IAG/IUG/IEG/CEG/LEG
Magnetic Circuit Protectors
Introduction | 105
Single & Multi-Pole | 106
Rocker, Sealed Toggle | 109
Configurations | 114
Operating Characteristics | 116
Delay Curves | 117
Specifications | 121
Decision Tables | 123
IAG/IUG/IEG/CEG/LEG
IAG/IUG/IEG/CEG/LEG Series SINGLE POLE CIRCUIT PROTECTOR
ON
32º
32º
OFF
2.075 .690
[52.71] [17.53]
MAX.
INTRODUCTION
Single Pole Mounting Detail
The Airpax™ IAG/IUG/IEG/CEG/LEG magnetic circuit protectors equipment, vending and amusement machines, military
provide low-cost power switching, reliable circuit protection applications and wherever precision operation is required. +.010
-.000 .590
and accurate circuit control for equipment in the international Temperature differences which affect fuses and other thermal .625 [15.00] 2X 6 – 32 THREAD
marketplace. devices are not a concern. +.25
-.00 MAX. .140 [3.56] DEEP
M3 ISO THD. OPTIONAL
15.88
IEG models meet IEC spacing requirements which is mandatory One important feature of this protector line is a “trip free” action,
for equipment that must comply with IEC specifications 601 and which means the circuit will trip in the presence of an overload O O
F
N
950 and VDE specifications 0804 and 0805. In addition, they are even though the handle is held in the ON position. The delay 1.660 2.000 F
.1.660
1.050 [50.80]
UL Recognized as supplementary protectors per UL STD. 1077, mechanism senses the fault and the contacts open. [42.16]
[26.67] 1.220
[42.16]
standards is not required. DC, 50/60Hz or 400Hz versions. Handles come in seven different
colors and international markings are standard. Single or multi-
Designed using the latest in sensitive hydraulic magnetic pole versions are available, with a variety of pole arrangements
technology, the IAG/IUG/IEG/CEG/LEG line adapts itself to many to meet your specifications. Four pole models require a double
applications and environments. They’re ideal for data processing toggle handle. Units with a handle per pole come in one through LEG Type Units Require Screw
and business machines, medical instrumentation, broadcast six pole assemblies. Terminals
.230
[5.84]
1.530
[38.86]
Note: Tolerance ±.015 [.38] unless noted. Dimensions in brackets [ ] are millimeters.
105 IAG/IUG/IEG/CEG/LEG Series - Introduction http://airpax.sensata.com/ http://airpax.sensata.com/ IAG/IUG/IEG/CEG/LEG Series - Single Pole 106
IAG/IUG/IEG/CEG/LEG
MULTI-POLE CIRCUIT PROTECTORS MULTI-POLE CIRCUIT PROTECTORS
(IAG/IUG/IEG/CEG/LEG) (IAGH/IUGH/IEGH/CEGH/LEGH)
Two Pole Protectors The IAGH/IUGH/IEGH/CEGH/LEGH two, three and four pole
An assembly consisting of two single pole units, having their trip all units simultaneously. A single toggle handle operates all three models are available with a handle per pole.
mechanisms internally coupled and with a single toggle handle, poles for quick and convenient control, or if preferred, a handle
forms the IEG11 with quick-connect D.I.N.-style terminals. per pole is available. The four pole construction consists of four LEGH type units are available only in two pole models.
Individual poles may differ in ratings, delays and internal single pole units assembled with an internal mechanical
4X 6 – 32 THREAD
connections. An auxiliary switch may be included in either or interlock which actuates all units simultaneously. A double IAGH/IUGH/IEGH/CEGH/LEGH Protectors
2X .590 .140 [3.56] DEEP
both poles, allowing you to mix SELV and hazardous voltages. toggle handle operates all four poles. The individual poles need 1.687 .240 [15.00] M3 ISO THD. OPTIONAL
4X 6 – 32 THREAD
Rugged screw-type terminals can be provided, in which case the not have identical characteristics and any series trip pole may [42.85] [6.10]
2X
MAX.
.590 .140 [3.56] DEEP
designation would be IEG66. The IEGH offers a toggle handle for have an auxiliary switch. If screw-type terminals are required, [15.00] M3 ISO THD. OPTIONAL
ON
each pole. LEG type units are avavailable only in one or two pole the breaker designation will be IEG666 for a three pole version MAX.
32º
configurations. and IEG6666 for a four pole version. O O O O O O
F O O
F O O O O
F O O
F O O
F O O
F
N F N F N N N F N N N N
F F F F F F F F F
2.000 1.660
32º
Three Pole and Four Pole Protectors Protector poles are numbered consecutively when viewed from
[50.80] [42.16]
O O O O O O O O O O O O O O O O O O
F
1.220 N F N F N F N F N F N F N F N F N
OFF F F F F F F F F F
The three pole construction consists of three single pole units the terminal side, with the ON position up, starting with Pole #1 2.000 [31.00] 1.660
[50.80] [42.16]
assembled with an internal mechanical interlock which actuates on the left side and proceeding to the right. 1.220
[31.00] 1.515 3.015
2.075 .690 .168 2.265
[52.70] [17.53] [4.27] [38.48] [57.53] [76.58]
MAX. MAX. MAX. MAX.
.168 1.515 2.265 3.015
[4.27] [38.48] [57.53] [76.58]
IAG/IUG/IEG/CEG/LEG Multi-Pole Circuit Breakers MAX. MAX. MAX.
Panel Mounting Detail: Tolerance for Mtg. ±.005 [.13] unless noted.
IAG/IUG/IEG /CEG/LEG NOTE: We recommend machining slots into your panel for 2 or more poles. This eliminates the need to dissemble/reassemble the handle ties to be able to insert the handles thru
Two Pole* Three Pole* Four Pole* indvidiually drilled holes. LEG type units are only available in one or two poles.
