You are on page 1of 10

Journal of International Council on Electrical Engineering

ISSN: (Print) 2234-8972 (Online) Journal homepage: http://www.tandfonline.com/loi/tjee20

Optimal neutral ground resistor rating of the


medium voltage systems in power generating
stations

Choong-Koo Chang

To cite this article: Choong-Koo Chang (2015) Optimal neutral ground resistor rating of the
medium voltage systems in power generating stations, Journal of International Council on Electrical
Engineering, 5:1, 55-63, DOI: 10.1080/22348972.2015.1110878

To link to this article: https://doi.org/10.1080/22348972.2015.1110878

© 2015 The Author(s). Published by Taylor &


Francis

Published online: 20 Nov 2015.

Submit your article to this journal

Article views: 7423

View Crossmark data

Full Terms & Conditions of access and use can be found at


http://www.tandfonline.com/action/journalInformation?journalCode=tjee20
Journal of International Council on Electrical Engineering, 2015
Vol. 5, No. 1, 55–63, http://dx.doi.org/10.1080/22348972.2015.1110878

Optimal neutral ground resistor rating of the medium voltage systems in power generating
stations
Choong-Koo Chang*
Professor, Department of Nuclear Power Plant Engineering, KEPCO International Nuclear Graduate School
(Received 25 August 2015; accepted 19 October 2015)

Neutral grounding resistors (NGRs) are used to protect insulation breakdown in faulty electrical equipment. These faults
are caused by transient over-voltages produced by arcing ground on ungrounded systems. NGR also reduces mechanical
stresses in circuits and apparatus carrying fault currents in solidly grounded systems. In the medium voltage auxiliary
power systems of power generating stations, low resistance grounding system is widely used with a NGR. The purpose
of this paper is to present the method determining optimal NGR size for the medium voltage systems in power
generating stations.
Keywords: system grounding; impedance grounding; neutral grounding resistor; phase to ground fault

1. Introduction In general, system grounding is practiced based on


To determine optimal neutral grounding resistor (NGR) past experience or an extension to the grounding methods
size, many items should be considered. The maximum in existing installations. There are three types in system
ground fault current allowed by the resistor has to be grounding: (1) ungrounded, (2) resistance or impedance,
large enough to actuate the applied ground fault protec- and (3) effective or solid grounding. Each has its applica-
tion relay. The allowable fault current must be decided tion in practice, along with advantages and disadvantages.
in accordance with the protection scheme and nominal The recommendations are based on general practices and
current of equipment (generator or transformer). How- some personal preferences. [1]
ever, the most of literatures related to resistance ground-
ing system design describe only the approximate range
2.1. Ungrounded systems
of the NGR rating for low and high resistance grounding
system. And the only existing standard specific for NGR An ungrounded system is one in which there is no inten-
is the IEEE – 32 standards – where the allowed tempera- tional connection between the conductors and the
ture rise and time rating are defined. Sophisticated NGR ground. However, in any system, a capacitive coupling
sizing and verification method is not introduced in any exists between the system conductors and the adjacent
literature. Therefore, design, construction and operation grounded surfaces. Consequently, the ‘ungrounded sys-
engineers in the job field experience difficulties due to tem’ is, in reality, a ‘capacitively grounded system’ by
the mismatch of NGR rating and ground protection sys- virtue of the distributed capacitance. This is shown in
tem during commissioning and operation. Throughout Figure 1.[2,3]
this study a procedure for the determination of optimal The voltages and impedances indicated in Figure 2
NGR will be proposed, and it will be verified through a are as follows:
case study.
VPN: the applied phase to neutral system voltage (infinite
source)
2. System grounding Z1(sys), Z2(sys), Z0(sys): the equivalent positive, negative,
Power system grounding is very important, particularly and zero sequence source impedance values, respectively
because the majority of faults involve grounding. Thus, ZTX: the transformer impedance (since the return path for
it has a significant effect on the protection of all the the transformer has negligible impedance, the positive,
components of the power system. The principal pur- negative, and zero sequence impedance values, for the
pose of grounding is to minimize potential transient transformer are all the same)
overvoltages to comply with local, state, and national Z1(line), Z2(line), Z0(line): the impedance values for the line
codes for personnel safety requirements; and to assist between the transformer secondary terminals and the PG
in the rapid detection and isolation of trouble or fault (phase to ground) fault.
areas.

