
Motor Speed
DataSet 2/11 Value 1
Par.: 91. 02 : 102 Value
PAR DataSet 2/11 Value 2
Value 1
91 Group Read selected value Value 2
(free pro- (Group 1.02) and transmitt
DataSet 2/11 Value 3
grammable) 2 Index Value 3
it to DDCS - Link
102 InitValue
Motor Current
100 2 (Index)
Index
Value
Par.: 91. 03 : 107 PAR
91 Group Read selected value
(free pro- 3 Index
(Group 1.07) and transmitt
grammable) it to DDCS - Link
107 InitValue
Name
107 PARRD
D SET 2/11 VAL 3
1 (Group)
DIV Group
100 7 (Index)
Index
Value
Motor Torque
Parameter
Selection
Par.: 94. 01 : PAR Read selected value
94 Group (Group x.xx) and transmitt
(free pro-
1 Index
it to DDCS - Link WriteDataSet values
grammable)
InitValue
to DDCS - Link
xxx
xxx PARRD
DSET 19 VAL 1 Name x (Group)
DIV Group DSWRITE
100 xx (Index) Index 19 DataSet
DataSet 19 Value 1
Par.: 94. 02 : Value Value 1
PAR DataSet 19 Value 2
94 Group Read selected value Value 2
(free pro- (Group x.xx) and transmitt DataSet 19 Value 3
2 Index Value 3
grammable) it to DDCS - Link
xxx InitValue
DataSet 50 DataSet 51
Value 1 Value 1
Value 2 Value 2
DS16READ DS16WRITE
Value 3 Value 3
ParWrite
DIV Group
100 Index
Input
ParRead
Group
DIV
100 Index
Output
MSW_FAULT
MSW_NON_POW ER FAULT_WITH_
DEFECT FAULT WITH DEFECT
NON_POWER SWITCH-ON INHIBITED ASW 2 Bit7 = 1
MCB_OFF
POWER_ON
DISCHARGED
MSW_INIT_PPCS AUXILIARY_POWER_OFF
INIT_PPCS SWITCH-ON INHIBITED
ASW 2 Bit 0 = 0
MSW_FAULT_STOPPED
FAULT_STOPPED TRIPPED
MSW Bit 3 = 1
MSW_READY_TO_CHARGE
READY_TO_
CHARGE READY TO SWITCH ON
MSW Bit 0 = 1 TIME_TAU_ROTOR
MSW_FAULT_1A MSW_FAULT_1B
FAULT_1A FAULT 1 A FAULT_1B FAULT 1 B
MSW _CHARGING
CHARGING ACW2 Bit 1 = 1 ACW2 Bit 2 = 1
READY TO SWITCH ON
STOP_MOTOR
MCW Bit 3 = 0
RESET
MCB_OFF
OCW Bit 7 = 1
MCB_OFF
CHARGING_TIME
OCW Bit 0 = 0 (from any state)
MSW _BREAKING
BREAKING OPERATION ENABLED
MSW_FAULT_3
FAULT_3 FAULT 3
ASW2 Bit 5 = 1
START_MOTOR MCB_OFF
N < CRIT SPEED
OCW Bit 3 = 1
MECH_TIME_CONST
RESET
MSW_STOPPING OCW Bit 7 = 1
STOPPING STOPPING
PROCESS_STOP PROCESS_COAST_
OFF3 OFF3 STOP
MSW STOPPED OFF2
OCW Bit 2 = 0 OFF2
STOPPED STOPPED OCW Bit 1 = 0
ASW1 Bit 11 = 0 n(f) = 0 n(f) = 0 / I = 0
MCB_CLOSED MCB_OFF
ASW2 Bit 5 = 1 MSW Bit 0 = 0
Note!
If
75.04 CommModule FBA DSET 10 READ/WRITE
is set, the communication to the overriding system is done via DataSet 10…51. The control of the drive is working in the
same way.
1.5.2 Pre-Conditions
5238
D
231 H
14F6
H
239 H
Note!
If a fault is pending (Bit 03 of 8.01 MSW is set to “1”) check the reason for
it. After you have get rid of it, set Bit 07 of 7.06 OCW to “1” for at least 1s.
Þ set Bit 00 in 7.06 OCW to “1” Þ MCB will be switched on and ACS1000
starts charging the DC – Link.