1.687 .240
[42.85] [6.10]
+.010
ON LEG Type Units Require Screw Terminals -.000 Two Pole Three Pole* Four Pole*
2X .625
32º .230 +.25
O O O O +.010
-.00
O O F O F O F -.000
N F N N N [5.84] 15.87
F F F F 2X .625
32º +.25
-.001.660
OFF 15.87[42.16]
1.050
1.660 [26.67]
1.530 [42.16]
[38.86] 1.050
2.075 .690 1.515 2.265 3.015 [26.67] .750 .750 .750
[52.71] [17.53] [38.48] [57.53] [76.58] 4X .156 .750 .750 .750 [19.05] [19.05] [19.05]
[3.96] [19.05] [19.05] [19.05]
MAX. MAX. MAX. MAX.
.750 .750 .750
4X .156 .750 .750 .750 [19.05] [19.05] [19.05]
(Optional: Handle may be [19.05] [19.05] [19.05]
[3.96]
located in Pole 1 instead
of Pole 2)
LEG Type Units Require Screw LEG/LEGH Barriers (required)
Terminals *See Two Pole Mounting Detail for hole sizes and locations.
In order to meet UL listing requirements, the LEG/LEGH two
.230 Two Pole* Three Pole* Four Pole* pole model requires barriers. Available with a standard
[5.84]
+.010
straight barrier or an optional “Z” type barrier.
2X .625 -.000
[15.88+.25
-.00 [ Standard Barrier Optional “Z” Barrier
1.530
[38.86]
1.660
[42.17] 1.050
[26.68]
Panel Mounting Detail: Tolerance for Mtg. ±.005 [.13] unless noted. Note: Tolerance ± .015 [.38] unless noted. Dimensions in brackets [ ] are millimeters.
*See Single Pole Mounting Detail for hole sizes and locations. LEG type units are only Note: Tolerance ± .015 [.38] unless noted. Dimensions in brackets [ ] are millimeters.
available in one or two poles.
107 IAG/IUG/IEG/CEG/LEG Series - Multi-Pole http://airpax.sensata.com/ http://airpax.sensata.com/ IAG/IUG/IEG/CEG/LEG Series - Multi-Pole 108
IAG/IUG/IEG/CEG/LEG
Rocker CIRCUIT Protectors Rocker CIRCUIT Protectors
(IAGX/IAGZX/IUGX/IUGZX/IEGX/IEGZX/CEGX/CEGZX/LEGZX) (IAGBX/IUGBX/IEGBX/CEGBX/LEGBX)
The IAGX/IUGX/IEGX/CEGX and IAGZX/IUGZX/IEGZX/CEGZX/ The IAGZX/IUGZX/IEGZX/CEGZX/LEGZX style adds our “EZ” The innovative new design of our IEG BX style circuit breaker Available on a variety of versions with a full range of agency
LEGZX styles offer two attractive rocker actuator versions of our options of contrasting dual color rocker actuators, affording a features a flat front rocker that not only satisfies your aesthetic approvals, the new IEG BX style circuit breakers meet or exceed
popular IAG/IUG/IEG/CEG/LEG family. Designed with the operator clear visual indication of the handle position and integrated needs, it guards against accidental actuation while providing the all current performance specifications, including interrupting
in mind, each features handles with a concave surface and handle guards, to help prevent accidental turn-on and turn-off of highest degree of circuit protection and quality. Only Airpax capacities up to 50,000 amperes. Various guard options offer
aesthetic appearance for front panel applications. the unit. Available with a black rocker and white, red or green offers this new standard in user interface, providing additional additional and increasing levels of actuation protection
indicator color for either ON or OFF indication. peace of mind that guards alone can’t supply. performance. The two shot mold on the flat rocker surface
Both are available with rocker handle styles in a choice of five provides a clean, crisp legend that can withstand demanding
single colors: black, red, grey, orange or white. use.
IAGX/IUGX/IEGX/CEGX IAGBX/IUGBX/IEGBX/CEGBX/LEGBX
Single Pole Two Pole Three Pole Four Pole
6 – 32 THD. (TYP.)
M3 ISO THD.
OPTIONAL 1.515 2.265 3.015
.750 [38.48] [57.53] [76.58]
1.687 [19.05] MAX. MAX. MAX.
[42.85]
(Optional: Handle may be
2.206 located in Pole 2 instead of ON
I
1.220 ON
[30.99]
[56.03] Pole 1) I
2.000 ON
ON ON ON ON O O
[50.80] 1.972 1.660
[50.09] [42.16] OFF OFF
OFF OFF OFF OFF OFF ACTUATION
2.378 MAX .387 REF. ACCESS
HANDLE (SEE NOTE) HANDLE
[60.40] [9.84]
POSITION "OFF" POSITION "ON"
2.470 .490 ±.005 .125 WITH GUARD WITH GUARD
[62.74] [12.45] .735 1.687 [3.18] (SIXTH DECISION, G) (SIXTH DECISION, G)
MAX. MAX. [±.13]
[42.85]
[18.67] Mounting Detail
(HANDLE WIDTH)
Single, Two & Three Pole Four Pole*
2X .156 1.510
[3.96] [38.35]
2.000 ON
1.220
Panel Mounting Detail: Tolerance for Mtg. [50.80] ON I
[30.99] I
1.660 ±.005 [.13] unless noted.
[42.16] 1.530 PUSH PUSH
1.260
*See Single Pole Mounting Detail for hole sizes [38.86] TO TO
RESET RESET
.200 [32.00]
and locations.