*Email: ckchang@kings.ac.kr

© 2015 The Author(s). Published by Taylor & Francis.


This is an Open Access article distributed under the terms of the Creative Commons Attribution License (http://creativecommons.org/licenses/by/4.0/), which permits
unrestricted use, distribution, and reproduction in any medium, provided the original work is properly cited.
56 C.-K. Chang

2.2. Solidly grounded systems


There is no intentional impedance between the system
neutral and ground as shown in Figure 3.
The voltage and impedance values indicated in
Figure 4 are the same as those defined originally for
Figure 2. In terms of the applied voltage and the system
impedance values given, the bolted PG fault current
magnitude would be determined as follows:
Figure 1. Ungrounded system. 3VPN
IPG ¼ (3)
½2Z1ðsysÞ þ 3ZTX þ 2Z1ðlineÞ þ Z0ðlineÞ

2.3. Resistance grounding


There are two broad categories of resistance grounding:
low resistance and high resistance. In both types of
grounding, the resistor is connected between the neutral
of the transformer secondary as shown in Figure 5 or the
generator winding and the earth ground.
The voltage and impedance values indicated in the
resistance grounding system are the same as those
defined originally for ungrounded system except neutral
ground impedance RN inserted between transformer neu-
tral and ground.
In terms of the applied voltage and the system
impedance values given, the bolted PG fault current
magnitude would be determined as follows:
3VPN
IPG ¼ (4)
½2Z1ðsysÞ þ 3ZTX þ 3ZN þ 2Z1ðlineÞ þ Z0ðlineÞ
In general, other impedances than the neutral impe-
dance are negligible. Since the neutral impedance is in a
Figure 2. Sequence network model for phase to ground fault residual portion of the zero sequence current circulation
on an ungrounded system. path, its impedance value is modelled as three times its
actual value and XC0 is negligible in low resistance
grounding system. For this reason, the PG fault current
The equal positive and negative sequence components magnitude is determined by the neutral impedance value
of the total distributed shunt capacitive reactance (XC1 used:
and XC2), shown in Figure 2, are so large compared
3VPN VPN VPN
to the system impedances parallel to them that they IPG ¼ ¼ ffi (5)
can be neglected.[2] In terms of the applied voltage 3ZN ZN RN
and the system impedance values given, the bolted PG
fault current magnitude would be determined as
follows:
3VPN
IPG ¼ (1)
½2Z1ðsysÞ þ 2ZTX þ 2Z1ðlineÞ þ Z0ðlineÞ þ XC0 
Because XC0 dwarfs the other system impedance
values, the simplified Equation 1 gives a close approxi-
mation:
3VPN
IPG ¼ (2)
XC0
As a result, the PG fault current on an ungrounded
system has a very small magnitude, very small for
overcurrent relaying to be used for detecting ground
faults. Figure 3. Delta/grounded-wye transformer connection.
Journal of International Council on Electrical Engineering 57

• To reduce the arc blaster flash hazard to personnel


who may have accidentally caused or who happen
to be in close proximity to the ground fault.

High resistance grounding typically uses ground fault


current levels of 10 A or less, although some specialized
systems in the 15 kV voltage class may have higher
ground fault current levels. On the other hand, low resis-
tance grounding typically uses ground fault current levels
of at least 100 A, with currents in the 400–2000 A range
being more usual.[4,5]

3. System grounding practice in a nuclear power


generating stations
The following is a brief description of the system
grounding practice in nuclear power generating stations
and Figure 6 shows the conceptual diagram of the sys-
tem grounding.

