Professional Documents
Culture Documents
Miscellaneous
Objectives
Introduction
Q-meters are designed to measure effective Quality Factor of a coil without measuring the
inductance and resistance of that coil separately. It is very useful in measuring characteristics
of coils and capacitors.
The Transformers used in conjunction with measuring instruments for the purpose of
enhancement of the range of an instrument. High Current and Voltage measurement directly
may be uneconomical and hence these must be stepped down before measurement.
Potentiometer/Null detector
Potentiometer is a null detector type of Instrument i.e. we get the measurement when the
galvanometer shows zero deflection. So, a big advantage of Potentiometer is that no current
flows in the circuit containing unknown cell and hence no energy is consumed from that cell.
Vx V2
V2 R 2 l2
V1 R1 l1
If l1 1m & l2 60cm
60
Vx 10 6V
100
Practical Arrangement
Iw Working current
VB
Iw , where l = length of slide wire having a resistance r per unit length
R w l.r
Applications of Potentiometer
It is used to measure
1) Unknown battery voltages
2) Low values of Resistances
3) Non-electrical quantities like displacement, pressure, force etc.
It is also used for Calibration of voltmeter, Ammeter and Wattmeter.
The arrangement for measurement of low resistances is shown in the figure below. The basic
idea behind this arrangement is to convert the value of resistance into an equivalent voltage
which can then be measured using Potentiometer.
Here, we consider two resistances out of which one is a Standard Resistance S and other is
an unknown resistance R. This method also works on the principle of comparison of these
two values.
VR l
Hence, R .S R .S
Vs ls
Solved Examples
Problem: A potentiometer using a standard cell of 2V and has a slide wire has a length of
2m, the standard cell is balanced at 150cm position of slide wire, the low resistance is
measured using potentiometer and voltage across this low resistance is balanced at 125cm
and the voltage across standard resistance of 2.5mΩ is balanced at 175cm. Find unknown
resistance.
lR 125
Hence, R .S 2.5 1.785 mΩ
ls 175
V2 l2
Solution:
V1 l1
V2 680
1.18 600
680
V2 x1.18 1.337 V
600
Q-meter works on the principle of series resonance. The test coil is connected in series with a
variable capacitor and by varying the capacitance the circuit is resonated and the voltmeter
across the capacitor is calibrated in terms of Q of the coil.
At Series Resonance
XL X C
V
I
R
VX c VXL
Vc IXc
R R
Quality Factor of the coil is given by,
L X L
Q
R R
Hence, VC V.Q where V=constant
Therefore, Vc Q
Applications
Q meter is used to measure
1. unknown Q of the coil
2. unknown capacitance
3. distributed or self-capacitance of a coil
4. unknown inductance from a measured Q value
Practical Q-meter
The practical arrangement of a Q-meter is shown in the figure below. The test coil is
connected between T1 and T2 and the variable capacitor is connected between T3 and T4. The
circuit is resonated using an oscillator which may also have a shunt resistance of its own as
shown in the figure.
To reduce the error in the measurement of Q of the coil, the series resistance of oscillator is
maintained low value in mΩ range.
1
f
2 L(C1 CT )
Now we remove the unknown capacitance and the vary the capacitance C to obtain
resonance condition. Assuming under resonance condition C C2
1
f
2 LC2
Since, source remains as it is so resonance frequency is also same in both cases. Hence by
comparison we can say,
C1 CT C2
Test capacitance CT C2 C1
The electrical model of a coil having a self or distributed capacitance is shown below,
Ideal Model,
At High Frequencies,
1
f1
2 L(C1 Cd )
1
f2 nf1
2 L(C2 Cd )
1 n
2 (L(C2 Cd )) 2 (L(C1 Cd ))
C1 n2C2
Cd
n2 1
Solved Examples
Problem: A reading of 120 is obtained when a standard inductor was connected in the
circuit of a Q-meter and the variable capacitor is adjusted to a value of 300 pF. A lossless
capacitor of unknown value C, is then connected and the same reading was obtained when
the variable capacitor is readjusted to a value of 200 pF. The value of Cx in pF is?
Instrument Transformers
Also, when dealing with large currents and voltages the power loss in these resistances is
very high. So, insulation of these instruments also poses a challenge.
Instrument Transformers step down currents and voltages considerably so that they can
be measured by Instruments of moderate size.
Current Transformers are used for stepping down the current and Potential Transformers
are used for stepping down the voltages.
The relation between currents and voltages on two sides of Transformer is given by,
N2 V2 I1
N1 V1 I2
Current Transformer
The figure below shows the typical arrangement of a Current Transformer with multiple
secondary windings with different devices connected across different windings. The second
figure shows the representation of Current Transformer.
Since, Current Transformer is used to step down the current, primary winding has single
turn and multiple secondary turns. It is also termed as bar primary.
The standard secondary current of Current Transformer is 1A or 5A.
Lower the current rating of the Current Transformer lower the power consumption so
higher the sensitivity of Current Transformer.
