Professional Documents
Culture Documents
Objective of Earthing
Z S = Z0 + Z4 + R1 + R2 + Z3
Phase conductor
circuit resistance
Protective
conductor circuit
Transformer resistance
Phase
impedance
conductor
impedance
external to
circuit
Installation earth
Source resistance
earth
resistance Z S = Z0 + Z4 + R1 + R2 + RA + RB
LeeCW
Earthing / Lee CW
Earth Electrodes
200,000
100,000
80,000
60,000
40,000
20,000
0 10 20 30 40 50
Classifications of Protective
Conductors
Circuit protective conductor
Main equipotential bonding conductor
Earthing conductor
Supplementary equipotential bonding conductor
26
LeeCW
Earthing / Lee CW
27
LeeCW
Earthing / Lee CW
32
LeeCW
Earthing / Lee CW
33
LeeCW
Earthing / Lee CW
ZE R2
Zs = ZE + (R1 + R2)
LeeCW
Earthing / Lee CW
45
LeeCW
Earthing / Lee CW
230V
For Type 2, Zs (max) = = 32.85/I n
7. I n
230V
For Type 3, Zs (max) = = 23/I n
10. I n
230V
For Type B, Zs (max) = = 46/I n
5. I n
230V
For Type C, Zs (max) = = 23/I n
10. I n
230V
For Type D, Zs (max) = = 11.5/I n 46
20. I n
LeeCW
Earthing / Lee CW
Transformer
Neutral
Earthing conductor
Z s × I ∆n ≤ 50V
Earthing Conductors
The minimum cross-sectional areas of buried earthing
conductors (Table 54A):
Protected against Not protected
mechanical against
damage mechanical
damage
Protected against
corrosion by a Cl 543-01 16 mm2
sheath
Not Protected
against corrosion 25 mm2 25 mm2
54
LeeCW
Earthing / Lee CW
Objective of Bonding
55
LeeCW
Earthing / Lee CW
58
LeeCW
Earthing / Lee CW
62
LeeCW
Earthing / Lee CW
63
LeeCW
Earthing / Lee CW
Design Question 1
A 400/230 V 3-phase circuit is run in single-core
non-armoured copper conductor cable with PVC
insulation, the cross-sectional area of the live
conductors being 16 mm2. The cable is installed
in conduit with cables of other circuits and is
protected against overload and short circuit by a
32 A Type B MCB.
Design Question 2
Design Question 3