SPECIFICATION FOR TRANSFORMER
8. ACCESSORIES : The transformer will be furnished with all necessary accessories as follow :
To. Date 12 MARCH 2018
Spec No. GENERAL ACCESSORIES SPECIAL ACCESSORIES
√ HV Porcelain Bushing on Side Wall - Plug in Bushing mm2 c/w straight connector on cover
1. TYPE ONAN/ONAF : Oil immersed self cooled / in / out door use / step-up / step-down / hermetically sealed with N2 cushioned √ LV Porcelain Bushing on Side Wall
distribution transformer - Oil Level Indicator w/o Contact - Integrated Safety Device c/w Contact
- Thermometer w/o Contact √ Magnetic Oil Level Gauge c/w Alarm Contact
2. SERVICE CONDITION : The transformer will be installed at the altitudes below 1.000 meters and the maximum √ Manual Off-Load Tap Changer √ Dial Thermometer c/w Alarm & Trip Contact
o
ambient temperature does not exceed 40 C √ Name Plate - Buchholz Relay c/w Alarm & Trip Contact
√ Earth Terminal - Conservator c/w Sampling Valve
3. STANDARD : The transformer is designed, manufactured and tested in accordance with : √ Radiator Panel - Breather c/w Silicagel
SPLN 50 / 97 / SLI 1985 / ANSI C.57.12 √ Drain Valve - Air-filled LV Junction Box
- Sampling Valve √ HV/LV Cable Box
4. RATING √ Lifting lug √ N2 Filling Valve
4-1 Number of Phase : 3 phase 4-2 Frequency : 50 Hz √ Jacking Lug √ Pressure Vacuum Gauge c/w Bleeder
4-3 Primary Voltage : 3,45 kV 4-4 Secondary Voltage : 400 Volt - Roller - Pressure Relief Valve w/o Contact
Winding Connection : DELTA Winding Connection : WYE - Square Hole √ Pressure Relief Device c/w Alarm Contact
4-5 Rated Capacity (total) : 1000/1120 kVA √ Skid Base (Pad Mounted) √ Radiator Fans (increase capacity)
Incase of double primary voltage, Capacity will be : - Hanger ( Pole Mounted ) - Radiator Valves
at : - kV Rated Capacity : - kVA √ Oil Filter Valve √ Terminal Control Box
at : - kV Rated Capacity : - kVA - Voltage Change Over Board - Neutral CT
Incase of double secondary voltage, Capacity will be : - Thermometer Pocket
at : - V Rated Capacity : - kVA √ Winding Thermometer c/w Alarm & Trip Contact
at : - V Rated Capacity : - kVA √ CT for Winding Thermometer
4-6 Additional Taps on High Voltage : +/- 2.5 % & +/- 5 % ( 5 Taps ) - Sudden Pressure Rise Relay + Seal in Relay c/w Alarm & Trip Contact
9. ADDITIONAL INFO : - Ladder
5. POLARITY AND PHASOR RELATIONSHIP : The transformer will be subtractive polarity for single phase and
phasor relationship for three will be Dyn-1 DESCRIPTION

6. ELECTRIC PERFORMANCE :
Primary Voltage Secondary Voltage
6-1 Insulation Class : 5 kV 1,2 kV
6-2 Basic Impulse Level : 75 kV 45 kV
6-3 Applied Voltage Test During 1 Minute : 19 kV 10 kV
6-4 Induced Voltage Test : Apply 2 times of the rate voltage at 350 cycles per second for 18 second
o
6-5 Temperature Rise : The coil temperature rise measured by resistance method will not exceed 65 C
o
and the oil temperature rise will not exceed 55 C
6-6 Losses at Rated Voltage 3,45 / 0,4 kV
No Load Losses : 1.950 Watt Note : - Nuts, Bolts and Washers Stainless Steel
Load Losses ( at 85 °C ) : 12.000 Watt
Total Losses : 13.950 Watt
6-7 Efficiency at % Rated Capacity : 100 75 50 25 %
at P.F. = 1,0 : 98,62 98,85 99,02 98,93 %
6-8 Exciting Current / Off load Current at Nominal Voltage : 2,00 % Date of Approval :
6-9 Percent Impedance : 5,00 % PROPOSER :
6 - 10 Voltage Regulation at P.F. = 1,0 : 1,32 %
Voltage Regulation at P.F. = 0.8 : 3,92 % hp

P180265 - Af