Calculate Size of Neutral Earthing
Transformer (NET)

FEBRUARY 6, 2018  13 COMMENTS
(HTTPS://ELECTRICALNOTES.WORDPRESS.COM/2018/02/06/CALCULATE‑SIZE‑OF‑NEUTRAL‑
EARTHING‑TRANSFORMER‑NET‑2/#COMMENTS)

Calculate Size of Neutral Earthing Transformer (NET) having following details

 Main Transformer Detail :

Primary Voltage(PVL): 33KV
Secondary Voltage (SVL): 11 KV
Frequency(f)=50Hz
Transformer Capacitance / Phase(c1)=0.006 μ Farad
Transformer Cable Capacitance / Phase(c2)= 0003 μ Farad
Surge Arrestor Capacitance / Phase(c3)=0.25 μ Farad
Other Capacitance / Phase(c4)=0 μ Farad

Required for Neutral Earthing Transformer:

Primary Voltage of the Grounding Transformer (Vp) =11KV
Secondary Voltage of the Grounding Transformer (Vs) =240V
Neutral Earthing Transformer % Reactance (X%)=40%
% of Force field condition for Neutral Earthing Transformer (ff) =30%
Neutral Earthing Transformer overloading factor(Of)=2.6
Neutral Earthing Transformer Base KV (Bv) =240V=0.240KV

Calculation:

Phase to Neutral Voltage (Vp1) =SVL /1.732
Phase to Neutral Voltage (Vp1) =11 /1.732 = 6.35 KV
Phase to Neutral Voltage under Force Field Condition (Vf) =Vp + (Vpxff)
Phase to Neutral Voltage under Force Field Condition (Vf)=6.35+ (6.35×30%) =8.26KV
Total Zero Sequence Capacitance (C)=C1+C2+C3+C4
Total Zero Sequence Capacitance (C)=0.006+0.0003+0.25+0=0.47730 μ Farad
https://electricalnotes.wordpress.com/2018/02/06/calculate­size­of­neutral­earthing­transformer­net­2/ 1/5
10/27/2018 Calculate Size of Neutral Earthing Transformer (NET) | Electrical Notes & Articles

Total Zero Sequence Capacitance (C)=0.006+0.0003+0.25+0=0.47730 μ Farad
Total Zero Sequence Capacitance Reactance to Ground (Xc)=10×6 / (2×3.14xfxC)
Total Zero Sequence Capacitance Reactance to Ground (Xc)=10×6 / (2×3.14x50x0.47730)=6672.35
Ω/Phase
Capacitive charging current/phase (Ic)=Vf / Xc
Capacitive charging current/phase (Ic)=8.26×1000 / 6672.35 = 1.24Amp
Total Capacitive charging current (It) =3xIc
Total Capacitive charging current (It) =3xIc =3×1.24 =3.71Amp
Rating of Neutral Earthing Transformer (Pr)=VpxIt
Rating of Neutral Earthing Transformer (Pr)=11×3.71=40.83KVA
Size of Neutral Earthing Transformer (P)=Pr/ Of
Size of Neutral Earthing Transformer (P)=40.83/ 2.6 = 16KVA
Residual Capacitive reactance (Xct) =Xc/3
l Capacitive reactance (Xct) = 6672.35 /3 =2224.12Ω
Turns Ratio of the Grounding Transformer (N)= Vp/Vs =11000/240 =45.83
Required Grounding Resistor value at Secondary side (Rsec)=Xct/NxN
Required Grounding Resistor value at Secondary side (Rsec)=2224.12 /45.83×45.83 =1.059 Ω
Required Grounding Resistor value at primary side (Rp)=Xct
Grounding Resistor value at primary side (Rp)= 2224.12Ω
Neutral Earthing Transformer Secondary Current=P/Vs
Neutral Earthing Transformer Secondary Current=16000/230= 65.44Amp
Neutral Earthing Transformer Secondary Resistor Current (for 30 Sec)=1.3xItxN
Neutral Earthing Transformer Secondary Resistor Current (for 30 Sec)=1.3×3.71×45.83=221.18Amp
Neutral Earthing Transformer Reactance Base(Base X)=BvxBv/P/1000
Neutral Earthing Transformer Reactance Base(Base X)=0.24×0.24/11/1000=3.67Ω
Neutral Earthing Transformer Reactance in PU (Xpu)=X% =40%=0.04Pu
Neutral Earthing Transformer Reactance (X)=Xpu x BaseX
Neutral Earthing Transformer Reactance (X)=0.04×3.67 =0.15Ω
Neutral Earthing Transformer X/R Ratio=X/Rsec
Neutral Earthing Transformer X/R Ratio=0.15/1.059 = 0.14
Fault current through Neutral (single line to ground fault) (If)=Vp1/Rp
Fault current through Neutral (single line to ground fault) (If)=6.35×1000/2224.12 =2.86Amp
Short time Rating of Neutral Earthing Transformer=PxOf =16×2.6 =41KVA

Result:

