Passive Components for RS-485 Networks

4.3.1 Area of Application and Technical Specifications of the Bus


Connector

Uses
You require bus connectors to attach the PROFIBUS LAN cable to 9-pin sub-D
interfaces. There are various bus connectors with the degree of protection IP 20
and the situations in which they are used are listed in Table 4-6.

Table 4-6 Design and Applications of the IP 20-compliant Bus Connectors

Order 6ES7 972-0BA11-0XA0 6ES7 972-0BA40-0XA0 6ES7 6GK1


numbers: 6ES7 972-0BB11-0XA0 6ES7 972-0BB40-0XA0 0BA30-0XA0 500-0EA02
Appearance:
SIEMENS

35_ cable outlet 30_ cable outlet


Recommended
for:
S IM 308-B ~ (version 6 or higher) ~ ~
S IM 308-C ~ ~ ~
S S5-95U ~ ~
Use in PLC with
integrated
interface:
S S7-300 ~ ~ ~
S S7-400 ~ ~ ~
S M7-300 ~ ~ ~
S M7-400 ~ ~
Use in PLC with
S IM 308 C ~ ~ ~
S CP 5431 ~ ~ ~
FMS/DP
S CP 342-5 ~ ~ ~
S CP 343-5 ~ ~ ~
S CP 443-5 ~ ~ ~
Use in PG with
MPI interface ~
Use in PG with
S CP5412(A2) ~
S CP 5411 ~
S CP 5511 ~
S CP 5611 ~
S CP 5613/14 ~

PROFIBUS Networks SIMATIC NET


6GK1970-5CA20-0AA1 Release 2 05/2000 4-33
Passive Components for RS-485 Networks

Table 4-6 Design and Applications of the IP 20-compliant Bus Connectors, continued

Order 6ES7 972-0BA11-0XA0 6ES7 972-0BA40-0XA0 6ES7 6GK1


numbers: 6ES7 972-0BB11-0XA0 6ES7 972-0BB40-0XA0 0BA30-0XA0 500-0EA02
S ET 200B ~ ~ ~
S ET 200L ~ ~ ~
S ET 200M ~ ~ ~
S ET 200S ~ ~ ~
S ET 200U ~ ~ ~
S PG ~ ~ ~
720/720C
S PG 730 ~ ~ ~
S PG 740 ~ ~ ~
S PG 750 ~ ~ ~
S PG 760 ~ ~ ~ ~
S Repeater ~ ~ ~ ~
S OP ~
S OLM ~ ~ ~ ~

Use in
SINUMERIK
840 C and 805
SM
S IM 328N ~ ~
S IM 329N ~ ~
Use in NC 840
D and FM NC
SIMODRIVE
611 MCU
S CP 342-5 ~ ~

Use in TI 505
S TI 505 FIM ~
S TI 505
PROFIBUS
DP ~ ~
S RBC

PROFIBUS Networks SIMATIC NET


4-34 6GK1970-5CA20-0AA1 Release 2 05/2000
Passive Components for RS-485 Networks

Technical Specifications
The following table shows the technical data of the various bus connectors:

Table 4-7 Technical Specifications of the IP 20-compliant Bus Connectors

Order numbers: 6ES7 972- 6ES7 972- 6ES7 972- 6GK1 500-
... 0BA11-0XA0 ... 0BA40-0XA0 0BA30-0XA0 0EA02
... 0BB11-0XA0 ... 0BB40-0XA0
PG socket 0BA11: no 0BA40: no no no
0BB11: yes 0BB40: yes
Max. transmission 12 Mbps 12 Mbps 1.5 Mbps 12 Mbps
rate
Terminating resistor integrated integrated no integrated
and disconnect
function
Cable outlet vertical oblique 35_ oblique 30_ axial
Interfaces
S to PROFIBUS 9-pin sub-D male 9-pin sub-D male 9-pin sub-D male 9-pin sub-D male
node connector connector connector connector
S to PROFIBUS 4 modular 4 modular 4 insulation 4 modular
LAN cable terminals for wires terminals for wires displacement terminals for wires
up to 1.5 mm2 up to 1.5 mm2 terminals for wires up to 1.5 mm2
0.644 " 0.04 mm
Connectable 8 " 0.5 mm 8 " 0.5 mm 8 " 0.5 mm 8 " 0.5 mm
PROFIBUS cable
diameter
Power supply (must 4.75 to 5.25 V DC 4.75 to 5.25 V DC --- 4.75 to 5.25 V DC
be supplied by DTE)
Current consumption max. 5 mA max. 5 mA --- max. 5 mA
Permitted ambient
conditions
S Operating 0 _C to +60 _C 0 _C to +60 _C 0 _C to +60 _C 0 _C to +55 _C
temperature -25 _C to +80 _C -25 _C to +80 _C -25 _C to +80 _C -25 _C to +70 _C
S Transport/storage
temperature max. 75 % at max. 75 % at max. 75 % at max. 95 % at
S Relative humidity +25 _C +25 _C +25 _C +25 _C
Dimensions (in mm) 15.8 54 34 16 54 38 15 58 34 15 39 57
Weight approx. 40 g approx. 40 g approx. 30 g approx. 100 g

Disconnect Function
The disconnect function means that the remaining LAN cable is disconnected from
the bus when the terminating resistor is activated. If the terminating resistor is
accidentally activated in the middle of the LAN cable, the error can be recognized
and localized immediately due to the nodes that are no longer accessible.

PROFIBUS Networks SIMATIC NET


6GK1970-5CA20-0AA1 Release 2 05/2000 4-35