1477
H
MAX CHARGING
Udc
7.06 - OCW
8.01 - MSW
233 H
147F
H
7.06 - OCW
Imot
8.01 - MSW
337 H
1.5.6 Change the Direction of Rotation (Motor is Running with Given Speed)
147F
H
0
t
3.24 - Ref1 OS
(- 20000)
MIN
337 H
drive is “RUNNING”
Þ set Bit 03 & Bit 06 in 7.06 OCW to “0” Þ drive starts to decelerate to 0
rpm and will be switched off at zero speed
1437
H
MAX
Stopping Stopped
7.06 - OCW
8.01 - MSW
Imot
t
nmot
233 H
Þ drive starts to decelerate to 0 rpm Þ as soon the actual motor speed is below
the given speed reference Bit 08 in 8.01 MSW will be set to “0” Þ as soon the
actual motor speed reaches zero speed, drive will be switched off and Bit02 in 8.01
MSW will be set to “0” Þ drive is “READY FOR START”
Þ set Bit 03 in 7.06 OCW to “0” Þ drive starts to ramp down (with zero torque), if
actual speed is below self excitation speed, drive will be switched off
1477
H
7.06 - OCW
8.01 - MSW
nself
Imot
t
nmot
563 D 1 1 0 0 1 1 0 0 0 1 0 0 0 0 0 0
233 H
Þ drive starts to decelerate with zero torque Þ as soon the actual motor speed is
below the given speed reference Bit 08 in 8.01 MSW will be set to “0” Þ as soon
the actual motor speed is below the self excitation speed the drive will be switched
off and Bit02 in 8.01 MSW will be set to “0” Þ drive is “READY FOR START”
Þ set Bit 01 in 7.06 OCW to “0” Þ drive will be switched off immediately and
MCB will be opened
147D
H
7.06 - OCW
8.01 - MSW
Imot
Udc
t
Imot
nmot
MIN
7.06 - OCW 8.01 - MSW
Bit 01: 1 -> 0 Bit 02: 1 -> 0
Bit 08: 1-> 0
268 H
Þ drive and MCB will be switched off immediately Þ Bit 03 & 06 in 8.01 MSW will
be set to “1” and Bit 00, 01, 02, 04 & 08 in 8.01 MSW will be set to “0” Þ drive is in
“TRIPPED” state
Þ set Bit 02 in 7.06 OCW to “0” Þ drive starts to decelerate to 0 rpm and MCB will
be switched off at zero speed
147B
H
MAX
Emergency Stop MCB Off
7.06 - OCW
Udc
8.01 - MSW
Imot
t
nmot
258 H
Þ drive starts to decelerate to 0 rpm Þ as soon the actual motor speed is below
the given speed reference Bit 08 in 8.01 MSW will be set to “0” Þ as soon the
actual motor speed reaches zero speed, drive and MCB will be switched off Þ Bit
03 & 06 in 8.01 MSW will be set to “1” and Bit 00, 01, 02 & 05 in 8.01 MSW will be
set to “0” Þ drive is in “TRIPPED” state
The drive parameter and data set information is mapped into a 4xxxx
register area. This holding register area can be read from an external device,
and an external device can modify the register values by writing to them. There are
no setup parameters for mapping the data to the 4xxxx register. The mapping is
pre-defined and corresponds directly to the drive parameter grouping which is
being used by the local drive panel. All parameters are available for both reading
and writing.
The parameter writes are verified for correct value, and for valid register
addresses. Some parameters never allow writes (including actual values), some
parameters allow write only when the drive is stopped (including setup variables),
and some can be modified at any time (including actual reference values).
Register Mapping:
In this mapping, the thousands and hundreds correspond to the group number,
while the tens and ones correspond to the parameter number within a group.
CAUTION! The type definition (GSD) file required for configuration of the master station is
available from www.profibus.com or your local ABB representative. The filename
is ABB_6012.GSD. Please refer to the master station documentation for more
information.
GSD File:
ASCII-format device descriptions file in a specified form. Each device (active &
passive stations) on PROFIBUS has to have its own GSD File.
*Not supported
In this example, PROFIBUS Parameter No. 918 is used to read the station
number of the slave.
Parameter 918 Þ 918d Þ 396h
NOTE!
The drive always observes the Control Word (CW) and Reference (REF)
bytes. The values shown below are examples.
CAUTION! The register addresses which are not allocated to any drive parameter or data set
are invalid. No reads or writes are allowed for these addresses. If there is an
attempt to read or write outside the parameter addresses, the Profibus interface
will return an exception code to the controller.
Detailed instructions for the installation and programming are described in the
NPBA-12 Installation and Start-up Guide manual.
With NPBA-12 SW version V1.5 (or later), Request Labels 1, 2 and 3 can
be used to access drive parameters and PROFIBUS parameters as with
older SW versions. Examples of using these Request Labels are presented
at the end of Chapter 6 of the NPBA-12 Installation and Start-up Guide.
The following is a table of the Request/Response functions updated for
NPBA-12 SW Version V1.5 (or later).