[5.08]
HANDLE HANDLE
POSITION "OFF" POSITION "ON"
.750
[19.05]
.750
[19.05]
1.239 GUARD WITH NO ACTUATE GUARD WITH NO ACTUATE
.314 [31.47] OFF FEATURE OFF FEATURE
[7.98] (SIXTH DECISION, X) (SIXTH DECISION, X)
IAGZX/IUGZX/IEGZX/CEGZX/LEGZX
Single Pole* Two Pole* Three Pole Single, Two & Three Pole
2.470 MAX. .420 REF. .750 1.515 2.265 Max. 2X .156 6-32 THD. MOUNTING 2X ÿ .156
[62.74] [10.67] [19.05] [38.48] [57.53] [3.96]
.750 M3 ISO THD. OPTIONAL [3.96]
ON
I
6 – 32 THD. (TYP.) ON
1.687 .125 M3 ISO THD. [19.05] I
[42.85] [3.18] OPTIONAL O
1.660 O
[42.16] OFF
OFF
1.220 1.260
2.000 [30.99] .200 [32.00]
[50.80] [5.08] 1.660 1.260
2.165 ON ON ON [42.16] HANDLE HANDLE
1.530 1.660 [32.00] POSITION "ON"
[38.86] [54.98] POSITION "OFF"
[42.16] ON ON WITHOUT GUARD
WITHOUT GUARD
OPTIONAL OFF OFF OFF .750
I
HANDLE GUARDS OF
[19.05]
2.217 1.660 DETAIL "A"
(SEE DETAIL “A”)
[56.31] [42.16] NOTE: ACCESS IS LIMITED TO A DEVICE SMALLER THAN THE
.430
1.239 Panel Mounting Detail: Tolerance for Mtg. O UNDERWRITERS LABORATORY "ARTICULATED PROBE"
[31.47] OFF DEFINED IN UL-489 FIG. 11.1.7.2.1.
[10.92] ±.005 [.13] unless noted. .200 .750
[5.08] [19.05]
Detail “A”
Note: Tolerance ± .015 [.38] unless noted. Dimensions in brackets [ ] are millimeters.
109 IAG/IUG/IEG/CEG/LEG Series - Rocker http://airpax.sensata.com/ http://airpax.sensata.com/ IAG/IUG/IEG/CEG/LEG Series - Rocker 110
IAG/IUG/IEG/CEG/LEG
SEALED TOGGLE CIRCUIT PROTECTORS SNAP-IN CIRCUIT PROTECTORS
(IAGN/IUGN) (IEGS/IEGHS/CEGS/CEGHS/lEGS/LEGHS)
The IAGN/IUGN family is a sealed toggle version of the IAG/ The Snap-In version of the IEG brings mounting simplification The IEGS is offered in either flush or beveled versions, in 1, 2, 3
IUG family. The silicone rubber seal around the handle and international spacing together in a package that is or 4 pole packages, and with a handle per pole or per unit.
assures panel seal integrity and makes this style a natural aesthetically enhanced. The IEGS securely snaps into a
for harsh environments. rectangular cut-out, eliminating the need for panel mounting The IEGS is UL Recognized, CSA Certified and VDE approved.
hardware and the associated costs. The face plate of the IEGS
This sealed toggle family is available in one to three poles with is a clean, black matte and it satisfies the increasing demand
ratings of .050 to 50 amperes. for front panel components that are designed with ergonomic
considerations.
Single Pole Two Pole Three Pole IEGHS/CEGHS/LEGHS Circuit Protectors (Note B)
(Multi-Pole-IEGH Handles Per Pole)
KEYWAY (Omit H for Single Pole)
.060 [1.52] – .065 [1.65] WIDE
.030 [.76] – .035 [.89] DEEP 2.265
1.515 1.687
[38.48] [57.53] .240 .744 1.488 2.232 2.976
.750 [42.85] [6.09] [37.80] [75.59]
[19.05] MAX. MAX. [18.90] [56.69]
.130 6 – 32 MTG. SCREW
[3.30] FOR HIGH SHOCK ON
ON ON ON ON ON ON ON ON ON ON
MTG. 32º
2.000
LOCKWASHER ±3º 1.220 [50.80]
13º 32º 2.598
[30.99]
ON 1.220 [65.99]
2.000 [30.99] OFF
[50.80]
OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF
.656 2.075 .690
±3º [16.66]
OFF 13º [52.70] [17.53]
MAX.
1/2 – 32 HEX NUT
2.256 (Optional: Handle may be
[57.30] RUBBER “O” RING
located in Pole 2 instead
MAX. .625 .750 of Pole 1) DIM. “B”
[15.88] [19.05] (SEE TABLE)
Note:
Panel Cutout Detail A: Flush face plate is optional. See decision tables, sixth decision.
Panel Thickness: (See Table) B:Tolerance ± .031 [.79] Angles: ±5° unless noted. Dimensions in brackets [ ] are
millimeters.
DIM. “C”
Mounting Detail (SEE TABLE)
Optional Handle Single Pole Two Pole* Three Pole*
.656
[16.66] DIMENSIONS “A”, “B”, “C”
Number of Poles Dimension “A”, inches [ mm ] Dimension “B”, inches [ mm ] Dimension “C”, inches [ mm ]
Panel Mounting Detail: Tolerance for Mtg. ±.005 [.13] unless noted.
*See Single Pole Mounting Detail for hole sizes and locations. 1 pole .750 [19.05] max .755 [19.18] min
2 pole 1.515 [38.48] max 1.520 [38.61] min 2.180 ± .005 2.186 ± .011
Note: Tolerance ± .015 [.38] unless noted. Dimensions in brackets [ ] are millimeters. 3 pole 2.265 [57.53] max 2.270 [57.66] min [55.37 ± .13] [55.52 ± .28]
4 pole 3.015 [76.58] max 3.020 [76.71] min
.040 to .059 .060 to .100
Panel Thickness
[1.02 to 1.50] [1.52 to 2.54]
111 IAG/IUG/IEG/CEG/LEG Series - Sealed Toggle http://airpax.sensata.com/ http://airpax.sensata.com/ IAG/IUG/IEG/CEG/LEG Series - Snap-In 112
IAG/IUG/IEG/CEG/LEG
.230
IEGS/CEGS/LEGS Circuit Protectors (Note B) CONFIGURATIONS .230
[5.84] [5.84]
(Add H for multiple handles per unit, IEGHS)
Series Trip
1.687 .240
[42.85] [6.09] .960 1.700 2.450 3.190 The most popular configuration for magnetic protectors is the
[24.38] [43.18] [62.23] [81.03] series trip where the sensing coil and contacts are in series 1.530 1.530
Series Switch
ON ON ON ON ON ON with the load being protected. The handle position conveniently [38.86] [38.86]
Only
32º indicates circuit status. In addition to providing conventional
2.000 overcurrent protection, it’s simultaneously used as an on-off
[50.80]
32º
2.598
[65.99]
switch.