Figure 4. Sequence network model for a bolted PG fault on 3.1. Main generator and transformer
the solidly grounded system. The main generator should always be high resistance
grounded and the main transformer for the generating
plant should always be solidly grounded at the high side.
Low side connected to the generator is always delta con-
nected. No special equipment is required for high side
grounding.[6]

3.2. Unit auxiliary transformers


Unit auxiliary transformers (UAT) connected to the
generator leads should always have the high side delta
connected. Low side of the UAT is generally wye con-
nection and should be low resistance grounded allowing
a maximum of 2000 A ground fault current. Grounding
resistor directly connected to the neutral should have a
minimum of 10 sec rating.

3.3. Standby auxiliary transformers


Standby auxiliary transformers (SAT), when used, may
Figure 5. Resistance grounded system. have wye connection for high and low side winding with
delta connection tertiary winding. For high side, wye
connection, neutral should be solidly grounded. For low
The reasons for limiting the current by resistance side wye connection, neutral should be low resistance
grounding may be one or more of the following: grounded allowing a maximum of 2000 A ground fault
current to flow. Rating of this equipment should have a
• To reduce the burning and melting effects in minimum of 10 sec rating.
faulted electric equipment, such as switchgear,
transformers, cables, and rotating machines.
• To reduce mechanical stresses in circuits and appa- 3.4. Load centre transformers
ratus carrying fault currents.
Transformer feeding low voltage load centre should be
• To reduce electric-shock hazards to personnel
delta/wye connection with neutral solidly grounded,
caused by stray ground-fault currents in the ground
unless specifically required by the client to be different.
return path.
58 C.-K. Chang

Figure 6. System grounding of a nuclear power generating station.

3.5. Diesel generators • Transient overvoltage and insulation level of


Diesel generators, when provided, should be low resis- equipment
tance grounded at the medium voltage and solidly • Fault current withstand time and temperature rise
grounded at low voltage distribution. Low resistance • Ground fault protection and coordination.
grounding should allow a maximum of 1000 A ground
fault current. Grounding resistor directly connected to 4.1. Charging current and fault current level
the neutral should have a minimum of 10 sec rating.
The charging current of a system can be calculated by
summing the zero-sequence capacitance or determining
4. Determination of NGR rating for medium voltage capacitive reactance of all the cable and equipment con-
network nected to the system. The system charging current in
normal operation condition is as follows, where C0 is the
For the purpose of this study, a design and verification
zero-sequence capacitance in μf (microfarad) per phase
process of Figure 7 has been developed. Every factor
and kV is the line-to-line voltage (see Figure 8):
affecting the rating of NGR are reviewed and cross
checked in the process to confirm the suitability of NGR 6
• Capacitive reactance, XCO ¼ xC
10
Ohm per phase,
rating. In the last, the NGR ratting is verified through o

the ground fault protection relay coordination check.


where
The line-to-ground capacitance associated with sys-
tem components determines the magnitudes of zero x¼2pf (6)
sequence charging current. The resistor must be sized to
ensure that the ground fault current limit is greater than
• Charging current in Amps at 60 Hz:
the system’s total capacitance-to-ground charging current.
If not, then transient overvoltages can occur.[3] Further- p
more, NGR selection is a comprehensive task which x  C0  kV  3
3ICO ¼ ¼ 0:652  C0  kV (7)
involves many aspects of power system as shown in 1000
Figure 7. The following items are mainly considered Typical values of system-capacitance data are avail-
when selecting NGRs:[7,8] able from the cable manufacturer catalogue or Westing-
house design guide [9] and the GE Data Book.[10]
• Charging current On the other hand, it is preferable to measure the
• Allowable maximum fault current for network magnitude of the charging current on existing power
Journal of International Council on Electrical Engineering 59

Figure 8. Ground fault current path in resistance grounding


systems.