When primary is excited, secondary of Current Transformer cannot be open circuited
because there is no opposing flux produced to the primary flux and hence high voltage is
induced on the secondary which is very dangerous to the people working nearer to the
Current Transformer.
N2 XL X s
Turns Ratio, n tan1( )
N1 RL R s
Ip N2
Nominal ratio=k=
Is N1
From the phasor diagram shown below,
OC2 OB2 BC2
(OA AB)2 BC2
Ip2 [nIs Io sin( )]2 [Io cos( )]2
Ip2 [n2I2s I2o sin2 ( ) 2nIsIo sin( ) I2o cos2 ( )]
Ip2 [n2I2s I2o 2nIsIo sin( )]
Assume Io 2 n2I2o
Ip2 [n2I2o 2nIsIo sin( )]
Ip [n2I2s 2nIsIo sin( )]1/2
2Io
IP nIs [1 sin( )]1/2
nIs
x
By Binomial expansion, (1 x)1/2 1
2
Io
Ip nIs [1 sin( )]
nIs
nIs Io sin( )
Ip Io sin( )
R n
Is Is
Ip Io sin cos Io cos sin
R n
Is Is
Iw cos I sin
R n
Is
Ratio error
The turns ratio of Current Transformer is not equal to the current ratio due to no-load
component of the current Io . The difference between the two quantities is termed as Ratio
Error.
K R
%r 100
R
N2
K=nominal ratio n
N1
Ip Iw cos I sin
R= Actual ratio n
Is Is
BC BC
tan
OB OA AB
Io cos( )
=
nIs Io sin( )
Assume: Io sin( ) nIs , tan
Io cos( )
nIs
Io cos cos Io sin sin
nIs
I cos Iw sin
...... Radians
nIs
I cos Iw sin 180
……degrees
nIs
Phase angle between Ip &Is (180 )
Potential Transformer
The figure shown below shows the schematic arrangement of a Potential Transformer.
This type of construction is called as Core Type Transformer.
The two windings of Transformer are wound on two legs of the core.
The fluxes produced by Primary and Secondary windings are shown by dotted lines and as
can be seen flux produced by Secondary winding opposes the flux produced by Primary
winding.
Equivalent Circuit
This circuit is similar to Equivalent Circuit of Current Transformer and the terminologies used
are mentioned below,
N1
Turns ratio=n=
N2
Vp
Actual transformation ratio=R=
VS
N1
Nominal ratio=K=
N2
Xl
Rp (n2R s Rp ) tan1( )
Rl
Xp (n2 XS Xp )
Ratio Error
Actual Transformation Ratio is given by,
Is
(R p cos Xp sin ) Iwrp I X p
R n n
Vs
So, ratio error is
K R
Ratio error= 100
R
By using strip wound core or toroidal core the numbers of core joints are reduced so that
reluctance is minimized which causes Io to reduce and hence Ratio Error and Phase angle
error are minimized.
By reducing distance between primary and secondary turns, the air leakage flux is minimized
and hence total flux is reduced which causes reduction in Magnetizing Current so that Io is
minimized.
For reducing the Ratio and Phase Angle Error, Primary Current has to be increased.
Io cos( )
Phase Angle Error,
Ip
So, as Primary Current increases Phase Angle Error decreases.
Io sin( ) I sin( )
R n n o
Is nIP
Io sin( )
R n
nIP
As, Primary Current increases the difference between Actual ratio and Nominal Ratio
decreases so that Ratio Error decreases.
To increase Primary Current we decrease primary Number of Turns and hence we use N1 1
i.e. bar primary.
Turns Compensation
It is used to compensate ratio error only. If the number of turns on the secondary are
reduced for reducing the value then Actual Ratio is reduced so that it becomes closer to the
Nominal Ratio.
Solved Examples
Problem: A 500 A/5 A, 50 Hz current transformer has a bar primary. The secondary burden is
a pure resistance of 1 and it draws a current of 5A. If the magnetic core requires 250 AT for
magnetization, the percentage ratio error is?
Primary Turns = 1
Magnetizing Current = 250 A
Problem: A 200 / 1 Current transformer (CT) is wound with 200 turns on the secondary on a
toroidal core. When it carries a current of 160 A on the primary, the ratio and phase errors of
the CT are found to be 50% and 30 minutes respectively. If the number of secondary turns
is reduced by 1 the new ratio error (%) and phase error (min) will be respectively.
I 0 cos ( )
Solution: R = n +
IS
Where, R = Transformation ratio and n = Turns ratio
I cos ( )
R = 200 + 0 [assume = 0 ]
IS
nominal ratio transformation ratio
% ratio error = 100
Transformation ratio
Kn R
0.5 = 100
R
0.5 R = 100 Kn 100 R [ Kn = 200]
I0 cos ( )
R = 201= 200 + 1=200 +
IS
I0 cos ( )
=1
IS
When Secondary Turns are reduced it does not affect much the Phase Angle Error
So, Phase Angle Error = 30 min