1.220
[30.99] OFF
OFF OFF OFF OFF OFF Shunt Trip
2.075
The shunt trip is designed for controlling two separate loads with
.690
[52.70] [17.53] one assembly. The control is established by providing overload Optional flat
MAX. protection for the critical load. When the current through this screw terminal 2.52 MAX.
.230 [64.00]
load becomes excessive and reaches the trip point, the protector [5.84] (See Note A)
will open and remove power from both loads simultaneously. The
DIM. “B”
Panel Cutout Detail (SEE TABLE) total current rating of both loads must not exceed the maximum 1.380
Panel Thickness: (See Table) contact rating. [35.05]
1.530 Shunt
Auxiliary Switch (Applies to Series Trip Only) [38.86]
DIM. “C”
(SEE TABLE)
This is furnished as an integral part of a series pole in single or
multi-pole assemblies. Isolated electrically from the protector’s
DIM. “A”
(SEE TABLE) .130 circuit, the switch works in unison with the power contacts
[3.30] and provides indication at a remote location of the protector’s
on-off status.
Auxiliary switch contacts actuate simultaneously with the
main protector contacts, and will open regardless of whether Standard Auxiliary Switch VDE Auxiliary Switch
DIMENSIONS “A”, “B”, “C” the protector contacts are opened manually or electrically. For
auxiliary switch ratings below 6Vac or 5Vdc, an auxiliary .441 .469
[11.20] [11.91]
Number of Poles Dimension “A”, inches [ mm ] Dimension “B”, inches [ mm ] Dimension “C”, inches [ mm ] switch with gold contacts designated as REG is available. Gold
contacts are not recommended for load current above 100
1 pole .750 [19.05] max .780 ± .015 [19.81 ± .381] milliamps.
1.083
[27.51] .848
1.059 .764
[26.90][
[21.53] 19.04]
2 pole 1.515 [38.48] max 1.540 ± .015 [39.12 ± .381] 2.180 ± .005 2.186 ± .011
3 pole 2.265 [57.53] max 2.290 ± .015 [58.17 ± .381] [55.37 ± .13] [55.52 ± .28]
4 pole 3.015 [76.58] max 3.040 ± .015 [77.22 ± .381]
.040 to .059 .060 to .100
Panel Thickness
[1.02 to 1.50] [1.52 to 2.54]
2.438 MAX. 2.454 MAX.
[61.93]
Main Terminal TYPES .110
[2.79] (See Note A) .187 [62.33]
(See Note A)
[4.75]
Optional Handle Guard Amp 8-32 M4 10-32 M5
Push-On .260 .250
.780
[19.82] Rating Screw Screw Screw Screw –IREC4
[6.60] [6.35]
–IREG4 –IREC5
.05 to 30 X X X
30.1 to 50 X X
1.560
[39.62] Series with Auxiliary Switch
NO
Note: NC
A: Terminal protrusion dimensions are referenced from back mounting panel. BREAKER IN
OFF POSITION
.734 B: Main terminals are male push-on type .250 [6.35] wide x 0.31 [.79] thick x .375 [9.53] long or 8-32
[18.64] Note: A: Tolerance ± .015 [.38] unless noted. Dimensions in brackets [ ] are millimeters. x .187 [4.75] screw type. Metric screw terminals are M4 x 5mm (<=30A): M5 x 5mm screw type
B: Bevelled face plate is standard. (>30A). On VDE approved builds with screw terminals, external tooth lockwashers are supplied. On
VDE approved builds with push-on terminals a soldered connection is required above 25 amperes.
113 IAG/IUG/IEG/CEG/LEG Series - Snap-In http://airpax.sensata.com/ http://airpax.sensata.com/ IAG/IUG/IEG/CEG/LEG Series - Configurations 114
IAG/IUG/IEG/CEG/LEG
OPERATING CHARACTERISTICS
Relay Trip TYPICAL RESISTANCE / IMPEDANCE
This permits the overload sensing coil to be placed in a
.230
[5.84]
2.52 MAX.
[64.00] Inrush Pulse Tolerance
(See Note A) Impedance
circuit which is electrically isolated from the trip The following table provides a comparison of inrush
contacts. The coil may be actuated by sensors .620 Current Ratings DC AC, 50/60Hz AC, 400Hz pulse tolerance with and without the inertial delay
monitoring pressure, flow, temperature, speed, etc.
[15.75]
(Amps) (ohms) (ohms) (ohms) feature for each of the 50/60Hz delays. Pulse
Other typical applications include crowbar, interlock 1.380
[35.05] 51, 52, 53, 59 61, 62, 63, 69 41, 42, 43, 49 tolerance is defined as a single pulse of half sine
and emergency /rapid shutdown circuitry. Trip may be 1.530
[38.86]
wave peak current amplitude of 8 milliseconds
accomplished by voltage or current, which must be Relay 0.200 36.6 34.2 74.2 duration that will not trip the circuit breaker. The
removed after trip. 1.00 1.38 1.47 2.85 table at left provides a guide to determine if the
inertia delay feature is required. Consult factory for
2.00 0.31 0.25 0.64
further assistance.