systems. High resistance grounding systems are designed


to meet the criterion of Rg ≤ Xco/3 or RO ≤ XCO to limit
the transient overvoltages due to arcing ground faults.
Where, Rg is the grounding resistance as seen from the
system being grounded and R0 is the per-phase
zero-sequence resistance of the system. Xco is the capac-
itive reactance-to-ground per phase and includes the
capacitance of all cables, motor windings, transformer
windings, surge or shunt capacitors, and other equipment
connected to the system.[5,11] Total fault current is the
vector sum of capacitive charging current and resistor
current:
p
If ¼ fI 2R þ ð3IC0 Þ2 g (8)
So, if IR = 3IC0, then IF = 1.414 IR
Total fault current must not exceed the value for
which the system is braced. However, in many cases, the
system is already braced for the three-phase fault current
which is much higher than the single line-ground fault
current of a resistance grounded system.[12]
In low resistance grounding, ground fault detecting
current relays are sometimes connected in the common
Figure 7. Flow diagram of NGR determination and ground or residual circuit of current transformers. Where selec-
fault relay setting. tive tripping is to be accomplished, the fault current is
typically limited to a value equal to the primary current
systems for correct grounding equipment selection. The rating of the largest current transformers. This practice
measured values must be adjusted to obtain the maxi- usually results in the maximum ground fault current
mum current if all the system components were not in being approximately equal to the full load rated current
operation during the tests.[3] For safe measuring of of the power supply transformer. Justification for this is
neutral point capacitor current, measurement from the based on the 5 A secondary rating of the current trans-
secondary side of grid is proposed. Also different fre- formers. With an overcurrent relay having a minimum
quency injection method is widely used for the measure- available setting of 0.5 A, the grounding resistance
ment of capacitive current.[8] selected would permit 10 times the relay pickup current
In a resistance grounded system, the resistance must during a zero impedance fault. This will assure reliable
be low enough to allow the system capacitance to dis- relay performance.[11] Typical current values used range
charge relatively quickly. The level of fault current is from 400 A on modern systems using sensitive toroid or
commonly thought to be 10 A or less in ungrounded core balance current transformer ground sensor relaying
60 C.-K. Chang

and up to perhaps 2000 A in the larger systems using try to shift to +1 pu, in succession another time over-
residually connected ground overcurrent relays.[4] shoot, this time to a potential maximum of +5 pu. This
could continue to −7 pu, meanwhile, the system insula-
tion would no doubt break down, causing a major fault.
4.2. Transient overvoltage and insulation level Thus, ungrounded systems should be used with caution,
An ungrounded system with no intentional conductive and applied at the lower voltages, where the system insu-
path to ground has a path for alternating currents to flow lation levels are higher.[1]
between the phase conductors and ground through the For resistance grounding systems at 15 kV and
distributed capacitance to ground of circuits and equip- below, such overvoltages will not ordinarily be of a
ment windings and any surge capacitors or power factor serious nature if the resistance value lies within the
correction capacitors connected to ground. This capaci- following boundary limits: R0 ≤ XC0, R0 ≥ 2X0. Where,
tance is a significant factor in the generation of transient X0 is zero-sequence reactance. The corresponding
overvoltage during an arcing ground fault. ground-fault current is far less than is normally used for
Restriking arcs after current interruption in the low-resistance grounding, but is the design criterion for
breaker or in the fault can result in large destructive high-resistance grounding.[5]
overvoltages in ungrounded systems. This phenomenon
is illustrated in Figure 9.
In the capacitive system, the current leads the voltage 4.3. Fault withstand time and temperature rise
by nearly 90°. When the current is interrupted or the arc Normally, protective relaying will trip within a few
is extinguished at or near its zero value, the voltage will cycles. IEEE 32 defines standard resistor on times. Low-
be at or near its maximum value. With the breaker open, est rate is 10 seconds, but could potentially go less in
this voltage remains on the capacitor to decay at a time order to save material/space. It can go as high as 30 or
constant of the capacitive system. In the source system, 60 seconds as required (rare). Extended or continuous
it continues as demonstrated by VS. Thus, in a half cycle, ratings are almost never used in this application due to
the voltage across the open contact is almost twice the the relatively high fault currents. Coefficient of resistivity
normal peak value. If a restrike occurs (switch closed in typically increases with temperature of the material, thus
Figure 9), the basic +1 pu voltage of the capacitive sys- resistance of the NGR increases while the unit runs. As
tem will shift to the system voltage of −1 pu, but resistance increases, current decreases.[12] Therefore, the
because of the system inductance and inertia, it will time rating and resistivity coefficient of resistor should
overshoot to a maximum possibility of −3 pu. If the arc be confirmed when make a ground fault relay setting
goes out again near current zero (switch open) but calculation.
restrikes (switch closed) again, the system voltage will

