N 21025
Page 1 of 12
Low Voltage
Specifications AnomAlert Hardware AnomAlert
Models (≤480
General
Vac)
Information
Tap directly off voltage lines to
Motor Type
motor
Three-phase, AC motors
Medium/High
Fixed speed (line driven) or variable Voltage
speed (inverter driven) AnomAlert
Models (>480Vac)
If variable speed: inverter chopping
frequency must be greater than 2 Fixed speed or scalar controlled
kHz; motor current load and speed VFD: Three Potential Transformers
should not vary by more than 15% (supplied by customer): 1% or
during 6 sec intervals better accuracy; 100 V, 110 V, or
120 V secondary voltages.
Not for use with soft-starter
systems unless they are Vector controlled VFD: Voltage
automatically bypassed divider such that nominal input to
immediately after motor start-up AnomAlert is 100 V to 120 V.
and during subsequent use
Measurement
Operation Type Current Inputs
Continuous Voltage, current,
impedance:
Environmental
Varies by model number. Refer to
Operating Table 2
Temperature
Fixed Speed
32 – 104⁰ F (0 – 40⁰ C) AnomAlert
Models and 1A or
Humidity
5A Variable
Up to 90% RH, non-condensing Speed Models
Inputs Three Current Transformers
(supplied by customer): 1% or
Note: Current and voltage
better accuracy, with either 5A or
transformers must meet local
1A secondary outputs depending
standards and regulations. For
on AnomAlert model selected.
North America, transformers must
be certified by an OSHA appointed Variable Speed
NRTL to appropriate product safety (Inverter Driven)
standards such as UL or CSA. AnomAlert
Models
Measurement
Voltage Inputs 3 Hall-effect Current Sensors
(supplied by customer) with 50-400
Voltage:
mA secondary outputs; selection
480 VrmsL-L / 277 VrmsL-N, max, CAT
based on motor to be monitored
II
and AA model chosen. Refer to
Impedance: Table 2.
3.5 MΩ phase-to-phase
Note: Hall-effect Current Sensors
Frequency: need external power sources,
Varies by model number. Refer to generally installed in the motor
Table 1. control panel, too.
Specifications and Ordering Information
Part Number 286754-01
Rev. K (07/15)
Page 2 of 12
Power Input Mounting
Required
Front Panel Mounting (indoor)
Use UL listed fuse with proper
Protection Class
voltage rating:
Front Panel: IP 40
100-240 Vac (-15%, +10%), 47 – 64
Hz, 19 VA, 200 mA Whole Unit: IP 20
or Indicators
120-300 Vdc, 19 VA, 200 mA 6 LEDs and LCD Readout
Outputs Keypad
Alarms 6 tactile membrane keys
4 Alarm Compliance & Certifications
Parameters:
EMC:
Line Change (unexpected change in
incoming power) Europe:
Load Change (unexpected change EMC Directive 2004/108/EC
in process)
EN 61326-1: 2006
Examine 1: plan maintenance Measurement Control and
Laboratory Use for Industrial
Examine 2: perform maintenance
Environments
Warnings
Australia/New Zealand:
Any measured or calculated
C-tick
parameter outside its expected
range based on internal data base IEC 61326-1: 2005
and learned mode. Measurement Control and
Laboratory Use for Industrial
Relay
Environments
One assignable relay output, user
Electrical Safety:
programmable; NC/NO contacts
Europe:
Communications
Electrical Safety Directive 2006/95/EC
RS422/485
EN 61010-1 Safety
RS232 (with additional appropriate
Requirements for Electrical
converter)
Equipment
Ethernet (with additional
North America:
appropriate converter)
UL Listed, Canada and US
Physical
UL 61010-1 Safety
Weight
Requirements for Electrical
Line: 2.58 lb (1170 g) Equipment
Inverter: 2.16 lb (980 g) Australia/New Zealand:
Dimensions C-Tick
WxHxL
IEC 61010-1 Safety
3.78 in x 3.78 in x 5.51 in Requirements for Electrical
Equipment
(96 mm x 96 mm x 140 mm)
Page 3 of 12
Specifications AnomAlert Enterprise Communication
Page 4 of 12
Ordering Information AnomAlert Enterprise Software
Must be ordered separately. Order 1 per enterprise computer.
