Hot Sync
User benefits
• Available for both single- and three -phase products
to meet any mission-critical need up to 2.5 MVA
(400V) systems 20%
Single UPS
Modular UPS
10% Parallel redundant UPS
Hot Sync
The secret here is a patented built-in digital signal processor (DSP) even for a single instant, is an indication of an internal failure,
algorithm, running continuously in each unit. It drives the UPS e.g. a shorted inverter IGBT. In a response the UPS trips immedi-
outputs toward synchronisation and takes care of load sharing. If ately off-line, causing minimal voltage disturbance. This feature is
there is a common bypass available, it is used as valid synchro- known as ‘selective tripping’.
nisation source for output. In the absence of a common bypass,
Hot Sync technology allows full maintenance to be performed
the processor makes subtle adjustments to the inverter frequency
one-by-one on redundant UPS modules without an external main-
on the basis of output power level measurement in order to find
tenance bypass switch. The critical load does not need to be dis-
a common frequency and load balance among the units. There
connected from the conditioned power. Scheduled or unscheduled
exists, as shown in Figure 2, a relationship between the power
maintenance can be performed with the load supported continu-
imbalance and the voltage phase difference.
ously by the UPS-grade clean power.
UPS 1
P1 90
f1 deg
P1+2
UPS 2
P2
f2
V2 Vdiff
P1 Power level difference diminishes Idiff
V1
0 deg
P2
Frequencies are continuously
adjusted based on P1 and P2
Figure 3. A phase displacement between parallel connected UPS volt-
Voltages out of phase Outputs are synchronised ages (V1 and V2) causes current flow between the units thus imbal-
ances load share.
VUPS 1
VUPS 2 Compute
output power pn
In the interests of continuous product improvement all specifications are subject to change without notice. © 2009 Eaton Corporation, All Rights Reserved, 00DATA1018110 rev A, April 2009