Figure 10. Ground fault protection scheme of the class 1E


Figure 9. Transient overvoltage on an ungrounded system. MV switchgear fed from unit aux. transformer.
Journal of International Council on Electrical Engineering 61

(a) Lack of coordination

(b) Better coordination

Figure 11. Ground fault protection coordination curve for MV switchgear.


62 C.-K. Chang

4.4. Ground fault relay coordination current and ground fault level, transient overvoltage and
CTs and relays must be designed such that system will insulation level, fault withstand time and temperature
trip on a fault of the magnitude of the ground fault cur- rise, and ground fault relay coordination.
rent, but not on transient events such as large motor In the high resistance grounding system, NGR must
startup. be sized to flow resistive ground fault current that is
Figure 10 is an example of the ground fault protec- greater than capacitive charging current and the system
tion scheme for the Class 1E 4.16kV Switchgear fed is not subject to destructive transient overvoltage. On the
from Unit Auxiliary Transformer (UAT) in a nuclear other hand, in the low resistance grounding system,
power plant. Secondary side neutral of the UAT is ground fault current level and selectivity of ground fault
grounded with the NGR. In this example system, NGR relays are more critical to determine NGR rating than
rating is 2.15063 Ω and maximum fault current is 1200 other parameters.
A. The maximum fault current was decided to a value In the case study, system ground fault relay (51G)
equal to the rated current of X winding at ONAN rating. was set at 13.3% (160 A) of the NGR rating and selec-
X and Y windings use the same size of resistance for the tive tripping was possible through the coordination with
convenience of design and maintenance. branch feeder’s relay of the 4.16 kV SWGR. Therefore,
Figure 11 is the time current characteristic curves of the NGR rating satisfies the requirements specified in
ground protection relays showing the coordination Sections 4.1–4.4. The transformer neutral CT is 1200/
between upstream and downstream relays. The time 400 multi-ratio type and 400 A CT is preferred for refer-
overcurrent relay (51G) installed on the grounded neutral ence system for more reliable protection. If the NGR rat-
of a transformer is set to minimum values of current ing is greater than 1200 A, it is inevitable to allow
pickup but not less than 10% of NGR rating and time higher ground fault current in the circuit. However, if the
delay to be selective with downstream feeder ground NGR rating is smaller than 1200 A, coordination
fault relays. Accordingly, about 160 A is appropriate to between downstream 51N relays are difficult or fault
set 51G relay to make coordination with the 4.16 kV detection in high impedance ground fault is insensitive.
SWGR branch feeder ground fault relays which are set
at 20 A and 120 A as explained in below. The ground
6. Conclusion
protection relays installed on the incoming feeder of
switchgears are residual type (51N). Usually the importance of NGR rating is overlooked
In Figure 11(a), the 51N relay of the Class 1E 4.16kV because NGR is ordered in the early stage of the project
SWGR was set at 120 A for the coordination with the with the power transformer which is long lead time
transformer neutral ground protection relay 51G. In that equipment. As a result, in many cases, the rating of
case, 51N(R2) relay’s setting value is only 4% of the CT NGR already installed is not suitable for the proper set-
rating (3000 A) and it may cause undesired tripping of ting and coordination of ground fault protection relays.
the ground relay due to CT error. Relay must not be set Consequently it results in unsatisfactory coordination of
to pick up at less than CT accuracy class. In general, ground fault protection system. Optimal NGR rating
accuracy of the IEEE type protection CT is 10%. determination procedure and verification method pro-
Coordination between 51G(R1) of the UAT neutral posed in this paper will contribute to the design of the
and 51N(R2) of the 4.16 kV SWGR incoming feeder reliable and safe ground protection systems for power
can be sacrificed. However, coordination between 51N generating stations. Additionally, as the power system
(R2) and downstream relays (R3 and R4) should be design progresses and data becomes available, the
maintained as shown in Figure 11(b). grounding system and NGR design should be reviewed
Motor feeders are protected with instantaneous ground and re-evaluated when necessary to ensure that the sys-
overcurrent relay (50G) connected to a core balance CT. tem will perform within the established criteria and
50G(R4) for motor feeder is set at lowest tap and typical design margins. This re-evaluation may be required when
pick-up value is 10–20 A. In the case of an outgoing fee- transformer with NGR proposal is evaluated to check
der for subsidiary 4.16 kV Non Class 1E SWGR, 51N whether the rating proposed by the manufacturer is
(R3) device is used and it must coordinate with upstream acceptable. A final re-evaluation is necessary after NGR
and downstream ground overcurrent relay. The 51N(R3) test data and ground protection relay information are
is set at 120 A. 120 A is 10% of the CT primary rating of available.
1200 A. As a result, the 51N(R3) relay properly coordi-
nates with the upstream relays. Therefore, Figure 11(b) is Acknowledgements
better protection coordination than Figure 11(a). This research was supported by the 2015 Research Fund of the
KEPCO International Nuclear Graduate School (KINGS).