For a detailed listing of country and product specific Refer to Figure 4. Includes ability to change data presentation
approvals, refer to the Approvals Quick Reference from English to Spanish, Portuguese, Russian or Turkish.
Guide (document 108M1756) located at the following Includes step-by-step setup movies, manuals, quick install
website: www.GEmeasurement.com. guides.
Order one AnomAlert per motor to be monitored. Refer 390125-01 AnomAlert Enterprise Software
to Figure 1, Figure 2, and Figure 3.
The CTs, PTs, and CSs are customer supplied. Refer to Note: To bring data into System 1 see datasheet
Measurement Inputs section of Specifications Section 174590-01 to order S1 AnomAlert System Extender.
above for requirements. Quick configuration tool for bringing data into S1 is
available at BN technical support via the following
Order the type and number of converters as required website:
for your network of AnomAlerts. Refer to Figure 4. www.GEmeasurement.com.
Order at least one version of the software. For
integration into System1 refer to datasheet 174590-01 Converter Kits
for the AnomAlert Extender. Up to 10 AnomAlert units can be connected through each
converter to a computer. Refer to Figure 4.
For generator monitoring see AnomAlert datasheet
288496-01. 287127-01
RS 232/485 to RS 422 converter, with
AnomAlert for Fixed Speed Motor power supply and plug adapters. Kit
390100 – AXX – B01 – CXX - D01 includes sample cable for connection to
AnomAlert, and sample cable for
A: Motor Voltage interconnection between converter and
01 Low ( ≤ 480 Vac) PC (1 required for each PC to which daisy-
02 Medium/High ( > 480 Vac) chained AnomAlerts will be connected).
B: Motor Speed Type
01 Fixed (line driven) 287128 – AXX
02 Variable (inverter driven)
C: Motor Nominal Current (CT secondary output) Moxa* Nport* DE-311 RS422 to TCP/IP
01 1A Ethernet converter with null modem mini
02 1-5A adapter and power supply. Kit includes
D: Language sample cable for connection to AnomAlert
01 English and a sample cross-cable for Ethernet
connection.
AnomAlert for Variable Speed Motor
390100 – AXX – B02 – CXX - D01 A: Power Plug Type
01 American (US, Canada, Japan,
A: Motor Voltage Mexico)
01 Low ( ≤ 480 Vac) 02 British (UK, Hong Kong)
02 Medium/High ( > 480 Vac) 03 European (Turkey, Germany,
B: Motor Speed Type Russia…)
01 Fixed (line driven) 04 Australian
02 Variable (inverter driven) 05 China
C: Motor Nominal Current
01 up to 1 A AnomAlert Manuals
02 1-5A
Hardware and software manuals can be found in electronic
03 5 - 100 A
format on the DVD that contains the software itself.
04 100 – 500 A
However, the hardware manual can be ordered in hardcopy
05 500 – 1000 A
format using the following part number, if desired.
06 1000 – 2000 A
D: Language 286869-01 User’s Manual
01 English
Specifications and Ordering Information
Part Number 286754-01
Rev. K (07/15)
Page 5 of 12
AnomAlert Quick Install Guides
Not required to be ordered. Are included in electronic format
on the AnomAlert Enterprise Software DVD and come in
hardcopy with the appropriate monitors and converter kits.
They can also be ordered as hardcopies using the following
part numbers, if required.
286870-01 Low Voltage, Line
286871-01 Low Voltage, Inverter
286872-01 Med/High Voltage, Line Model
286873-01 Med/High Voltage, Inverter Model
286874-01 RS485-RS422
286875-01 TCP/IP
286876-01 Software TCP/IP
Page 6 of 12
Figures and Tables
Page 7 of 12
Figure 2: Model Number Selection: Variable Speed, Low Voltage
Specifications and Ordering Information
Part Number 286754-01
Rev. K (07/15)
Page 8 of 12
Figure 3: Model Number Selection: Variable Speed, Medium Voltage
Specifications and Ordering Information
Part Number 286754-01
Rev. K (07/15)
Page 9 of 12
Specifications and Ordering Information
Part Number 286754-01
Rev. K (07/15)
Page 10 of 12
Specifications and Ordering Information
Part Number 286754-01
Rev. K (07/15)
Page 11 of 12
Figure 4: System Architecture
*Denotes a trademark of Bently Nevada, Inc., a wholly owned subsidiary of General Electric Company:
AnomAlert
Bently Nevada
Page 12 of 12