Rating of Neutral Earthing Transformer (P)=40.83/ 2.6 = 16KVA
Short time Rating of Neutral Earthing Transformer=41KVA
Ratio of Neutral Earthing Transformer =11000/240 Volt
Neutral Earthing Transformer Secondary Current=65.44A
Required Grounding Resistor value at primary side (Rp)=2224.12Ω
Required Resistance at secondary side (Rsec)= 1.059Ω
Neutral Earthing Transformer Secondary Resistor Current (for 30 Sec)= 221.2A

FILED UNDER UNCATEGORIZED
https://electricalnotes.wordpress.com/2018/02/06/calculate­size­of­neutral­earthing­transformer­net­2/ 2/5
10/27/2018 Calculate Size of Neutral Earthing Transformer (NET) | Electrical Notes & Articles

About Jignesh.Parmar
Jignesh Parmar has completed M.Tech (Power System Control), B.E(Electrical). He is member of
Institution of Engineers (MIE) and CEng,India. Membership No:M‑1473586.He has more than 16 years
experience in Transmission ‑Distribution‑Electrical Energy theft detection‑Electrical Maintenance‑
Electrical Projects (Planning‑Designing‑Technical Review‑coordination ‑Execution). He is Presently
associate with one of the leading business group as a Deputy Manager at Ahmedabad,India. He has
published numbers of Technical Articles in “Electrical Mirror”, “Electrical India”, “Lighting
India”,”Smart Energy”, “Industrial Electrix”(Australian Power Publications) Magazines. He is Freelancer
Programmer of Advance Excel and design useful Excel base Electrical Programs as per IS, NEC,
IEC,IEEE codes. He is Technical Blogger and Familiar with English, Hindi, Gujarati, French languages.
He wants to Share his experience & Knowledge and help technical enthusiasts to find suitable solutions
and updating themselves on various Engineering Topics.

13 Responses to Calculate Size of Neutral Earthing
Transformer (NET)

bala raman says:
February 6, 2018 at 5:14 pm
Dear sir,             ATS   (auto transfer switch) symbol fill  in Single line diagram

Thanks&Regards K.Balaraman Ayyan electricals 9840768817

Reply
Jignesh.Parmar says:
February 6, 2018 at 5:27 pm
????

Reply
isaac chibwe says:
February 6, 2018 at 6:45 pm
Thank you , Sir Jignesh .regard isaac chibwe ampnet electrical services.

Reply
Dennis says:
February 6, 2018 at 10:00 pm
This could be a great guide for electrical engineers looking to calculate the size of a neutral earthing
transformer. It’s awesome that you listed the specific calculations for the voltages and frequencies for
the main transformer. This information could be helpful for technicians who are running data
centers, and looking for the exact voltage to get the job done. Thank you for such precise breakdown
of the numbers!

Reply
Shiv kumar says:
February 7, 2018 at 3:14 am
Very good knowledge sir

Reply
https://electricalnotes.wordpress.com/2018/02/06/calculate­size­of­neutral­earthing­transformer­net­2/ 3/5
10/27/2018 Calculate Size of Neutral Earthing Transformer (NET) | Electrical Notes & Articles

Reply
Vivekanand Pandey says:
February 7, 2018 at 10:26 am
Thank you sir for value able post

Reply
Anthony Dickson Ojih says:
February 7, 2018 at 4:36 pm
Kindly explain how you get the factors used in calculating the value of Xc

Reply
N.dhetchinamoorthy says:
February 8, 2018 at 9:34 am
Please help HV to trive vector meter multification factor Formula

Reply
Tarek Aboukhadra says:
February 9, 2018 at 10:33 am
Dear Jignesh.Parmar
thanks for your explaniation
but what is the base for your equations which used in the calculation
thanks again

Reply
Mohammed Rafi says:
February 16, 2018 at 4:25 pm
Sir, Here i found that the grounding transformer has secondary voltage. how can the grounding
transformer have secondary winding. please reply

Reply
Md. Mostaq says:
February 18, 2018 at 1:10 am
ok, Thank you. But how can we calculate the three phase four wire (star) AC impedance (resistance
& reactance). Please give me answer.

Reply
Pankaj Pal says:
February 22, 2018 at 4:00 pm
Hello Jignesh sir how to calculate the connected load of passenger lift ( 8 persons). Please ,will wait
for your reply.

Reply
Rafael says:
April 15, 2018 at 1:19 am
Hello Mr. Jignesh: Why is the earthing transformer primary voltage (11 kV) a third of the three phase
main transformer primary voltage (33 kV)? I have seem that many other authors say that it has to be
the line to ground voltage of the main transformer (33 kV/1,73)

Reply

https://electricalnotes.wordpress.com/2018/02/06/calculate­size­of­neutral­earthing­transformer­net­2/ 4/5
10/27/2018 Calculate Size of Neutral Earthing Transformer (NET) | Electrical Notes & Articles

https://electricalnotes.wordpress.com/2018/02/06/calculate­size­of­neutral­earthing­transformer­net­2/ 5/5

You might also like