5. Results and discussion


NGR rating in a resistance grounding system must be ORCID
decided considering the above mentioned charging Choong-Koo Chang http://orcid.org/0000-0001-5649-6779
Journal of International Council on Electrical Engineering 63

References for main transformers in Bandar Imam Petrochemical


[1] Blackburn J. Lewis, Domin Thomas J. Protective relaying Complex (BIPC) power station located in south west of
principles and applications. CRC Press Taylor & Francis Iran. Electrical Machines and Systems, ICEMS 2005. Pro-
Group, NW, 2007, p.221. ceedings of the Eighth International Conference, 2005,
[2] Johnson Gerald, Schroeder Mark, Dalke Gerald. A review September 27–29, pp. 2349–2353.
of system grounding methods. Proceedings of the Protec- [8] Siming Hua, Hua Zhang, Feng Qian, Chunjie Chen,
tive Relay Engineers 61st Annual Conference; 2008. Meixia Zhang. The research on neutral grounding scheme
[3] Post GloverTM, Ground fault protection technical guide, of Fengxian 35 kV and 10 kV power grid, Energy and
converting ungrounded systems to high resistance ground- Power Engineering. 2013;5:898.
ing. 2013;2–6. [9] Westinghouse. System neutral grounding and ground fault
[4] IEEE Std 141-1993. IEEE recommended practice for elec- protection. Publication PRSC-4B-1979, Westinghouse,
tric power distribution for industrial plants, pp. 366–367. 1979, pp. 6–10.
[5] IEEE Std 142-1991. IEEE recommended practice for [10] General Electric Co. GE industrial power systems data
grounding of industrial and commercial power systems, book. Schenectady, NY: General Electric; 1964.
pp. 2–6. [11] IEEE Std 666™-2007. IEEE design guide for electric power
[6] IEEE Std C37.101-1993. IEEE guide for generator ground service systems for generating stations, pp. 159–160.
protection, pp. 8–32. [12] GloverTM Post. Grounding for electrical power systems
[7] Izadfar Hamid R, Farsad MR, Davood Andavari, Shokri S. (low resistance and high resistance design). IEEE Baton
Design and calculation of 66 kV neutral grounding resistor Rouge. 2012 May;8:11–16.

You might also like