5.00 0.053 0.051 0.100
.230 2.52 MAX. 10.0 0.016 0.013 0.027
[5.84] [64.00]
(See Note A) 20.0 0.006 0.005 0.008
30.0 0.0027 0.0026 0.004 INRUSH PULSE TOLERANCE
1.380
[35.05] 50.0 0.0019 0.0018 — Delay Pulse Tolerance
Dual Coil 1.530 DCR and Impedance based on 100% rated current applied and stabalized for 61, 62, 63, 71, 72, 73 10 times rated current (approx)
[38.86] Dual Coil a minimum of one hour. Tolerance .05-2.5 amperes ± 20%: 2.6 -20 amperes
By combining two electrically independent coils on a 61F, 62F, 63F, 71F, 72F, 73F 12 times rated current (approx)
± 25%, 21-50 amperes ± 50%. Consult factory for special values and for coil
common magnetic circuit, it is possible to provide impedance of delays not shown. 64, 65, 66 25 times rated current (approx)
contact opening when either an over-current or trip
voltage is applied to the respective coils. One coil will
be a current trip coil with standard specifications. The Percentage of Rated Current vs Trip Time in Seconds at +25°C (Vertical Mount)
second, or dual coil, can be used to provide a control
function permitting contact opening from a remote .230 2.52 MAX. Delay 100% 125% 150% 200% 400% 600% 800% 1000%
interlock or other transducer functions. Standard coils [5.84] [64.00]
are 6, 12, 24, 48, 120 and 240 volts. Tripping is
(See Note A) 41 No Trip May Trip .500 to 8.0 .150 to 1.9 .020 to .40 .006 to .25 .004 to .1 .004 to .05
instantaneous and must be removed (usually self- .620 42 No Trip May Trip 5 to 70 2.2 to 25 .40 to 5.0 .012 to 2 .006 to .2 .006 to .15
interrupting) after trip. [15.75]
1.380 43 No Trip May Trip 35 to 350 12 to 120 1.5 to 20 .012 to 2.2 .01 to .22 .01 to .1
[35.05]
1.530
[38.86]
49 No Trip May Trip .100 Max .050 Max .020 Max .020 Max .020 Max .020 Max
Dual Coil
51* No Trip .500 to 6.5 .300 to 3.0 .100 to 1.2 .031 to .500 .011 to .25 .004 to .1 .004 to .08
52* No Trip 2 to 60 1.8 to 30 1 to 10 .15 to 2.0 .04 to 1 .008 to .5 .006 to .1
53* No Trip 80 to 700 40 to 400 15 to 150 2 to 20 .23 to 9 .018 to .55 .012 to .2
59* No Trip .120 Max .050 Max .050 Max .022 Max .017 Max .017 Max .017 Max
61* No Trip .700 to 12 .35 to 7.0 .130 to 3.0 .030 to 1 .015 to .3 .01 to .15 .008 to .1
Voltage Trip Optional Barriers (IEG Only) 62* No Trip 10 to 120 6 to 60 2 to 20 .2 to 3.0 .02 to 2 .015 to .8 .01 to .25
Sometimes called “dump circuits” or “panic trip 63* No Trip 50 to 700 30 to 400 10 to 150 1.5 to 20 .4 to 10 .013 to .85 .013 to .5
circuits,” these units make it possible to open main .571
115 IAG/IUG/IEG/CEG/LEG Series - Configurations http://airpax.sensata.com/ http://airpax.sensata.com/ IAG/IUG/IEG/CEG/LEG Series - Operating Characteristics 116
IAG/IUG/IEG/CEG/LEG
DELAY CURVES (IAG/IUG/IEG/CEG/LEG) DELAY CURVES (IAG/IUG/IEG/CEG)
MAY TRIP
1000 DELAY 61 1000 DELAY 62 1000 DELAY 51 1000 DELAY 53
MAY TRIP
MAY TRIP
MAY TRIP
TIME IN SECONDS
TIME IN SECONDS
TIME IN SECONDS
TIME IN SECONDS
10 10 10 10
1 1 1 1
.1 .1 .1 .1
MAY TRIP
1000 DELAY 63 1000 DELAY 69 1000 DELAY 52 1000 DELAY 59
MAY TRIP
MAY
100 100 100 100
TIME IN SECONDS
TIME IN SECONDS
TIME IN SECONDS
TIME IN SECONDS
10 10 10 10
MAY TRIP
1 1 1 1
.1 .1 .1 .1
117 IAG/IUG/IEG/CEG/LEG Series - Delay Curves http://airpax.sensata.com/ http://airpax.sensata.com/ IAG/IUG/IEG/CEG/LEG Series - Delay Curves 118
IAG/IUG/IEG/CEG/LEG
DELAY CURVES (IAG/IUG/IEG) DELAY CURVES (IAG/IUG/IEG)
Multi-frequency - DC, 50/60Hz Delay Curves (typ) 400Hz Delay Curves (typ)
MAY TRIP
1000 DELAY 71 1000 DELAY 72 1000 DELAY 41 1000 DELAY 43
MAY TRIP
MAY TRIP
MAY TRIP
TIME IN SECONDS
TIME IN SECONDS
10 10 10
1 1
1 .1 .1
01 01 .01 .01
MAY TRIP
100 100 100
TIME IN SECONDS
100
TIME IN SECONDS
TIME IN SECONDS
TIME IN SECONDS
10 10 10 10
MAY TRIP
1 1 1 1
MAY TRIP
1 1 .1 .1
01 01 .01 .01
119 IAG/IUG/IEG/CEG/LEG Series - Delay Curves http://airpax.sensata.com/ http://airpax.sensata.com/ IAG/IUG/IEG/CEG/LEG Series - Delay Curves 120
IAG/IUG/IEG/CEG/LEG
SPECIFICATIONS AGENCY APPROVALS
Trip Free Vibration IAG/IUG/IEG Supplementary Protectors Rated Current (Amps) Short Circuit Rating (SC), Amps
Will trip open on overload, even when forcibly held in the ON position. This pre- Circuit protector shall not trip when vibrated per MIL-STD-202, Method 204, Test Max Voltage Frequency (Hz) Phase Minimum Poles UL/CSA TüV UL1077 & CSA TüV
vents the operator from damaging the circuit by holding on the protector. Condition A with 100% rated current applied to delayed units and 80% rated cur-
80 DC — 1 .02 to 50 .10 to 30 U2, 7500 4000
rent to instantaneous units.