With NPBA-12 SW version V1.5 (or later), drive parameters can also be
accessed using Request Labels 6, 7 and 8. The allocation of drive
parameters to the Parameter Identification part of the PPO type is shown
below:
DRIVE PARAMETERS
Sub-
Par. No. Index Sub-
Index Index Request Label Example
(Decimal (Decimal Index
(Decimal (Hex) Example No.
) ) (Hex)
)
101 1d 1d 1h 1h
102 1d 2d 1h 2h
199 1d 99d 1h 63h R/W 6/7 1, 2
: : : : :
9999 99d 99d 63h 63h
To determine the parameter number and sub index for drive parameter
reading, convert the drive parameter group number and the parameter
index number to hexadecimal. The index number is the sub index (IND),
and the group number is the parameter number (PNU). For example, to
read parameter 84.11 from the drive:
Parameter 84.11 Þ Group 84d . Index 11d Þ Group 54h . Index 0Bh
84.11 = 54h.0Bh Þ Parameter Number = 54h, Sub index = 0Bh
To determine the parameter number and sub index for drive parameter
writing, convert the drive parameter group number and the parameter index
number to hexadecimal. The index number is the sub index (IND), and the
group number is the parameter number (PNU). For example, to write
parameter 12.02 to the drive:
Parameter 12.02 Þ Group 12d . Index 02d Þ Group 0Ch . Index 02h
12.02 = 0Ch.02h Þ Parameter Number = 0Ch, Sub index = 02h
· This first tripping level will be used for slower protective actions
and it includes following actions:
· The torque will be reduced to zero with a ramp.
· The flux will also be reduced with a ramp in order to avoid
overcurrents.
· Then the zero voltage vector will be switched to short circuit the
machine. After a programmable period (5 times rotor time
constant or once the mechanical time constant) the inverter will be
switched off.
· Depending on the failure the MCB will be opened or stay closed.
Therefore we have two different kind of a Trip 1, in order to be
able to react the proper way according to the failure:
· FC2:In this case the MCB will stay closed. In case the MCB will
stay closed and the fault is reseted the drive is in the state „ready
to run“ again.
· FC1:In this case the MCB will be opened. In case the MCB is
opened, the drive is in the state „ready to charge“ after reseting
the fault.
This trip will be used for fast protective actions and it consists of the
following action:
· All inverter IGCTs will be switched off directly; the protection
IGCTs will be opened directly in case of a GUSP fail.
With other faults the protection IGCTs will stay closed until the
DC-link voltage reaches the undervoltage alarm level.
Depending on the failure the MCB will be opened or stay closed. Therefore
we have two different kind of a Trip 2, in order to be able to react the proper
way according to the failure:
· FC2:In this case the MCB will stay closed. In case the MCB will
stay closed and the fault is reseted the drive is in the state „ready
to run“ again.
· FC1:In this case the MCB will be opened (the protection IGCTs
will be switched off with GUSP faults directly). In case the MCB is
opened, the drive is in the state „ready to charge“ after reseting
the fault.
This trip is an enhanced tripping level of the trip 2 and it normally only will
occur, if the inverter is blocked. In this level following actions will be done:
· The machine will be short circuit with the zero voltage vector
directly.
· The protection IGCTs will be switched off in case of short circuit
faults.
With other faults the protection IGCTs will stay closed until the DC-
link voltage reaches the undervoltage alarm level.
· The MCB will be opened.
·
Self excitation could not happen, because the zero voltage will stay
switched. Only used if serious damage to the inverter has happened.
The following chapters give an overview of the I/O signals of all IOEC
boards according to the new aux. power concept.
The tables contain two columns with signal designations, one for ACS 1000
with EPS and one for ACS 1000 resp. ACS 1000i without EPS (new aux.
power concept, UPS). The new aux. power concept is part of the new I/O
concept which also supports ACS 1000i.
The UPS configuration is defined by type code and can be seen in
parameter 112.08 ‘UPSConfiguration’.
ACS 1000-A =ACS 1000 air cooled type; the signal designation is also valid
for ACS 1000i, if ACS 1000i is not extra listed,
ACS 1000-W =ACS 1000 water cooled type,
ACS 1000 =ACS 1000 air and water cooled type,
ACS 1000i =ACS 1000i (air cooled with integrated transformer).
For the new aux. power concept, two new signals had to be placed on IOEC1:
‘UPS Alarm’ and ‘UPS in Battery Mode’. Therefore the ‘Tripping Loop
Supervision’ has been deleted and ‘Disable Local Operation’ has been
moved to IOEC2.
For the new signal ‘MCB Order Trip Supervision’ the signal ‘External Motor
Protection Tripped’ has been moved to IOEC3.