Trip Indication 125 50/60 1 1 .02 to 50 — U2, 3000 —
The operating handle moves positively to the OFF position on overload. VDE Approval 125 50/60 1 1 .02 to 30 — C1, 5000(3) —
IEG is VDE approved under VDE 0642 (EN60934). The IEG has 8mm creepage and
125 50/60 1 1 .02 to 50 — U3, 1000 —
Ambient Operation clearance between the main circuit and the following areas:
IAG/IUG/IEG/CEG/LEG protectors operate in temperatures between –40° C to A. Operator accessible area around the handle. 125 / 250 50/60 1 2 .02 to 50 — U1, 3000 —
+85° C. B. The mounting inserts or brackets. 125 / 250 50/60 1 1 2/1 - 30/15 — C2, 5000(1) —
C. The auxiliary switch circuit. 240 50/60 1&3 1 .02 to 50 — U1, 2000 —
Insulation Resistance D. Between poles.
240 50/60 1&3 1 .02 to 50 — C2, 5000(1) —
Not less than 100 megohms at 500 volts DC.
Care must be taken to maintain spacings at the terminals when wired. The VDE 250 50/60 1 1 .02 to 2 — U2, 5000 —
Dielectric Strength approval for standard terminals is not for use with bare wire. A crimp type lug is 250 50/60 1&3 1 .02 to 30 .10 to 50 U1, 2000 2000
IAG/IUG/IEG/CEG/LEG protectors withstand 3750Vac, 60Hz for 60 seconds required. In addition, all VDE approved units will be in compliance with specific 250 50/60 1&3 1 .02 to 30 — C2, 3500(2) —
between all electrically isolated terminals, except auxiliary switch terminals shall CE Directives. These units will be marked as CE Compliant.
250 (4) 50/60 1&3 1 .02 to 30 — C1, 3500(2) —
withstand 600Vac, 60Hz for REG and REC types. Four terminal dual coil and relay
construction (not offered in the IEG) will withstand 1500Vac. UL1500 (Marine Ignition Protected) 250 (4) 50/60 1&3 1 .02 to 30 — U1, 1000 —
IDG/IDGH is approved for Marine Ignition Protection 250 (5) 50/60 1 2 .02 to 50 — U3, 1000 —
Endurance 250 (5) 50/60 3 3 .02 to 50 — U3, 1000 —
Operating as a switch, the operating life exceeds 10,000 operations at a rate of 6 UL489A Listed
277 50/60 1 1 .02 to 30 — U2, 2000 —
per minute when tested as follows: 6000 OPS @ rated current plus 4000 OPS @ at The CEG is dimensionally the same as the popular IEG, but provides UL listing to
no load. UL489A. Available in one to three poles, in series, series with auxiliary switch, 277 50/60 1 1 .02 to 30 — C2, 5000(2) —
shunt, dual coil and voltage trip configurations. As a circuit breaker, the CEG pro- 250 400 1&3 1 .02 to 30 — U2, 1500 —
Electrical Characteristics vides communication equipment manufacturers with a UL listed circuit breaker in 250 400 3 — .02 to 30 — U3, 200 —
.050-50 amperes; 80Vdc Max., 240Vac Max., 50/60Hz and .050-30 amperes: 250Vac a very compact package that meets the stringent environmental requirements of
Max., 400Hz. Units above 30 amps are not suitable for across-the-line motor today’s marketplace. This makes the CEG ideal for switching, transmission and
IDG Supplementary Protectors
starting. wireless applications.
Max Voltage Frequency (Hz) Phase Minimum Poles UL/CSA TüV UL1077 & CSA TüV
121 IAG/IUG/IEG/CEG/LEG Series - Delay Curves http://airpax.sensata.com/ http://airpax.sensata.com/ IAG/IUG/IEG/CEG/LEG Series - Delay Curves 122
IAG/IUG/IEG/CEG/LEG
ROCKER HANDLE
1 First Decision 5 Fifth Decision 6 Sixth Decision
COLOR INDICATING COLOR
IEGH**
O
LINE O OFF ON
1.00 35.0*
CUGH+ BX BX Rocker w/ integral mounting FIG. 1 FIG. 2 FIG. 3 FIG. 4 FIG. 5 FIG. 6
descriptive drawing exists to provide cross reference, Marked * Not available on snap-in units O ON OFF
ON OFF
LOAD
11 66 Two pole
ON
O
ON
traceability and manufacturing control. 111 666 Three pole Color Unmarked I-O MARKING DETAIL “B” (SEE TABLE)
For example, the following is the code for a single pole, 1 2 3 4 5 7 Orange -60 -61 MOUNTING/INDICATOR CODE: M, N, P, R
LINE
ON
O
LINE
OFF
LOAD
ON
handles and black on white, yellow and orange handles. FIG. 2 FIG. 3 FIG. 6
See alternate 7th decision below for X, ZX & BZ rocker handles.
circuit. It has a short time delay, a rating of 20 amperes, 3 Third Decision 4 Fourth Decision MARKING DETAIL “C” (SEE TABLE)
-1RLS4 Series w/ alarm switch, -62 50/60Hz long delay Grey N/A Black N/A -40 -41 -42 -43 -44 -45 -46 A
Notes: electrical trip, Orange N/A Black N/A -50 -51 -52 -53 -54 -55 -56
-63 50/60Hz motor start
.110 Q.C. terminals (mid-trip only) White N/A Black N/A -90 -91 -92 -93 -94 -95 -96
-64 50/60Hz short delay
A. It is recommended that power leads be soldered to circuit -3 Shunt IAGZX, IUGZX, IEGZX, CUGZX, CEGZX Rocker Handle (Dual Rocker Color)
protectors having push-on type terminals for current trip -65 50/60Hz long delay
Black White White On -A0 -A1 -A2 -A3 -A4 -A5 -A6
-4 Relay
ratings above 20 amperes. -66 50/60Hz motor start
Black Red White On -B0 -B1 -B2 -B3 -B4 -B5 -B6
* Only one auxiliary switch is normally supplied on two or
-69 50/60Hz 125% instant trip
three pole units. Switch is located in the right-hand pole Black Green White On -C0 -C1 -C2 -C3 -C4 -C5 -C6 A
B. When “A” (metric thread mounting) is specified in the sixth (viewed from terminal end) unless otherwise specified.
-71 DC/60Hz short delay Black White White Off -F0 -F1 -F2 -F3 -F4 -F5 -F6
decision in combination with screw terminal option in the -72 DC/60Hz long delay Black Red White Off -G0 -G1 -G2 -G3 -G4 -G5 -G6
second decision, metric screw terminals are supplied. Black Green White Off -H0 -H1 -H2 -H3 -H4 -H5 -H6
-73 DC/60Hz motor start
-79 DC/60 Hz 135% instant trip Black White White On -J0 -J1 -J2 -J3 -J4 -J5 -J6
C. IEG, IEGH, IEGS, IEGHS, IEGX and IEGZX circuit protectors are
designed to meet 8mm creepage and clearance requirements For addition of inertial delay, add an ìFî to any
Black Red White On -K0 -K1 -K2 -K3 -K4 -K5 -K6 B
delay numeral. Black Green White On -L0 -L1 -L2 -L3 -L4 -L5 -L6
for installation Category III, Pollution Degree 3, Case A as * CEG types are only available with DC ratings
IAGBX, IUGBX, IEGBX, CUGBX, CEGBX Rocker Handle (Dual Rocker Color)
measured in IEC 664. Intended for use in equipment designed
Black White White Off -M0 N/A -M2 -M3 N/A -M5 -M6
to comply with IEC 601 and 950 and VDE 0804 C = CCC Approved V = VDE and CCC Approved Black Red Red Off -N0 N/A -N2 -N3 N/A -N5 -N6
and 0805. C
The shaded areas denote VDE and CCC (if applicable) approval Black Green Green Off -P0 N/A -P2 -P3 N/A -P5 -P6
This approval requires the addition of a C at the end options. This approval requires the addition of a V at the end of the Black Yellow Yellow Off -R0 N/A -R2 -R3 N/A -R5 -R6
of the part number. The unit will not be VDE Approved. part number. The V will be added to any part number formed entirely
from shaded decisions. If non-shaded areas are selected, the unit will Notes: A. Bezels of IAGBX, IUGBX, IEGBX, CUGBX, CEGBX are black.
not be VDE or CCC Approved, but other approvals still apply. B. Consult factory for other marking options.
123 IAG/IUG/IEG/CEG Series - Decision Tables http://airpax.sensata.com/ http://airpax.sensata.com/ IAG/IUG/IEG/CEG Series - Decision Tables 124
IAG/IUG/IEG/CEG/LEG
ROCKER HANDLE
5 Fifth Decision 6 Sixth Decision
COLOR INDICATING COLOR
ON
First Decision
LEG DECISION TABLES OFF ROCKER HANDLE
COLOR
Select Type and Terminal Use three numbers to print required current value Standard hardware. No designation required. OFF
ZX ZX Rocker w/ integral mounting* -S Face plate sides flush with breaker LINE OFF O OFF
O OFF ON
O OFF
O ON
The coding given permits a self-assigning part number Note: All types are UL489 listed, CUL certified Note: Add "F" for flat screw terminals
-X* Handle guard with no actuation feature
(BX rocker only)
MARKING DETAIL “A” (SEE TABLE)
but with certain limitations. Special applications may * Not available on mid-trip units
-Z "Z" Barriers
require a factory-assigned part number. Typical examples
INDICATING COLOR
Notes: OFF
are units with mixed ratings, combinations of styles, or 1. One or more descriptions may be used as required.
2. When this is not used, table one may be substituted and U.S. thread LINE
constructions not listed in the third decision table. With will be supplied. Unit will be rated at 250V (50/60Hz only.) ON ROCKER HANDLE
COLOR
3. LEGS standard face plate has beveled sides(see pg. 90)
* Not available on mid-trip units
these, it is suggested that order entry be by description 2 Second Decision 7 Seventh Decision
and/or drawings and a part number will be established.
INDICATION “ON”
MOUNTING/INDICATOR CODE:
J, K, L
Poles and Terminals Handle Color and Marking Selection
Additionally, it is standard policy to establish a factory- Push-on Screw Toggle Handle
assigned part number whenever a descriptive drawing Terminals Terminals LINE OFF
O OFF
LOAD LINE LOAD LINE LOAD LINE
O
Marked
O ON OFF
ON OFF
LOAD
1 6 Single pole
ON
O
When specifying a circuit breaker for AC motor start Yellow -10 -11
or high inrush applications, the peak amplitude and surge Red -20 -21 ON
I
duration should be specified for factory assistance in Example: Blue -30 -31 LINE
O
OFF
O
LINE LOAD
handles and black on white, yellow and orange handles. FIG. 2 FIG. 3 FIG. 6
To determine the ordering number for your particular LEG -1 Series -61 50/60Hz short delay
unit, simply follow the steps shown. You may use this -1REC4 Series w/ auxiliary switch *
.110 quick connect
-62 50/60Hz long delay 7 Seventh Decision
number to place an order or as a reference for further -63 50/60Hz motor start Rocker Handle Color, Indicator Color and Marking Selection (See Note)
-1REC5 Series w/ auxiliary switch *
questions you may have. .187 quick connect
-69 50/60Hz 125% instant trip
LEGZX Rocker Handle (Single Rocker Color)
For addition of inertial delay, add an “F” to any
delay numeral.