INPUT Signal Designation ACS 1000 with EPS Signal Designation ACS 1000 / ACS 1000i Remarks
without EPS (default)
INPUT Signal Designation ACS 1000 with EPS Signal Designation ACS 1000 / ACS 1000i Remarks
without EPS (default)
INPUT Signal Designation ACS 1000 with EPS Signal Designation ACS 1000 / ACS 1000i Remarks
without EPS (default)
Continue Optional I/O Board IOEC 6 – Synchronised Bypass (only for 2…4 Motors)
4.6 Optional I/O Board IOEC 6 – Synchronised Bypass (only for 2…4
Motors)
04 NOM DC VOLTAGE
Index Description: Downloaded inverter nominal DC-link voltage. The correct value will be set by the loading
package.
Unit: V Type: R Min: 0 Max: 10000 Def: Int. scaling:
05 INU CONFIGURATION
Index Description: Inverter Unit Type. The correct value will be set by the loading package.
Note:
Do not change!
0 = SINGLE INU single inverter unit
Unit: - Type: I Min: 0 Max: 0 Def: 0 Int. scaling: -
06 LSU SUPERVISION
Index Description: RESERVED
Note:
Do not change!
Unit: - Type: B Min: 0 Max: 0 Def: 0 Int. scaling:
07 PFF ENABLE
Index Description: RESERVED
Note:
Do not change!
Unit: - Type: B Min: 0 Max: 0 Def: 0 Int. scaling:
08 HARDPARALLEL ENA
Index Description: RESERVED
Note:
Do not change!
Unit: - Type: B Min: 0 Max: 0 Def: 0 Int. scaling:
09 (Not Used)
Index Description:
Unit: Type: R Min: Max: Def: Int. scaling:
10 DC LINK CAPACITY
Index Description: DC-link capacitance.
Unit: µF Type: R Min: 0 Max: 10000 Def: 0 Int. scaling:
11 SERIES INDUCTANCE
Index Description: Cable inductance in case of cables longer than 1000 meter.
Unit: mH Type: R Min: 0 Max: 40 Def: 0 Int. scaling:
12 STRAY CAPACITANCE
Index Description: Cable capacitance in case of cables longer than 1000 meter.
Unit: µF Type: R Min: 0 Max: 50 Def: 0 Int. scaling:
13 UPS CONFIGURATION
Index Description: In this parameter the implemented ‘Uninterruptible Power Supply’ configuration is shown.
It is set automatically by the loading package according to the type code.
NOTE!
With the configurations 1 and 2 the following signals are connected and the new I/O concept
is used:
IOEC1DI04Control Backup Supply Failure,
IOEC1DI08Control Supply Failure
1 = UPS/Ext3Pinternal UPS (no external safeline) and external 3-phase voltage,
2 = Safel/Ext3Pexternal safeline and external 3-phase voltage.
3 = UPS/Int3Pinternal UPS (no external safeline) and internal 3-phase voltage,
4 = Safel/Int3Pexternal safeline and internal 3-phase voltage.
Unit: - Type: I Min: 1 Max: 4 Def: 1 Int. scaling: -
14 INTEGRATED MCB
Index Description: Only for ACS 1000i:
The correct value will be set by the loading package.
0 = FALSE
1 = TRUE
Unit: - Type: B Min: 0 Max: 1 Def: 0 Int. scaling: -
150.0 RS
1
Index Description: Stator resistance RS.
Unit: W Type: R Min: 0 Max: Def: Int. scaling:
150.0 LS
2
Index Description: Stator inductance LS.
Unit: mH Type: R Min: 0 Max: Def: Int. scaling:
150.0 SIGMALS
3
Index Description: sLS value.
Unit: mH Type: R Min: 0 Max: Def: Int. scaling:
152.0 RLFi
3
Index Description: Filter resistance RLF. The correct value will be set by the loading package or during the filter
ID-Run.
Unit: W Type: R Min: 0 Max: 1000 Def: Int. scaling:
152.1 SelfExcitSpeed
0
Index Description: The self excitation speed of the motor is automatically calculated using the following
formula:
1 60
n selfex = 0 . 8 × ×
LS × C f 2 × p × p
Example:
1 60
nselfex = 0.8 × × = 651rpm
113.8 × 10 H × 135 × 10 F 2 × p × 3
-3 -6
01 R SWITCH POSITION
Index Description: This index includes switch positions of INU during time t-875ms…t+250ms with 25ms resolution
(t is time instant of latest stop/trip). Switch positions are visible with CDP312 panel and phase
order is A,B,C from left to right.
Unit: Type: txt Min: Max: Def: Int. scaling:
21 R NR OF AUTORESTS
Index Description: Diagnostic counter of number of Auto Restarts
Unit: pc Type: I Min: 0 Max: Def: Int. scaling:
s