Vertical Mounting Horizontal Mounting
-1REG4 Series w/ auxiliary switch*
* CEG types are only available with DC ratings
(gold contacts) Rocker On-Off On-Off
.110 quick connect Handle Indicating Marking On-Off I-O I-O On-Off I-O I-O Marking
Color Color Color Indicates: Unmarked Fig.1 Fig.2 Fig.3 Fig.4 Fig.5 Fig.6 Detail
-1RS4 Series w/ alarm switch*,
electrical trip, Black N/A White N/A -00 -01 -02 -03 -04 -05 -06
.110 Q.C. terminals V = VDE Approved
Red N/A White N/A -20 -21 -22 -23 -24 -25 -26
-1RLS4 Series w/ alarm switch*, The shaded areas denote VDE Approval options. Grey N/A Black N/A -40 -41 -42 -43 -44 -45 -46 A
electrical trip, mid-trip only, This approval requires the addition of a V at the end of
the part number. The V will be added to any part number
Orange N/A Black N/A -50 -51 -52 -53 -54 -55 -56
.110 Q.C. terminals
formed entirely from shaded decisions. White N/A Black N/A -90 -91 -92 -93 -94 -95 -96
If non-shaded areas are selected, the unit will
-3 Shunt not be VDE Approved, but other LEGZX Rocker Handle (Dual Rocker Color)
approvals still apply.
* Only one auxiliary switch is normally supplied on two pole Black White White On -A0 -A1 -A2 -A3 -A4 -A5 -A6
units. Switch is located in the right-hand pole (viewed from
terminal end) unless otherwise specified. Black Red White On -B0 -B1 -B2 -B3 -B4 -B5 -B6
Black Green White On -C0 -C1 -C2 -C3 -C4 -C5 -C6 A
Black White White Off -F0 -F1 -F2 -F3 -F4 -F5 -F6
C = CCC Approved Black Red White Off -G0 -G1 -G2 -G3 -G4 -G5 -G6
Black Green White Off -H0 -H1 -H2 -H3 -H4 -H5 -H6
This approval requires the addition of a C at the end
of the part number. The unit will not be VDE Approved. Black White White On -J0 -J1 -J2 -J3 -J4 -J5 -J6
Notes: Black Red White On -K0 -K1 -K2 -K3 -K4 -K5 -K6 B
A. When “A” (metric thread mounting) is specified in the sixth decision in Black Green White On -L0 -L1 -L2 -L3 -L4 -L5 -L6
combination with screw terminal option in the second decision, metric LEGBX Rocker Handle (Dual Rocker Color)
screw terminals are supplied.
Black White White Off -M0 N/A -M2 -M3 N/A N/A -M6
Black Red Red Off -N0 N/A -N2 -N3 N/A N/A -N6
B.
LEG, LEGH, LEGS, LEGHS, LEGZX and LEGBX circuit breakers are C
designed to meet 8mm creepage and clearance requirements for instal- Black Green Green Off -P0 N/A -P2 -P3 N/A N/A -P6
lation Category III, Pollution Degree 3, Case A as measured in IEC 664. Black Yellow Yellow Off -R0 N/A -R2 -R3 N/A N/A -R6
Intended for use in equipment designed to comply with IEC 601 and 950 Notes:A. Bezels of LEGBX are black.
B. Consult factory for other marking options.
and VDE 0804 and 0805.
125 LEG Series - Decision Tables http://airpax.sensata.com/ http://airpax.sensata.com/ LEG Series - Decision Tables 126
This document is generated from the AIRPAX™ full-line catalog #2455005000 printed in USA, January 2011
BUSINESS CENTERS
Sensata Technologies Sensata Technologies Holland B.V. Sensata Technologies Japan Ltd.
807 Woods Road Kolthofsingel 8 305, Tanagashira
Cambridge, MD 21613, USA 7602 EM Almelo, The Netherslands Oyama-cho, Sunto-gun, Shizuoka-ken
Phone: +1 410-228-1500 Phone: +31 546 87 95 55 Japan, 410-1396
Brands: Airpax™ Brands: Klixon™, Sensata Technologies™ Phone: +81 550 78 1211
Brands: Klixon™, Sensata Technologies™
Sensata Technologies Inc. Sensata Technologies China Co., Ltd.
529 Pleasant Street Novel Plaza, 8th Floor Sensata Technologies Nihon-Airpax
Attleboro, MA 02703, USA 128 Nanjing Road West 6-3, Chi Yoda 5 Chome
Phone: +1 508-236-3287 Shaghai, 20003 Saitama-Ken
Brands: Klixon™, Sensata Technologies™ People’s Republic of China Japan, 350-0214
Phone: +86 21 23061500 Phone: +81 492 83 7575
Sensata Technologies Brands: Klixon™, Sensata Technologies™ Brands: Airpax™
4467 White Bear Lake Parkway
St. Paul, MN 55110, USA Sensata Technologies Korea Ltd.
Phone: +1 800-553-6418 29F, Trade Tower
Brands: Dimensions™ 159-1 SamSung-Dong, KangNam-Ku, Seoul
135-729, Korea
Phone: +81-2-551-2918
Brands: Klixon™, Sensata Technologies™
Important Notice: Sensata Technologies (Sensata) reserves the right to make changes to or discontinue any
product or service identified in this publication without notice. Sensata advises its customers to obtain the
latest version of the relevant information to verify, before placing any orders, that the information being
relied upon is current. Sensata assumes no responsibility for infringement of patents or rights of others
based on Sensata applications assistance or product specifications since Sensata does not possess full
access concerning the use or application of customers’ products. Sensata also assumes no responsibility for
customers’ product designs.
http://airpax.sensata.com/